00 Calculation Sheet of HVAC Cooling Load
00 Calculation Sheet of HVAC Cooling Load
The calculation of infiltration heat consists of two parts: the infiltration heat caused by the
temperature difference between the inside and outside of smart string ESS container, and the
The calculation of the temperature difference infiltration heat is related comprehensive heat
Temperature difference between the inside and outside of the container: 45℃-25℃=20 ℃
96m)=78.64 m2
The calculation of the temperature difference infiltration heat is related comprehensive heat
transfer coefficient, thermal conductivity area of container, solar radiation intensity, and solar
radiation absorptivity.
96m)=78.64 m2
The cooling load of HVAC = 1.1 * (Heat generation of infiltration + heat generation of battery
2. Specification of HVAC
3. Conclusion
HVACs, so the cooling capability of HVACs can satisfy the cooling load of the system.