You are on page 1of 5

Karm Solar – Cairo 3A BESS

Technical Diagrams & Auxiliary Loads

Version 1.0 EN
Confidential
ST3956kWh-1375UD Technical Diagrams

1. Introduction
This document describes the technical diagrams and auxiliary power consumption for the
ST3956kWh-1375UD for Cairo 3A project .

This document is intended to be used by the specific addressees. No part of this document may
be reproduced or distributed in any form or by any means without the prior written permission of
Sungrow Power Supply Co., Ltd.

2. Degradation Simulation for 20 years


The following inputs are taken in consideration in building our simulation.

Item Parameter
Cycle/year 365
Life time 20

Resting SOC(%) 50

System power (MW) 1MW


PCS model SC1375UD
C-rate 0.25
Cell capacity (Ah) 280
Module configuration,series 16
Module configuration,parallel 1
Module No. per rack 23
Rack No. per container 12
Container capacity (Ah) 280
Container energy (MWh) 3.957
Container No. 1
Init. nameplate capacity (MWh) 3.957
DOD 100.00%
Shipment/Storage Time (Month) 3
Storage Retention 100.00%
PCS 98.30%

MVT efficiency 98.70%

LV line efficiency 99.90%

MV line efficiency 99.90%

Aux. consumption (MWh) External power supply

2
Confidential
ST3956kWh-1375UD Technical Diagrams

The following table is the result of the above mentioned inputs :

Year 0 1 2 3 4 5 6 7 8 9

SOH % 100% 94.85% 92.33% 90.30% 88.54% 86.96% 85.51% 84.15% 82.87% 81.65%

DOD% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%

Total AC Usable 3.831 3.540 3.445 3.370 3.298 3.239 3.186 3.134 3.087 3.041
Capacity(MWh)

System RTE 89.95% 89.73% 89.64% 89.58% 89.50% 89.45% 89.39% 89.34% 89.30% 89.23%

Year 10 11 12 13 14 15 16 17 18 19 20

SOH % 80.49% 79.38% 78.30% 77.27% 76.26% 75.29% 74.34% 73.41% 72.51% 71.62% 70.76%

DOD% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%

TotalAC 2.998 2.948 2.909 2.871 2.833 2.796 2.762 2.727 2.693 2.661 2.629
Usable
Capacity(M
Wh)

System RTE 89.20% 89.14% 89.10% 89.05% 89.00% 88.93% 88.92% 88.89% 88.85% 88.79% 88.76%

Notes :

*The ambient temperature assumption is constant for every case and is equal to 23℃ internal
temperature.

*SOH after 15 years is just for reference only .

*This set of indicative degradation curve is non-binding and is only provided for indication to help
customers in their early project development activities and preliminary ESS battery sizing.

3
Confidential
ST3956kWh-1375UD Technical Diagrams

Figure (1) : SOH&RTE vs. No. Of Years

SOH&RTE %
110.00%

100.00% SOH System RTE

90.00%

80.00%

70.00%

60.00%

50.00%
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Figure (2) : Energy Capacity vs. No. Of Years

Energy Capa. (MWh)


4.500

4.000

3.500

3.000

2.500

2.000 Total Nameplate Capc. (MWh)


1.500 Total DC Usable Capa. (MWh)
1.000
Total AC Usable Capa. (MWh)
0.500

0.000
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

4
Confidential
ST3956kWh-1375UD Technical Diagrams

3.Auxiliary Loads Consumption Table (Based on 45 degrees operation)

No. Item Average Unit System Status


Value

1 Battery Unit

1.1 Battery S/G 0.32 kW

1.2 Battery Fan 6.17 kW Running

2.47 kW Standby

1.3 HVAC 15.55 kW Running

6.87 kW Standby

1.4 FFS 0.12 kW

1.5 UPS 0.17 kW

1.6 Controller 0.19 kW

ESS operation 22.44 kW

ESS Standby 10.05 kW

ESS Self Consumption per day 350.23 kWh