Residential Building Type

Site Name : K-9


PIC Name : Flower Dance
Address : Gubernur Suryo Street, Jombatan, Jombang, Jombang Regency, East Java
Indonesia 61419
Coordinate : 7°33'29.1"S 112°13'42.1"E (-7.558075, 112.228349)
UTM Coordinate : Zone 49 S 9164370 N 635510.85 E
Azimuth : N 10° E
Phone : +6285174332523
Email :-
Area Open : North Side 62,46 m2 + Garage North 16,92 m2

South Side 43,06 m2 + Garage North 10,11 m2

Style of Roof : Box Gable


Type of Roof : Clay Tile
Roof Profile : Interlocking Roof
Roof Age : 15 Years
Roof Tilt : 10°-15°
Roof Direction : North-South Orientation
Roof Dimension : North Side approx. 10 m x 6 m, Garage North 3 m x 6 m
South Side approx. 7 m x 6 m, Garage South 2 m x 6 m
Accessible Roof : Yes
Lighting Protection : No

Irradiance Data

Electricity Bill and Saving (K-9) for Gross Wp Capacity Prediction

Monthly Electricity Bill : Rp. 141436


Installed Service Connection : 1300 VA
Maximum Inverter Capacity : Aprox 1300 VA or 2kVA Inverter (mostly 2kVA/3kVA – 2kW Inverter)
Minimum Billing (40hrs) : 40 hrs x 1,3 kVA x Rp. 1444,70/kWh = Rp. 75124,44
Maximum Saving : Rp. 141436 - Rp. 75124,44 = Rp. 66311.6
Maximum Energy Saving : Max Saving/ Rp. 1444,70/kWh = Rp. 66311.6/ Rp. 1444,70 = 45,89
kWh
Capacity Simulation : (Max Energy Saving/30 day)/(PSH x PR)
PSH : GHI/(1000W/m2) = 5265W/m2 per day / 1000 = 5.265 hrs

Capacity Simulation : (45,980 kWh/30 day)/(5.265 hrsx 80%)


: (63,861)/(4,212)
: 1,5161 kWP
: 1516 WP (approx. 3 Modules of 550 Wp)

Manual Components Analysis


Installed Capacity : R1/1300 VA (R1 = Rp. 1444,70)
GHI : 5,265 kWh/m2
Tilt : 10°-15°
Height : 8 meters

We offers the Tier 1 set-up and Affordable Tier


Tier 1 Set-Up:
- PV = Canadian Solar MonoCrystalline HiKu CS6W 550Wp (Rp. 3500000)
https://www.tokopedia.com/sonergysolar/canadian-solar-panel-mono-crystalline-550-
wp?extParam=ivf%3Dfalse%26src%3Dsearch&refined=true
Datasheet = https://solar.co.za/wp-content/uploads/2021/11/CS-Datasheet-HiKu6_CS6W-
MS_v1.6_F50A_EN_530-550W.pdf
- Inverter = Central Inverter MPP Solar Offgrid PIP-2024MSE 3kVA 2.4 kW MPPT 40A (Rp.
8500000)
https://www.tokopedia.com/ayuhobbies/hybrid-offgrid-inverter-2kva-2kw-mppt-40a-merk-
mpp-solar?extParam=ivf%3Dfalse%26src%3Dsearch&refined=true
- Storage* = Deep Cyccle SMT-POWER Battery SMMT12200 12 V 200AH (Rp.4050000)
https://www.tokopedia.com/brothersnetwork/deep-cycle-gel-battery-12v-200ah-baterai-
solar-panel-surya-smt-power?extParam=ivf%3Dfalse&src=topads

Affordable Tier Set-Up:


- PV = Maysun 100 WP Mono-Si MS100M-39 (Rp. 550000)
Datasheet by Picture
https://www.tokopedia.com/limin/solar-panel-mono-100wp-mysolar-solar-cell-panel-surya-
100-wp-my-solar-maysun-100wp?extParam=ivf%3Dfalse&src=topads
- Inverter = Power-Esun-Suyeego HB-PW-G 3.5 kVA MPPT 20/30A (Rp. 5995000)
https://www.tokopedia.com/ryan-jb/hybrid-solar-inverter-3000va-2400watt-3-5kw-bd94
- Storage* = MTC VRLA OT65-12 GEL 12V/65Ah/10HR (Rp.1471800)
https://www.tokopedia.com/leo-mtcbattery/mtc-baterai-vrla-solar-panel-12v-
65ah?extParam=ivf%3Dfalse&src=topads

1. Inverter Capacity
- Based on KemenESDM rules (Permen 26 Th. 2021) = 100% Installed Capacity
Pinverter= 100% installed capacity
Pinverter= 1300 VA = 1,3 kVA
- Based on PLN rules (EXIM Grid Scheme) = 15% Installed Capacity
Pinverter= 15% installed capacity
Pinverter= 1300 VA x 0,15= 195 VA = 0,195 kVA
2. Module PV Capacity
Sweetspot Ratio DC/AC = 1,25:1
PPV = Pinverter x DC/AC ratio
PPV KEMENESDM = 1,3 kVA x 1,25 = 1.625 kWP
PPV PLN = 0.195 kVA x 1,25 = 0.24375 kWP
3. Number of Modules
Nmod = Total PV Capacity/Pmodule (unit)

For Tier 1 Module:


Nmodule PV KemenESDM = 1.625 kWP/550 Wp = 2.9545 = 3 Modules
Nmodule PV PLN = 0.24375kWP/550 Wp = 0.443 = 1 Modules

For Affordable Tier Module:


Nmodule PV KemenESDM = 1.625 kWP/100 Wp = 16.25 = 17 Modules
Nmodule PV PLN = 0.24375kWP/100 Wp = 0.443 = 2 Modules

For the next calculation, is based on 100% Capasity Installed (if using PLN, low return)
4. Maximum PV Modules Per String

For Tier 1 Module (Max DC Voltage Input PIP-2024MSE = 105V, PV Operating Voltage = 41,3
V)
Nmodule/string = operating voltage range inverter input/operating voltage PV (Voc)
Nmodule/string = 105 V/41,3 V = 2.5 = 2 Modules (Series)
For Affordable Tier Module (Max DC Voltage Input Power-Esun-Suyeego HB-PW-G = 120V,
PV Operating Voltage = 24,66 V)
Nmodule/string = operating voltage range inverter input/operating voltage PV (Voc)
Nmodule/string = 120 V/24,66 V = 4.866 = 5 Modules (Series)

5. String Sizing
String sizing = Nmodules x Vmp PV

For Tier 1 Module:


String Sizing = Nmodules x Vmp PV = 2 x 41,3 V = 82,6 V
2 Modules in series/MPPT

For Affordable Tier Module:


String Sizing = Nmodules x Vmp PV = 5 x 24,66 V = 123,3 V
5 Modules in series/MPPT

6. Maximum Current Per String

For Tier 1 Module:


1 String = Imp= 13,08 A
MPPT Inverter 40A, still save in range max input current/MPPT

For Affordable Tier Module:


1 String = Imp= 4.67 A
MPPT Inverter 20-30A, still save in range max input current/MPPT

7. Maximum Short Circuit Per MPPT


Safety Factor Standard = 125% actual Isc PV
For Tier 1 Module:
1 String = Isc=13,90 A
Isc max per MPPT = Isc PV xSafety Factor
Isc max per MPPT = 13,9 Ax 1,25
Isc max per MPPT = 17,375A

For Tier 1 Module:


1 String = Isc=4,90 A
Isc max per MPPT = Isc PV xSafety Factor
Isc max per MPPT = 4,90 Ax 1,25
Isc max per MPPT = 6,125A

Manual Balance of System – MCB, Fuse and Cable Usage

1. Tier 1 Module:
- Fuse Rating – DC Side
Fuse Rating = Isc PV x Safety Factor
Fuse Rating = 13,9 A x 1,25
Fuse Rating = 17,375A = 20 A Fuse
- MCB Rating – DC Side
MCB Rating = Isc PV x Safety Factor
MCB Rating = 13,9 A x 1,25
MCB Rating = 17,375A = 20 A CB
- DC Cable
DC Cable = Isc PV x Safety Factor
DC Cable = 13,9 A x 1,25
DC Cable = 17,375A = 20 A Current Rating = 4mm2 cable
- Fuse Rating – AC Side
Fuse Rating = Max Output Inverter Current AC x Safety Factor
Fuse Rating = 25 A x 1,25
Fuse Rating = 31,25A = 30 A Fuse
- MCB Rating – AC Side
MCB Rating = Max Output Inverter Current AC x Safety Factor
MCB Rating = 25 A x 1,25
MCB Rating = 31,25A = 32 A CB
- AC Cable
DC Cable = Max Output Inverter Current AC x Safety Factor
DC Cable = 25 A x 1,25
DC Cable = 31,25A = 32 A Current Rating = 6 mm2 cable

2. Affordable Tier Module


- Fuse Rating – DC Side
Fuse Rating = Isc PV x Safety Factor
Fuse Rating = 4,9 A x 1,25
Fuse Rating = 6,125A = 7,5 A Fuse
- MCB Rating – DC Side
MCB Rating = Isc PV x Safety Factor
MCB Rating = 4,9 A x 1,25
MCB Rating = 6,125A = 7,5 A / 8 A MCB
- DC Cable
DC Cable = Isc PV x Safety Factor
DC Cable = 4,9 A x 1,25
DC Cable = 6,125A = 8 A Current Rating = 1,25mm2 cable
- Fuse Rating – AC Side
Fuse Rating = Max Output Inverter Current AC x Safety Factor
Fuse Rating = 20 A x 1,25
Fuse Rating = 25A = 30 A Fuse
- MCB Rating – AC Side
MCB Rating = Max Output Inverter Current AC x Safety Factor
MCB Rating = 20 A x 1,25
MCB Rating = 25A = 30 A CB
- AC Cable
DC Cable = Max Output Inverter Current AC x Safety Factor
DC Cable = 20 A x 1,25
DC Cable = 25A = 30 A Current Rating = 6 mm2 cable