You are on page 1of 38

PROCEDURE

FOR

RADIOGRAPHIC TESTING FOR PRESSURE VESSEL, BOILER AND PIPING

(GAMMA RAY)

……………………………………….
QA/QC Manager

Document No : ExWI‐NDT‐22113 Page : 1 of 38 Revise No: 00 Issue Date: June 1, 2022

Prepared By Reviewed and Approved By

Signature

Name Mr. Sorrawut Sarncharoen Mr. Wichan Chunta

Position NDT Division Manager NDE Level III

Sign Date June 1, 2022 June 1, 2022

Copy
Assigned to client Total Page
No.
38

Correction History

00 June 1, 2022 First Issue for ASME 2021 Edition


Revise No. Revise Date Description
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 2 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

TABLE OF CONTENTS

1.0 SCOPE 3‐3


2.0 PERSONNEL 3‐3
3.0 REFERENCE 3‐3
4.0 EQUIPMENT AND CONSUMABLE 3‐5
5.0 TECHNIQUE 5‐8
6.0 LOCATION MARKERS AND FILM IDENTIFICATION 8‐10
7.0 GEOMETRIC UNSHARPNESS 10‐10
8.0 EVALUATION OF RADIOGRAPHY QUALITY 10‐12
9.0 ACCEPTANCE CRITERIA 12‐12
10.0 DOCUMENTATION 12‐13
ATTACHMENT NO. I : RADIOGRAPHIC TESTING REPORT 14‐14
ATTACHMENT NO. II : SAFETY PROCEDURE 15‐18
ATTACHMENT NO. III : ACCEPTANCE CRITERIA 18‐40
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 3 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

1.0 SCOPE
This Radiographic testing procedure is applied for weldments and base material of carbon
steel, stainless steel, alloy steel, nickel steel and aluminum in the thickness range up to 75
mm by Gamma radiation.

2.0 PERSONNEL
2.1 Personnel performing this testing shall be qualified in accordance with Qualitech
Written Practice, which is in accordance with the guidelines of the SNT-TC-1 A or
equivalent.
2.2 Level I personnel may perform radiography and at least a Level II personnel shall
evaluate the results, interpret and make endorsed signature on the reports.

3.0 REFERENCE
3.1 ASNT Recommended Practice No SNT-TC-1A, 2006 & 2016 Edition.
3.2 ASME SECTION V, Article 2 “Nondestructive Examination, Radiographic Examination”
2021 Edition.
3.3 ASME SECTION I “Rules for Construction of Power Boilers” 2021 Edition.
3.4 ASME SECTION VIII Div.1 “Rules for Construction of Pressure Vessels” 2021 Edition.
3.5 ASME SECTION VIII Div.2 Alternative Rules “Rule for Construction of Pressure Vessels”
2021 Edition.
3.1 ASME B31.3 “Process Piping” 2020 Edition.
3.6 Client Project Specification

4.0 EQUIPMENT AND CONSUMABLE MATERIALS


4.1 Radiation
 Gamma Radiation
Isotopes : Iridium 192 or Selenium 75
Focal Spot Size : 3.0 X 3.0 mm. or 2.5 X 3.0 mm
4.2 Film
 Radiographic film shall be industrial radiographic film. The selection of film type
shall be based on the type of radiation source, type of materials, and their thickness
to be radiographed.
 Radiographic film shall be fine grain, high definition and high contrast
4.3 Screens
Lead intensifying screens with minimum 0.027 mm o f thickness for front and back
screens shall be used in each holder. Fluorescent screens are not used.
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 4 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

4.4 The Image Quality Indication (IQI)


The wire type IQI(s) to be used is in accordance with ASTM E‐747. The IQI(s) shall be
made from the same alloy material group or grade as identified SE‐747, or from an
alloy material group or grade with less radiation absorption than the material being
radiographed. Diameter of IQI for wire type shall be follow T‐233.2.
The designated essential wire IQI shall be as specified in Table T‐276 of ASME section
V. For wire type IQI, smaller diameter wire may be substituted for the essential wire
required for any thickness listed
TABLE T‐233.2
WIRE IQI DESIGNATION, WIRE DIAMETER AND WIRE IDENTITY

Set A Set B
Wire Wire Wire Wire
(mm.) (mm.)
Diameter,in. Identity Diameter,in. Identity
0.0032 (0.08) 1 0.010 (0.25) 6
0.004 (0.10) 2 0.013 (0.33) 7
0.005 (0.13) 3 0.016 (0.41) 8
0.0063 (0.16) 4 0.020 (0.51) 9
0.008 (0.20) 5 0.025 (0.64) 10
0.010 (0.25) 6 0.032 (0.81) 11

Set C Set D
Wire (mm.) Wire Wire (mm.) Wire
Diameter,in. Identity Diameter,in. Identity
0.032 (0.81) 11 0.100 (2.54) 16
0.040 (1.02) 12 0.126 (3.20) 17
0.050 (1.27) 13 0.160 (4.06) 18
0.063 (1.60) 14 0.200 (5.08) 19
0.080 (2.03) 15 0.250 (6.35) 20
0.100 (2.54) 16 0.320 (8.13) 21

4.5 Viewing Facilities


Viewing facilities shall provide subdued background lighting of an intensity that will not
cause reflections, shadows, or glare on the radiograph that interfere with the
interpretation process. Equipment used to view radiographs for interpretation shall
provide a variable light source sufficient for the designated wire to be visible for the
specified density range. The viewing conditions shall be such that light from around
the outer edge of the radiograph or coming through low‐density portions of the
radiograph does not interfere with interpretation.

4.6 Film Processing Standard guide for radiographic examination using industrial
radiographic film, SE 94 shall be used to manually process the exposed films. The
chemical used for Film processing shall be identical to the film manufacturer.
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 5 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

5.0 TECHNIQUE
5.1 Surface preparation
Prepare the weld surface by removing weld ripples or weld profile irregularities on
both sides (where accessible) by any suitable process to such a degree that the
resulting radiographic image due to any irregularities can not mask or be confused
with the image of any discontinuity. The finished surface of all butt‐welded joints may
have reasonably uniform crowns, with reinforcement on each side of all butt‐welded
joints.The weld reinforcement shall not exceed the applicable standard specified
values.
5.2 Radiographs shall be made with a single source of radiation centered as near as
practicable with respect to the length and width of that portion of the weld being
examined.
5.3 A single wall exposure technique shall be used whenever practical, when it is not
practical to use a single wall technique, a double wall technique shall be used. An
adequate number of exposures shall be made to demonstrate that the required
coverage has been obtained.
5.4 IQI(s) selection, placement and number.
5.4.1 The IQI(s) shall be selected and placed across the length of the weld or in the
area of interest being radiographed
a) For welds without reinforcement.
The thickness on which the IQI(s) will be based is the nominal single wall
thickness. Backing rings or strips are not to be considered as part of the
weld thickness.
b) For welds with reinforcement.
The thickness on which the IQI(s) will be selected will be based on the
nominal single wall material thickness plus the weld reinforcement
thickness estimated to be present on both sides of the weld (I.D and O.D).
The values used for the estimated weld reinforcement thickness shall be
representative of the weld conditions and shall not exceed the maximum
permitted by the referencing code section. Physical measurement of the
actual weld reinforcements is not required. Backing rings or strips shall not
be considered as part of the thickness in IQI selection.
5.4.2 Joining Dissimilar Materials or Welds with Dissimilar Filler Metal. When the
weld metal is of an alloy group or grade that has a radiation attenuation that
differs from the base material, the IQI material selection shall be based on the
weld metal and be in accordance with T‐276.1. When the density limits of T‐
282.2 cannot be met with one IQI, and the exceptional density area(s) is at the
interface of the weld metal and the base metal, the material selection for the
additional IQI shall be based on the base material and be in accordance with T‐
276.1
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 6 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

5.4.3 The number of IQI(s) to be used shall be in accordance with T‐277.2 of ASME V,
which is based on the length of radiographed, nominal base metal thickness,
type of structures tubular of nontubular, etc.
5 .4 .4 IQI shall be placed on source side of the part being examined, except for the
condition describe in 5.4.5
When, due to part or weld configuration or size, it is not practical to place the
IQI(s) on the part or weld, the IQI(s) may be placed on a separate block.
Separate blocks shall be made of the same or radiographically similar materials
(as defined in SE‐1025 for hole type or SE‐747 for wire type) and may be used
to facilitate IQI positioning. There is no restriction on the separate block
thickness, provided the IQI/area‐of‐interest density tolerance requirements of
s e ct i on 8 .1 o f th i s p r oce du re are met

5.4.5 Where inaccessibility prevents hand placing the IQI(s) on the source side, the
IQI(s) shall be place on the film side in contact with the part being examined. A
letter “F” shall be place adjacent to or on the IQI(s).
5.4.6 Placement for Welds – Wire IQIs. The IQI(s) shall be placed on the weld so that
the length of the wires a r e t r an s ve r se to t h e l on g i t u d in a l axis of the weld. The
identification numbers and, when used, the lead letter “F,” shall not be in the
area of interest, except when geometric configuration makes it impractical
5.4.7 IQI Placement for Materials Other Than Welds. The IQI(s) with the IQI
identification number(s), and, when used, the lead letter “F,” shall be placed in
the area of interest
5.4.8 Number of IQIs. When one or more film holders are used for an exposure, at
least one IQI image shall appear on each radiograph except as outlined in (b)
below.
( a) Multiple IQIs. If the requirements of T‐282 are met by using more than on
IQI, one shall be representative of the lightest area of interest and the
other the darkest area of interest; the intervening densities on the
radiograph shall be considered as having acceptable density.
(b) Special Cases
(1) For cylindrical components where the source is placed on the axis of
the component for a single exposure, at least three IQIs. Spaced
approximately 120 deg apart, are required under the following
conditions:
(a) When the complete circumference is radiographed using one
or more film holders, or;
(b) When a section or sections of the length between the ends of
the outermost sections span 240 or more deg, is radiographed
using one or more film holders. Additional film locations shall
be required to obtain necessary IQI spacing.
(2) For cylindrical components where the source is placed on the axis of
the component for an single exposure, at least three IQIs, with one
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 7 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

placed at each end of the span of the circumference radiographed


and one in the approximate center of the span, are required under
the following conditions:
(a) When a section of the circumference, the length of which is
greater than 120 deg and less than 240 deg, is radiographed
using just one film holder, or;
(b) When a section or sections of the circumference, where the
length between the ends of the outermost sections span less
than 240 deg, is radiographed using more than one film holder.
(3) In (1) and (2) above, where sections of longitudinal welds adjoining
the circumferential weld are radiographed simultaneously with the
circumferential weld, an additional IQI shall be placed on each
longitudinal weld at the end of the section most remote from the
junction with the circumferential weld being radiographed.
(4) For spherical components where the source is placed at the center
of the component for a single exposure, at least three IQIs, spaced
approximately 120 deg apart, are required under the following
conditions:
(a) When a complete circumference is radiographed using one or
more film holders, or;
(b) When a section of sections of a circumference, where the
length between the ends of the outermost sections span 240 or
more deg, is radiographed using one of more film holders,
Additional film locations shall be required to obtain necessary
IQI spacing.
(5) For spherical components where the source is placed at the center
of the component of a single exposure, at least three IQIs, with one
placed at each end of the radiographed span of the circumference
radiographed and one in the approximate center of the span, are
required under the following conditions;
(a) When a section of a circumference, the length of which is
greater than 120 deg and less than 240 deg, is radiographed
using just one film holder, or;
(b) When a section or sections of a circumference, where the
length between the ends of the outermost sections span less
than 240 deg is radiographed using more than one film holder.
(6) In (4) and (5) above, where other welds are radiographed
simultaneously with the circumferential weld, one additional IQI
shall be placed on each other weld.
(7) For segments of a flat or curved (i.e.,ellipsoidal, torispherical,
toriconical, elliptical,etc.) component where the source is placed
perpendicular to the center of a length of weld for a single exposure
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 8 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

when using more than three film holders, at least three IQIs, one
placed at each end of the radiographed span and one in the
approximate center of the span, are required,
(8) When an array of components in a circle is radiographed, at least
one IQI shall show on each component image.
(9) In order to maintain the continuity of records involving subsequent
exposures, all radiographs exhibiting IQIs that qualify the
techniques permitted in accordance with (1) through (7) above shall
be retained.
5.5 A lead symbol “B”, with minimum dimensions of 7/16 in (11 mm) height and 1/16 in.
(1.5 mm.) thickness, shall be attached to the back of each film holder during each
exposure to determine if back scatter radiation is exposing the film. The lead symbol
“B” shall be placed in a location so that it would be appear an area on the radiograph
that meets requirements of 8.1 b). If a light image of the “B” appears on a darker
background of the film, that radiograph shall be considered unacceptable. A dark
image of the “B” on a lighter background is not cause for rejection.

6.0 LOCATION MARKERS AND FILM IDENTIFICATION


6.1 Location markers, which shall appear as radiographic images on the radiograph, shall
be placed on the part, not on the exposure holder/cassette. Their locations shall be
permanently marked on the surface of the part being radiographed when permitted,
or on a map, in a manner permitting the area on a radiograph to be accurately
traceable to its location on the part, for the required retention period of the
radiograph. In addition, their locations do not limit the area of interest or the area to
be interpreted. Evidence shall also be provided on the radiograph that the required
coverage of the region being examined has been obtained. Location markers shall be
placed as follows
6.2 Lead number location markers (film interval numbers or identification numbers), which
are to appear as images on the film, shall be placed on the material adjacent to the
weld at the marks located in 6.1 and as follow:
6.2.1 Location markers shall be placed on the source side when radiographing joints
such as:
1. Flat components or longitudinal joints in cylindrical or conical components.
2. Curved or spherical components whose concave side is toward the source
and when the source to material distance is less than the inside radius of
the component.
3. Curved or spherical components whose convex side is facing toward the
source.
6.2.2 Location markers shall be placed on the film side when radiographing joints in
curved or spherical components whose concave side is toward the source and
when the source to material distance is greater than the inside radius.
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 9 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

6.2.3 Location markers shall be placed on either the source side or film side when
radiographing joints in curved or spherical whose concave side is toward the
source and the source to material distance equals to the inside radius of the
component.
6.2.4 As an alternative to source side placement in 6.2.1, Location markers shall be
placed on the film side when the radiograph shows coverage beyond the
location markers to the extent demonstrated by Fig. T‐275, sketch (e) of ASME
Section V.
6.3 Lead number markers for pipe welds shall be located as follows
6.3.1 For single wall viewing, circumferential number tapes shall be used. The 0 (zero)
number shall be placed on the top of the pipe and the remaining numbers
located clockwise (or counterclockwise) around the outside of the pipe. A
minimum number of markers shall be used to provide evidence that the
required coverage has been obtained.
6.3.2 For double wall viewing, at least one location marker shall be placed on the
outside surface adjacent to the weld for each exposure.
6.4 Lead markers shall be used to produce on each radiograph an identification that is
traceable to the item being radiographed and that is permanent for the retention
period of the radiograph. This identification system does not necessarily require that
the information appear as radiographic images, in any case, this information shall not
obscure the area of interest. Permanent mark on each film shall have the following
information:
[1] Project or Job Number
[2] Serial or Line number or Item Identification
[3] Weld or joint number
[4] Film interval numbers or identification number
[5] Manufacture’s name or symbol
[6] Welder identification
[7] Date of the radiograph
[8] Weld thickness
[9] Qualitech Company logo
Re‐shoot film shall be identified with symbol RS. Repair film shall be identified with
symbol R1 for first repair and R2, R3, etc. for subsequent repairs. In any case, this
information shall not obscure the area of interest. The above information shall be
changed as per the client requirement.
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 10 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

7.0 GEOMETRICAL UNSHARPNESS


7.1 The following geometrical unsharpness values shall be used as a guide for determining
the minimum source to weld or object distance (D).
Material Penetrated Thickness, inch Ug Maximum, inch (mm)
(mm)
Under 2” (50) 0.020” (0.51)

2” through 3” (50‐75) 0.030” (0.76)

Over 3” through 4” (75‐100) 0.040” (1.02)

Note: Material thickness is the thickness on which the IQI is based


Geometric unsharpness of the radiograph shall be determined in accordance with
Ug = Fd/D

Where
Ug = geometric unsharpness,
F = source size,
D = distance from source of radiation to weld or object being radiographed.
d = distance from source side of weld or object being radiographed to the film
D and d shall be determined of the approximate center of the area of interest.

7.3 The unsharpness formula is included for information and guidance and will operate
within practical limits. Final acceptance of radiographs shall be based on the ability to
see the IQI(s) image.

8.0 EVALUATION OF RADIOGRAPHIC QUALITY


8.1 All of radiographs shall be evaluated the radiographic quality by the image of a
properly located IQI(s) and the following film quality requirements:
a) The images of the identifying numbers, the wires of the IQI(s) which determine
IQI(s) sensitivity, shall be appeared on the radiograph.
b) The transmitted film density through the radiographic image of the body of the
appropriate or adjacent to the designed wire of a wire IQI and the area of interest
for single film viewing shall be 2.0 minimum. for single or composite viewing. For
composite viewing of multiple film exposure, each film of the composite set shall
have a minimum density of 1.3. The maximum density shall have 4.0 for either
single or composite viewing. A tolerance of 0.05 in density is allowed for variations
between densitometer readings. A density variation through the interest area shall
not be more than minus 15% or plus 30% from the density adjacent to the
designated wire of penetrameter.
Densitometer used for measuring density of the film shall undergo periodic
calibration verification checks at the beginning of each shift, after 8 Hr of
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 11 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

continuous use, or after change of apertures, whichever comes first. Densitometers


shall be calibrated at least every 3 months use complying T‐262.1 of ASME section
V, 2021 edition. Step wedge comparison films verification shall be
performed annually complying T‐262.2 of ASME section V, 2021
edition.
c) Each IQI(s) shall represent an area of essentially uniform radiographic density as
judged by a calibrated density comparison strip or calibrated densitometer. If the
film density through the area of interest varies by more than specified in 8.1.b) an
additional IQI(s) is required for the exceptional area or areas.
d) All radiographs shall be free from mechanical, chemical or other processing defects
that could interfere with proper interpretation of the radiograph.
e) Radiography shall be performed with a technique of sufficient sensitivity to display
the designated essential wire of a wire‐type IQI. The radiographs shall also display
the IQI identifying numbers and letters. If the designated essential wire of a wire
type IQI, do not show on any film in a multiple film technique, but do show in
composite film viewing, interpretation shall be permitted only by composite film
viewing. For wire‐type IQIs, the essential wire shall be visible within the area of
interest representing the thickness used for determining the essential wire,
inclusive of the allowable density variations described in 8 .1 (b) of th is p r ocedu re.
f) The image quality indicator (IQI) sensitivity shall be calculated based on penetrated
thickness and shall display the designated wire IQI(s) conforming to the
requirements of ASME Section V, Table T‐276.
g) The Manufacturer shall be responsible for the review, interpretation, evaluation,
and acceptance of the completed radiographs to assure compliance with the
requirements of Article 2 and the referencing Code Section. As an aid to the review
and evaluation, the radiographic technique documentation required by T‐291 shall
be completed prior to the evaluation. The radiograph review form required by T‐
292 shall be completed during the evaluation. The radiographic technique details
and the radiograph review form documentation shall accompany the radiographs.
Acceptance shall be completed prior to presentation of the radiographs and
accompanying documentation to the Inspector.
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 12 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

9.0 ACCEPTANCE CRITERIA


The acceptance criteria shall be as per the applicable design C odes.

10.0 DOCUMENTATION
10.1 The evaluation results shall be recorded in the report as shown in Attachment I of this
procedure. Reports shall be interpreted and signed by NDT personnel certified to at
least a Level II.
10.2 Record the radiographs with their results, on a “Radiographic Test Report”
10.2.1 Record the spot radiography and 100% radiography on separate report forms.
10.2.2 List reconfirm separately in sequence and mark them RC1, RC2, etc.
10.2.3 List repairs separately in sequence and mark them R1, R2, etc.
10.2.4 List reshoots, taken for reasons other than either of the above, separately from
the original film and mark then RS.
10.2.5 When inaccessibility or other limitations prevent the location of markers as
stipulated in Paragraph 6.2.1 or 6.2.2, a dimensioned sketch of the geometric
arrangement including marker locations shall be documented on sketch of
"Radiography Testing” form.
10.3 The following radiographs need not be retained or recorded.
10.3.1 In-Process Radiographs taken for information only on an area of a joint not fully
welded regardless of whether or not they are used for making repairs.
10.3.2 Technique radiographs showing no rejectable indications taken to establish
parameters that produce radiographs that meet the film quality requirements
of this procedure.
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 13 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

10.3.3 Radiographs showing no rejectable indications, but unacceptable from


standpoint of film quality requirements due to defective film, improper
processing, physical damage, or improper technique.
10.3.4 Radiographs that cannot be identified as to location such as parts or vessel
number, pipe number, joint number, film number.
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 14 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

ATTACHMENT NO. I: RADIOGRAPHIC TESTING REPORT


Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 15 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

ATTACHMENT NO. II: SAFETY PROCEDURE


1) GENERAL:
The purpose of this procedure is to make employees fully aware of their responsibilities
regarding personal safety and the safe usage of radioactive sources and / or irradiating
apparatus no set of rules can guarantee safety at work co-operation and common sense are
required as well, from all parties concerned, if incidents and accidents. These safety
procedures are based on the requirement of Thai laws, and have been approved.

2) OPERATOR'S RESPONSIBILITY:
No person shall operate any irradiating apparatus or radioactive substance without the use
and knowledge of application of
2.1) A functional radiation survey meter.
2.2) A functional personal radiation monitor, a dosimeter and or film badge.

3) WORKING RULES:
3.1 ) Handling and usage of radiographic equipment
- Before proceeding to the job site, the radiographer has to ensure that radiographic
testing team has radiation monitoring as below (at least)
1 unit/team ‐ functional radiation (monitor) survey meter
1 unit/team – audible alarm
1 set/person – film badge
2 set/team – flashlight
2 set/team – radiation warning sign
Any abnormalities or irregularities in the operation of the equipment shall
immediately be reported to management for corrective action and maintenance.
- During the transport of gamma radiography equipment, the source container is to
be secured to the vehicle to prevent any accidental shift under conditions normally
expected during transport, and located in or on the vehicle so that the radiation
dose received by any person traveling in the vehicle is minimized and within safe
limits. Only radiation workers are permitted in the vehicle and the dose rate to any
persons shall be verified to be less than 20 uSv (micro seivert) per hour by
measurement before commencing the journey, at appropriate times during the
journey and on arrival at destination.
3.2) Working rule for an open site ( Field)
a) On first arriving at the site, the operator shall:
- advise the person responsible for the area in which the radiography site will
be set up of the intended operations and the estimated amount of time
required to complete the work, and
- ascertain the nature, duration and location of all other work to be performed
in the vicinity of the site and the possible points of entry to the site.
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 16 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

b) Before commencing exposures, a well‐defined and clearly visible boundary shall


be erected around the site, including above and below as necessary, such that
the does rate at the boundary shall not exceed 25 uGy/hr during exposures. This
shall be checked periodically by the operator by means of a survey meter. The
boundary shall be marked with radiation warning signs. Warning lights shall be
used to indicate that an exposure is under way. The area within the boundary
shall be kept under surveillance at all times during exposures to ensure that no
person enters it or remains within it. Unnecessary occupation of areas near the
boundary shall be avoided.
c) The boundaries of adjacent exposure sites shall not overlap. If an overlap is
unavoidable, close liaison shall be maintained between operators responsible for
the overlapping sites to avoid accidental exposure.
d) The operator shall, according to appropriate advice prepared by the Engineer,
ensure that dose rates in occupied areas are such that no member of the public
will receive a dose exceeding 1 mSv per year from radiography performed within
the site.
e) A second person, who is capable of promptly taking charge in an emergency,
shall be immediately available to assist during industrial radiographic exposures.
The second person, the assistant industrial radiographer, shall be a radiation
worker. This person shall be thoroughly familiar with the equipment and its use,
the approved working rules and emergency procedures appropriate to work and
the relevant requirements.
f) At all times, collimators shall be used to restrict the area of primary radiation
beam to the minimum necessary for radiography. Radiography equipment and
the item to be radiographed shall be set up so that each of components,
particularly the X-ray tube or the source, are stable and therefore will not move
during the exposure.
g) Before commencing an exposure the operator shall ensure by inspection the all
unauthorized persons are outside the boundary and that the assistant operators
are in an area where the dose rate is as low as, or lower than, where he or she is.
h) Just prior to commencing an exposure, a signal shall be given to warn persons
within a reasonable distance that an exposure is about to take place.
i) A personal radiation monitoring device and a personal dosimeter shall be worn
by the operator and assistant operators at all times during industrial radiography
operations.
j) The operator shall continually check the radiation level at his or her location
during exposure using a survey meter.
k) The operator alone shall exercise control over:
- The radiation source during exposure; and
- The occupancy of the site during the period of exposure of the source by
continuous and competent supervision of the site.
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 17 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

l) Care shall be taken at all times to ensure that unauthorized persons cannot
operate the equipment.
m) Before a site is vacated. The operator shall ensure, by monitoring, that all
radiation source are locked in the fully shielded condition or switched off, as
appropriate, and returned to the source container store or to the transport
vehicle and that all boundary-defining equipment has been removed. The
operator shall inform the person responsible for the area when this has been
carried out.
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 18 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

ATTACHMENT NO. III: ACCEPTANCE CRITERIA

ASME SECTION VIII DIV.1, 2021 Edition


Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 19 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 20 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 21 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 22 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 23 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 24 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 25 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 26 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 27 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 28 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

ASME SECTION VIII DIV 2, 2021 Edition


Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 29 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 30 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

ASME SECTION I, 2021 Edition


Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 31 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 32 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 33 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 34 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 35 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 36 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022
Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 37 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

ASME B31.3, 2020 Edition


Doc. No.: ExWI‐NDT‐ 22113
RADIOGRAPHIC TESTING FOR PRESSURE Page : 38 of 38
VESSEL, BOILER AND PIPING
Revise No.: 00
(GAMMA RAY)
Issue Date: June 1, 2022

You might also like