When system in error status, the outdoor unit or indoor unit can
display the error code:
In the indoor PCB, there’s LED for error code display;
In the outdoor unit display board, it will display the error code.
E1
Outdoor unit Error Code
dF
dF: when in defrost mode,
it display “dF”
Outdoor unit Error Code
No
H1 to H1, H2 to H2?
Check the connection of
Yes
Open or short circuit? communication wire Reconnect or change
between outdoor units: communication wire.
Shielding wire?
No
Correct direction?
No
Correct direction?
Connect to the
transferring cable of
lower pressure
switch, i.e. the
original port of low
pressure switch. To Port Plug to here
95, 98
Note:
The logic is:
R——Phase A
Serial in the protector output signal to the Low pressure switch,
S——Phase B
When phase sequence error or lack of phase, the Outdoor PCB will display E1 or P2.
T——Phase C
Outdoor unit trouble shooting
E2: Communication Error Displayed quantity of
between Outdoor Unit and indoor units is not
Indoor Units stable
Check if sensor is
Open or short circuit Error
damaged Change a
new sensor
Temp. Resistor value
(℃) (KΩ ) OK
25 10
35 6.4 Check chip or
outdoor PCB
Outdoor unit trouble shooting
E9: Voltage too high or low,
Check chip
or outdoor
PCB
Outdoor unit trouble shooting
OK
Check chip or
outdoor PCB
Outdoor unit trouble shooting
P0, P4: High discharge temp.(P0
Charge additional refrigerant only for inverter compressor
correctly? Refrigerant leakage? Repair the leakage &
Too close between outdoor Lack of refrigerant
Error Charge refrigerant;
units? Outdoor fan is broken?
Short circuit between discharge
OK
air and suction air? Error
Clear the coil and
Too dirty of outdoor coil? High ambient temp or Heat- revise the wrong
exchanger of outdoor unit is bad points
Too many indoor units? OK
Error Reduce the quantity
Check if the cooling load or total capacity of
Total capacity of indoor unit is is too big
too big? indoor units
OK
Error
Discharge refrigerant,
High temp. of discharge and There is Air or N2
vacuum, recharge
suction, big operation current? in the system
refrigerant.
OK
Check sensor,
chip or outdoor
PCB
Outdoor unit trouble shooting
P1: High-pressure Protection
Too close between outdoor
units? Outdoor fan is broken?
Heat exchange of
Short circuit between discharge Error Check and repair
outdoor unit is not good
air and suction air?
one by one
Too dirty of outdoor coil?
OK
low temp. of discharge, low Too many refrigerant in Error Discharge some
pressure and high pressure is the system refrigerant from
high? Big current? system
OK
Check sensor,
chip or PCB
Outdoor unit trouble shooting
P2: Low-pressure Protection
Charge additional refrigerant Lack refrigerant Error Repair the leakage &
correctly? Refrigerant leakage? Charge refrigerant;
OK
Gas pipe is blocked?
Gas valve is not opened
High temp. of discharge and Check gas side of system Error Remove the dirty;
suction, low operation current, Open the valve
low pressure is low?
OK
Check chip
or PCB
Outdoor unit trouble shooting
P3,P7,P8: current protection of
compressor
Heat exchange of
outdoor unit is not good
OK
There is Air or N2
in the system
OK
Short circuit of strong
power part? Too much refrigerant in
the system
Compressor malfunction? OK
The normal resistance between Error Replace the
Compressor or strong
any two terminals of compressor or other
power part is abnormal
compressor is 1~3Ω damaged part.
OK
Heat exchange of
outdoor unit is not good
OK
ok
Check the liquid side of Check outdoor fan motor
system, jam?
Outdoor unit trouble shooting
P6: Inverter module protection
Compressor malfunction?
OK
Check chip
or PCB
Indoor unit trouble shooting
Indoor coil outlet temp. Check the connection Well connected the
Error
sensor T2B port between sensor and sensor and PCB
PCB is loosed or not?
No
Check IU
chip or
Replace IU
PCB chip or PCB
System trouble analysis
Poor performance wrong selection of refrigerant pipe, indoor EXV or
branch joint, the refrigerant distribution among
the indoor units is quite imbalance;
Capacity (x
22 28 36 45 56 71 80 90 112 140
100W)
Horsepower
0.8 1.0 1.2 1.6 2.0 2.5 3.0 3.2 4.0 5.0
(HP)
In the below example:
Operation and Alarm lamp is constant-on.
The capacity code = 8+1=9
Continue pressing the
“manual” button” of indoor
unit for 10s, the capacity
code of this indoor unit will
display.
8 4 2 1
System trouble analysis
OK
Indoor EXV jammed?
Indoor fan doesn’t run?
Check low pressure Error Clean the indoor unit;
Filter or coil of indoor unit is too Fix the broken part
dirty?
OK