Professional Documents
Culture Documents
Esd2100 Pib1020
Esd2100 Pib1020
1 OVERVIEW
◊ Multi-VDC
◊ Isochronous Operation
◊ Adjustable PID Functions
◊ Case Option Available
◊ Light Force Option Available
2 SPECIFICATIONS
Performance Environmental
Isochronous Operation ± 0.25 % or better Ambient Temperature -40° to 85 °C [-40 to 185 °F]
Speed Range / Governor 1 - 7.5 KHz Continuous Relative Humidity up to 90 %
Speed Drift with Temperature ±1% MAX All Surface Finishes Fungus-Proof
and Corrosion-Resistant
Speed Trim Range ± 450 Hz
PHYSICAL
Remote Variable Speed Range 500 Hz - 6 KHz
Dimension See Section 3, Installation
Terminal 9 Sensitivity 120 Hz. ±15 Hz./V
@ 250 K Impedance Weight 1.2 lbf (545 gf)
INPUT / OUTPUT Mounting Any position, Vertical Preferred
DC Supply 10 - 40 V DC RELIABILITY
Transient and Reverse
Voltage Protected* Vibration 5 g @ 20-500 Hz
Vertical orienta-
tion allows for the
draining of fluids
in moist environ-
ments.
Mount in a cabinet,
engine enclosure,
or sealed metal
box.
Dimensions:
in
(mm)
Use an overspeed shutdown device, independent of the governor system, to prevent loss of engine control which
may cause personal injury or equipment damage.
Do not rely exclusively on the governor system electric actuator to prevent overspeed. A secondary shutoff device,
such as a fuel solenoid must be used.
6 Battery Power (+) A 15 amp fuse must be installed in the positive battery lead to protect against reverse voltage
7
8
Variable speed isochronous operation can be obtained by connecting a 5K potentiometer to Terminals 8, 9, and
Speed Trim
9 10. To select the variable speed range, connect the appropriate resistor, R, to posts E4 and E5. See the Resistor
Control
Jumpers diagram below.
10
RECOMMENDATIONS
Shielded cable should be used for all external connections to the ESD control.
One end of each shield, including the speed sensor shield, should be grounded to a single point on the ESD case.
RESISTOR JUMPERS
FREQUENCY RANGE (Hz) RESISTOR
850 NONE
1280 2M
1880 750 K
3400 300 K
5700 150 K
IMPORTANT Make sure the following adjustments are set before starting the engine.
The speed control unit governed speed setting is factory set at approximately engine idle speed (1000 Hz., Speed sensor signal or
600 RPM)
Crank the engine with DC power applied to the governor system. The actuator will energize to the maximum fuel position until the
engine starts. The governor system should control the engine at a low idle speed. If the engine is unstable after starting, turn the
GAIN and STABILITY adjustments counterclockwise until the engine is stable.
NOTE The governed speed set point is increased by clockwise rotation of the SPEED adjustment pot. Remote speed adjustment
can be obtained with an optional 5K Speed Trim Control. See Section 4, Wiring.
STABILITY ADJUSTMENT
1. Rotate the GAIN adjustment clockwise until instability develops. Gradually move the adjustment counterclockwise until stability
returns. Move the adjustment one division further counterclockwise to ensure stable performance (270° pot).
2. Rotate the STABILITY adjustment clockwise until instability develops. Gradually move the adjustment counterclockwise until
stability returns. Move the adjustment one division further to ensure stable performance (270° pot).
3. Gain and stability adjustments may require minor changes after engine load is applied. Normally, adjustments made at no load
achieve satisfactory performance.
NOTE If instability cannot be corrected or further performance improvements are required, see Section 7, System Troubleshooting.
Should normal values be indicated during troubleshooting steps, and then the fault may be with the actuator or the wiring to the actu-
ator. Tests are performed with battery power on and the engine off, except where noted. See your actuator publication for additional
testing and troubleshooting procedures.
UNSATISFACTORY PERFORMANCE
3. Defective actuator
Engine remains 1. Measure the actuator output, Terminal 1 & 1. If voltage measurement is within 1.5 V DC of the battery supply voltage
below desired 2, while running under governor control. level, then fuel control is restricted from reaching full fuel position, pos-
governed speed sibly due to mechanical governor, carburetor spring, or linkage interfer-
ence.
INSTABILITY
The engine seems to 2. Turn off other electrical equipment that may be causing interference.
Fast Periodic jitter with a 3Hz or faster
irregularity of speed. 3. Cutting jumper from E1 to E2 should reduce the tendency to jitter.
2. Adjust Dead time compensation by adding a capacitor from posts E2 to E3 (negative on E2). Start
with 10 mfds and increase until instability is eliminated.
An irregularity of speed
Slow Periodic
below 3Hz.
3. Check fuel system linkage during engine operation for:
a. binding
b. high friction
c. poor linkage
1. Increasing the Gain should reduce the instability but not totally correct it. If this is the case, there is
most likely a problem with the engine itself. Check for:
a. engine mis-firings
b. an erratic fuel system
Non-Periodic Erratic Engine Behavior
c. load changes on the generator set voltage regulator.
2. If the throttle is slightly erratic, but the performance is fast, removing the jumper from E6 to E7 will
tend to steady the system.
A strong magnetic speed sensor signal eliminates the possibility of missed or extra pulses. The speed control unit will govern well with
a 0.5VAC RMS speed sensor signal. However, a speed sensor signal of 3 V AC RMS or greater is recommended.
The amplitude of the speed sensor signal can be raised by reducing the gap between the tip of the speed sensor and the top land of a
tooth on the engine’s ring-gear. This gap should not be any smaller than 0.020 in. (0.45 mm).
With the engine stopped, turn the magnetic speed sensor CW until it touches the top land of a ring-gear tooth, then turn it CCW 3/4 turn.
This will provide an acceptable gap.