Professional Documents
Culture Documents
Version 1.0 EN
Confidential
ST3956kWh-1375UD Technical Diagrams
1. Introduction
This document describes the technical diagrams and auxiliary power consumption for the
ST3956kWh-1375UD for Cairo 3A project .
This document is intended to be used by the specific addressees. No part of this document may
be reproduced or distributed in any form or by any means without the prior written permission of
Sungrow Power Supply Co., Ltd.
Item Parameter
Cycle/year 365
Life time 20
Resting SOC(%) 50
2
Confidential
ST3956kWh-1375UD Technical Diagrams
Year 0 1 2 3 4 5 6 7 8 9
SOH % 100% 94.85% 92.33% 90.30% 88.54% 86.96% 85.51% 84.15% 82.87% 81.65%
DOD% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
Total AC Usable 3.831 3.540 3.445 3.370 3.298 3.239 3.186 3.134 3.087 3.041
Capacity(MWh)
System RTE 89.95% 89.73% 89.64% 89.58% 89.50% 89.45% 89.39% 89.34% 89.30% 89.23%
Year 10 11 12 13 14 15 16 17 18 19 20
SOH % 80.49% 79.38% 78.30% 77.27% 76.26% 75.29% 74.34% 73.41% 72.51% 71.62% 70.76%
DOD% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
TotalAC 2.998 2.948 2.909 2.871 2.833 2.796 2.762 2.727 2.693 2.661 2.629
Usable
Capacity(M
Wh)
System RTE 89.20% 89.14% 89.10% 89.05% 89.00% 88.93% 88.92% 88.89% 88.85% 88.79% 88.76%
Notes :
*The ambient temperature assumption is constant for every case and is equal to 23℃ internal
temperature.
*This set of indicative degradation curve is non-binding and is only provided for indication to help
customers in their early project development activities and preliminary ESS battery sizing.
3
Confidential
ST3956kWh-1375UD Technical Diagrams
SOH&RTE %
110.00%
90.00%
80.00%
70.00%
60.00%
50.00%
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
4.000
3.500
3.000
2.500
0.000
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
4
Confidential
ST3956kWh-1375UD Technical Diagrams
1 Battery Unit
2.47 kW Standby
6.87 kW Standby