You are on page 1of 6

2022 7th International Advanced Research Workshop on Transformers (ARWtr) – Baiona - Spain, (23)24-26 October 2022

The Impact of the Use of Dry Lubricating


Compound on the Dielectric Properties of Solid
and Liquid Insulation of a Power Transformer
Gopalan Ramesh Senior Member, IEEE, Ashutosh Sharma, MCIGRE and Hemang Thakkar

Abstract -- This paper discusses the impact of the use of dry mature non-compliances of insulation properties of the power
lubricating compound during the manufacturing of a power transformer. The premature increase in insulation power
transformer on the dielectric properties of the solid and liquid factor and changes in solid insulation properties of power
insulation. Change in dielectric properties noticed in specific
transformers measured in the field and after factory dielectric
cases are discussed. An experimental set up was used for the
research work. The experimental set up and basis for simulating test failures may be attributed to the contamination of solid
the operating conditions and the impact of the use of dry insulation with compounds used during manufacture of the
lubricating compound on the solid and liquid insulation of the power transformer.
transformer are discussed. The test results of the experiment
indicate that the dielectric properties namely surface II. IMPACT OF MATERIALS USED IN THE MANUFACTURE OF
conductivity and DC resistivity of the solid insulation can be
POWER TRANSFORMERS
affected. This can be measured using the capacitance and power
factor test. Manufacturers often study the compatibility of the Dielectric properties of the solid and liquid insulation may
compound with liquid insulation (mineral oil) only and seldom be affected by the use of construction materials in the
on the solid insulation. The results suggest that the transformer. Usually, factory tests are conducted such as the
manufacturers should study the impact of the compounds on the capacitance and tan delta test or the modern dielectric
solid insulation as well and not only on liquid insulation.
frequency response analysis test to test the insulation
Index Terms—Power Transformers, Solid insulation, Dry condition of the transformer at the factory and in the field.
Lubricating Compound, Insulation Power factor, Surface However, some construction materials used in the
Conductivity, Tangent Delta manufacture may result in non-conformities and may affect
the dielectric properties at a later date during the service life
of the transformer. Such non-conformities may not be
I. INTRODUCTION immediately manifested during the factory acceptance tests or

T HIS paper discusses an important research work on the


impact of the use of dry lubricating compound containing
Molybdenum di-sulfide and graphite. One such commercially
during site acceptance tests. This depends upon the material
used and the actual place of use within the transformer. DNV
have noted that some of the transformer manufacturers use
available product in the market is the MOLYKOTE® G Rapid Molybdenum disulfide and graphite or solely Molybdenum
Plus [1], which was used in the research experiment. disulfide based dry lubricants. In order to study the impact of
Manufacturers often study the compatibility of a material [2] the use this compound on the dielectric properties of the solid
during the manufacture of the power transformers with the and liquid insulation, DNV and Emirates Global aluminium
liquid insulation using the ASTM standard D3455 [3]. (EGA) collaborated to conduct an investigative exercise, as a
Published work is available for compatibility with mineral oil research experiment on this subject. The experimental setup
and ester oil only [4]. However, the compatibility of the was established at the EGA workshop with an objective to
construction material with that of the solid insulation is not assess the impact of the use of the dry lubricating compound
available and most manufacturers seldom perform it. Field on the solid and liquid insulation of the transformer.
failures may have occurred, but such data is not available in
A. Use of Dry Lubricating Compound
the public domain. The increase in insulation power factor
(tangent delta) after some failures in the network is discussed Dry lubricating compound is used in power transformers
in [5] but the root cause for the increase in insulation power for the larger fasteners used inside the transformer namely
factor (tangent delta) after the noted failures and events of the core-yoke clamps at the top and bottom and also sometimes
power transformer during service is not discussed. The aim on the tank cover bolts. While the use of dry lubricating
of this research and experiments conducted is to study the compound on the tank cover bolts do not affect the internal
impact of the use of the dry lubricating compound on the solid insulation structure of the transformer, the use of the dry
and liquid insulation. The research work discussed in this lubricating compound in the top and bottom yokes do affect
paper suggests manufacturers to perform such investigations the internal insulation structure as the compound does mix
in light of some specific factory failures and known field pre- with oil and may also fall on the surface of the solid insulation,

A. Sharma is with Grid Assets Management and Studies Group of DNV


G. Ramesh is with Grid Assets Management and Studies Group of DNV Energy Systems, PO Box 11539 Dubai, United Arab Emirates (e-mail:
Energy Systems, PO Box 11539 Dubai, United Arab Emirates (e-mail: ashutosh.sharma@dnv.com).
gopalan.ramesh@dnv.com). H. Thakkar is with the Energy Group of Emirates Global Aluminium,
Dubai, United Arab Emirates (e-mail: hthakkar@ega.ae).

978-84-XX-XXXXX-X /22 © 2022 Red iNtransf 1


2022 7th International Advanced Research Workshop on Transformers (ARWtr) – Baiona - Spain, (23)24-26 October 2022

and depending upon the time of service, this may be absorbed specific gravity of 5.06. It is insoluble in water and
in the insulation as well. The compatibility of the transformer transformer oil. It is usually seen as a grey deposit in the
construction materials with transformer oil is studied prior to bottom of the frames. Existing literature indicates that MoS2
the use in a transformer. However, no research data or is an inorganic semiconductor [6] and at appropriate
manufacturer experience is available in the public domain for frequencies can affect the electric field distribution of the
the compatibility of the dry lubricating compound with solid transformer. This can be seen in the change in tan delta values
insulation namely, pressboard and insulation paper which is of the transformer and may be associated with an increase in
of cellulosic origin. DNV has conducted investigations on capacitance as well.
some 200 – 500MVA, 132kV-400 kV class, generator, and TABLE I
PHYSICAL PROPERTIES OF MOLYBDENUM DISULFIDE
transmission class transformers in the past where the tan delta
(insulation power factor) of the transformers found increased
Description Value for Molybdenum Disulfide
within a short span (a few months to about 4 years) of service
life. In some transformers, increase in capacitance was also Molecular Weight 160.07
seen. Investigation revealed use of Molybdenum disulfide and Appearance Black powder or solid in various
graphite or solely Molybdenum disulfide on those forms
transformers. The effect of these compounds present in the Melting Point 1185 ° C (2165 ° F)
MOLYKOTE G-Rapid Plus are discussed in the next sections. Density 5.06 g/cm3
Solubility in Water Insoluble
B. Molykote® G Rapid Plus
The Molykote G-Rapid Plus is a dry lubricant (Fig. 1) used Graphite, another component of the compound, is one of
in a spray form on fasteners. MoS2 is used as a dry lubricant the allotropes of carbon. Graphite is not an element or a
in the industry from a very long period of time. It is also used compound, it's an allotrope of carbon. It doesn’t have any
as an additive in lubricating grease and oils as well. Solid chemical formula of its own. Graphite is a well-known good
lubricants gained a lot of interest for space applications as conductor of electricity due to its free delocalized electrons. It
space missions involve a wide range of operating conditions is insoluble in organic solvents and has density of about 2.2
and longer durations where drive mechanisms need a robust g/cm3.
and reliable operation without maintenance. Authors are of
the view that the use of the compound in transformer C. Dissipation Factor (Tan Delta) or Insulation Power
Factor
application depends upon the skill of the operator and the
amount of spray is only controlled by the operator. In general, One of the tests that is used when testing the transformer
manufacturers do not have a limit on the amount of spray on insulation is the dissipation factor (tan delta) or the power
the fastener and no standard operating procedure exists for the factor test. Both tests are the same and they are based on the
spraying of the compound on the fasteners. trigonometric relations between the current and the applied
voltage and which angle is measured and used for calculation.
The difference is marginal when the insulation power factor
is less than 10% and both tests can be used interchangeably.
Hence all these terms are used interchangeably in this research
work and mean one and the same factor. The insulation power
factor of the winding is a measure of the losses in the
insulation under the influence of an electric field. Increasing
power factor makes the insulation system more conductive
and hence increase the losses dissipated in the insulation. The
insulation power factor can increase primarily due to:
1. Increase in moisture content of the insulation- Increase
in moisture content increases the conductivity of the
insulation surface by polarizing the surface. However, it
should be noted that low levels of moisture in solid insulation
up to 1% moisture content by weight of solid insulation, the
change or increase in conductivity with insulation moisture
content is not significant for the electric field levels
maintained in the transformer.
2. Contamination of the insulation system (composite oil
and solid insulation)- The insulation power factor or tan delta
Fig. 1. Molykote ® G Rapid Plus Compound. has a direct relationship with the conductivity of the
insulation. Increase in conductivity causes a higher power
It is noted from the datasheet [1] that this compound has factor. Hence if the insulation is contaminated with chemicals,
about 7-8% Molybdenum Disulfide (MoS2) and about 2.7% then we can infer that the cause of power factor increase is
graphite. The lubrication properties are achieved out of present. A high voltage power transformer insulation has to
Molybdenum disulfide and Graphite; both are well known be clean, smooth, and dry for it to provide adequate insulation
solid lubricants. Table I provides the physical properties of at the operating and test voltages. Contamination also
Molybdenum Disulfide (MoS2) . It is heavier than oil with a increases permittivity and hence if the capacitance has

2
2022 7th International Advanced Research Workshop on Transformers (ARWtr) – Baiona - Spain, (23)24-26 October 2022

increased with the power factor, we can conclude that the Two set ups were used. In set up-1 Fig. 3 and Fig. 4 as
contamination has affected the insulation. shown below, two pieces of insulation were separated by bolts
3. Aging of the insulation- Aging of the insulation in an oil bath. The bolts were used for separation only. One
increases the tangent delta of the transformer as polar side of the bolt had insulation sprayed with the
molecules are present in the oil and on the surface of the MOLYKOTE® compound and the other side had plain
insulation as a result of the insulation aging process which insulation without any spraying of the compound.
results in the decomposition and breakdown of the cellulose
molecules into esters, carbonates, water, and other organic
compounds.
4. Partial discharges or surface tracking path on the surface
of the solid insulation- The insulation power factor or tan delta
can increase if there are tracking paths available on the surface
of the insulation. A detailed inspection of the insulation
surface is necessary to determine whether or not these paths
are available on the surface.

III. EXPERIMENTAL SET UP

Most research literature available have studied the effect


of moisture on conductivity of the insulation but published
data is not available on the relationship of contamination with
conductivity of the insulation. Therefore, DNV in
collaboration and assistance with EGA set up an experimental
basis to study the impact of the MOLYKOTE® compound
applied on the fasteners of the transformer. The basis of the
investigation is to spray some MoS2 on the insulation and
bolts inside an oil bath and leave them at 90°C for 10 days and Fig. 3. Preparation of Samples
study the insulation electrical properties of the insulation and
oil along with reference insulation. This will provide an In the above Fig. 3, only one side of the insulation board is
indication of the change in properties of the insulation. sprayed -. The insulation board on the other side is not sprayed
with any compound and they are placed in the oil bath as
A. Preparation of Samples shown in the set up in Fig. 4.
All insulation samples were 150mm x 150mm x 0.5mm
thick press board (PSP). The same insulation being used in
the transformers. The following pictures highlight the
experimental set up and process of the experiments. The oil
was set at 90°C in the oil bath for 10 days and was monitored
regularly. Fig. 2 shows below the dried insulation samples
being cut and prepared for the experimental set up. The choice
of 90°C is to simulate the maximum oil temperature that can
be expected for the operating conditions of the transformers
based on ambient conditions.

Fig. 4. Set up-1 seen without oil in the bath

In the second set up, Fig. 5, a bolt was sprayed and hung
from the top of the insulation bath with a wire. This is to
simulate the dripping of the Molybdenum disulfide compound
from the top yoke frames onto the insulation structure in the
winding of the transformer.

Fig. 2. Preparation of Samples

3
2022 7th International Advanced Research Workshop on Transformers (ARWtr) – Baiona - Spain, (23)24-26 October 2022

Fig. 8. Oil in the bath being set at 90°C

B. Collection of Samples for testing after 10 days


Fig. 5. Set up-2 seen without oil in the bath After 10 days in the oil bath at 90°C, samples were
collected for all the 4-press board (PSP) samples. They were
During the experiment for 10 days, the oil bath was set at removed from the oil bath and placed on a piece of white
90°C. Figures. 6-8 show the set up as seen below. paper. In the set-up 1, we can clearly see the sediments of
molybdenum disulfide at the bottom of the oil bath.

Fig. 9. Sediments of Molybdenum Disulfide seen at the base of the oil bath

The four insulation samples two each per oil bath


Fig. 6. Set up-1 seen in oil in the bath
numbered from the left of Fig. 10 as 1-A, 1-B, 2-A, and 2-B
were collected, sealed, and sent to a laboratory in Europe for
electrical testing. A reference sample which was originally
received from the factory was also sent to be used for
comparison of the test results.
.

Fig. 7. Set up-2 seen in the oil in the bath


Fig. 10. Insulation Samples for testing. From the left, 1-A, 1-B, 2-A, and 2-
B

4
2022 7th International Advanced Research Workshop on Transformers (ARWtr) – Baiona - Spain, (23)24-26 October 2022

IV. TEST RESULTS We can infer that dissipation factor has increased
significantly due to the presence of Molybdenum disulfide.
The samples 1-A, 1-B and 2-A, 2-B along with reference The dissipation factor has increased by nearly 50 times and is
samples were sent to a laboratory for analysis. The tests out of the acceptance limit for transformers operating in the
requested were tan delta and surface conductivity or field at 0.01 or 1%. The capacitance and the relative
resistivity. These are the two parameters that can affect permittivity have also increased for the insulation sample
insulation performance. Any increase in tan delta or surface sprayed with the compound.
conductivity will lead to detrimental electrical performance of
C. Oil Test Results
the insulation. The results are summarized below in the
figures. The front and back side of each sample is The transformer oil samples from the oil bath were
distinguished as the sprayed side is taken as the front side for subjected to tests as per IEC 60296 [7] and IEC 60422 [8].
the surface conductivity test. The oil from the new oil drum was used as a reference. The
test results indicate that the oil test results for the oil in the oil
A. Surface Conductivity and Resistivity
Bath 1 and Bath 2 with dry lubricant present are similar to that
The results of the surface conductivity and resistivity of the of the new oil drum. This indicates that liquid insulation i.e.,
insulation samples is shown below in the Table II below. mineral oil is not affected by the presence of dry lubricant as
it is heavier and settles down at the bottom of the container
TABLE II
SURFACE CONDUCTIVITY AND SURFACE RESISTIVITY TEST RESULTS
V. DISCUSSION ON INSULATION TEST RESULTS
Sample Nr after 1 min Surface Surface A. Impact of dry lubricant on the Surface Conductivity of
Resistivity Conductivity Insulation
V A σin Ω κ in S As seen in the test results above, the surface conductivity
and tan delta of the sample spayed directly with dry lubricant
A 1000 1.25E-08 2.75E+12 3.63E-13 (main component MoS2) has increased significantly by many
Ref
B 1000 2.39E-08 1.44E+12 6.94E-13 times. However, in practice, the compound is sprayed on the
A 1000 6.70E-09 5.14E+12 1.95E-13 bolts and if excess quantity of the lubricant flows down and
Front side 1 reaches the solid insulation, it settles down and during the
B 1000 6.94E-05 4.96E+08 2.02E-09 drying process can get absorbed on the insulation surface. If
A 1000 1.29E-08 2.67E+12 3.75E-13 the surface of the insulation where the contaminant lubricant
2 settles down is in a high electrical stress area, then it can affect
B 1000 1.14E-08 3.02E+12 3.31E-13 the electrical properties due to increased surface conductivity
A 1000 2.09E-08 1.65E+12 6.07E-13 which leads to reduced creepage distance. This may lead to
Ref flash overs during testing. This is because the test voltages are
B 1000 9.30E-09 3.70E+12 2.70E-13
much higher than the operating voltages.
A 1000 3.63E-08 9.48E+11 1.05E-12 The test results indicate that there is an increase in the
Back side 1
B 1000 1.45E-08 2.37E+12 4.21E-13 conductivity of the samples sprayed with dry lubricant.
Clearly the insulation sprayed with dry lubricant has increased
A 1000 1.17E-08 2.94E+12 3.40E-13 conductivity nearly 10,000 times on the sprayed side, and
2
B 1000 1.92E-08 1.79E+12 5.58E-13 nearly 10 times on the back side of the non-sprayed sample
(back side) in the same oil bath. Therefore, while MoS2 is
We can clearly see the surface conductivity of the sprayed being used a lubricant, it has to be used with care and any
sample has increased by an order of 104 times the reference excess will flow down the insulation and may lead to increase
and other non-sprayed sample. in tan delta and conductivity of the insulation. Increase in
conductivity decreases electrical creepage, which is not
recommended as this may affect design calculations for
B. Insulation Power Factor or Dissipation Factor voltage stress and clearance. Fig. 11 below shows graphically
The results of the dissipation factor, capacitance, and relative the increase in surface conductivity of the insulation board of
permittivity of the insulation samples is shown below in the the various samples.
Table III.
TABLE III Sample Reference
DISSIPATION FACTOR, CAPACITANCE AND RELATIVE PERMITTIVITY TEST
RESULTS 1.00E-05
Front Side Conductivity- K

Ref-ARef-B 1-A 1-B 2-A 2-B


1.00E-07
Siemens

1.00E-09

1.00E-11

1.00E-13
Fig. 11. Increase in surface conductivity of solid insulation.

5
2022 7th International Advanced Research Workshop on Transformers (ARWtr) – Baiona - Spain, (23)24-26 October 2022

IX. REFERENCES
B. Impact of dry lubricant on the Dissipation Factor of
Insulation [1] Form No. 71-0084F-01 (11/20) AGP16261, MOLYKOTE® G Rapid
Plus, Dupont Corporation, 1997-2020
As seen in the test results above, the dissipation factor of [2] H. M. Wilhelm, V. Franch, L. Tulio, A. F. Franch “Compatibility of
the insulation can be affected by contamination of the Transformer Construction Materials with Natural Ester-based
Insulating Fluids”, IEEE Transactions on Dielectrics and Electrical
insulation and not only by moisture. The level of Insulation Vol. 22, No. 5; October 2015.
contamination has an impact on the quantum of increase in tan [3] ASTM D3455, “Standard test methods for compatibility of construction
delta of the insulation. As we infer from the test results, the material with electrical insulating oil of petroleum origin”, ASTM
International, West Conshohocken, PA, 2011, http://www.astm.org.
contaminated sample has an increase of tan delta nearly five [4] Technical Brochure 436, Experiences in Service with New Insulation
times the values of the other samples. Hence, the level of Liquids, CIGRE, Paris, 2010, page 39-40
contamination decides the magnitude of increase in [5] Fajli Mustafa, Shaga Shaulagara, Muhammad Ihsan, “The Through
Fault Current effect of 150/20 kV Transformer to Its Insulation
dissipation factor of the transformer. Fig. 12 shows the Resistance and Tan Delta test in PT. PLN (Persero) TJBB APP
increase in tan delta of the insulation samples. Durikosambi”, International Conference on High Voltage Engineering
and Power System, October 2-5, 2017, Bali, Indonesia
4.00E-02 [6] El Beqqali, I. Zorkani, F. Rogemond, H. Chermette, R. Ben
Dissipation Factor or Tan

3.00E-02 Chaabane,M. Gamoudi , G. Guillaude, “Electrical properties of


Molybdenum disulphide MoS2. Experimental study and density
2.00E-02 functional calculation results;” Synthetic Metals, November 1997
1.00E-02 [7] IEC 60296, Fluids for Electrotechnical Applications- Mineral
Delta

Insulating Oils for Electrical Applications, International


0.00E+00 Electrotechnical Commission, 2021.
1 2 3 4 5 6 [8] IEC 60422, Mineral Insulating Oils for Electrical Applications-
Supervision and Maintenance Guidance, International Electrotechnical
Ref-ARef-B 1-A 1-B 2-A 2-B Commission, 2013
Reference Samples
I. BIOGRAPHIES
Tan Delta at 23°C Tan Delta at 90°C
Gopalan Ramesh was born in Chennai, India and graduated with a degree in
Electrical Engineering from the Annamalai University in 1989 and obtained
a Post Graduate Diploma in Engineering by Research from Auckland
Fig. 12. Increase in dissipation factor of solid insulation. University of Technology, in 2000.
He is currently with DNV as a Senior Consultant with Grid Assets
Management and Studies Group of DNV, based in Dubai in the United Arab
VI. CONCLUSION Emirates. His employment experience includes working in the General
Electric Company of India, ETEL Transformers in New Zealand, ALSTOM
The results of the tests conducted indicate that dielectric and later AREVA Transformers in New Zealand, and in the UAE. Ramesh
properties namely surface conductivity and DC resistivity of has several years extensive experience in power and distribution transformers
and shunt reactors- Design, manufacturing, testing, field diagnostics,
the solid insulation are affected by construction materials used dissolved gas analysis, factory repair, onsite repair, on-site high voltage
in the transformer industry. Increase in electrical conductivity testing, refurbishment, condition assessment and life extension up to
of the solid insulation decreases the creepage path and this 800MVA, 400kV. Ramesh has gained extensive experience in the power,
distribution transformers and shunt reactors up to 800MVA, 400kV across
may affect the clearances. If Molybdenum disulfide, which is several countries in India, New Zealand, Australia, North Africa, Middle
used in the manufacture of power transformers as a solid East, Turkey, Mexico and in Europe.
lubricant is sprayed in sufficient quantities and it spreads into Ramesh is a Senior Member of IEEE and a member of Dielectrics and
Insulation Society (DEIS) and the Power and Energy Society of IEEE.
the solid insulation either during manufacture or later when
the transformer is in service, then this may affect the electrical Ashutosh Sharma is presently working as Senior Principal Consultant in
performance of the transformer. Grids Asset Management and Studies team of DNV based in United Arab
Emirates. His expertise is in the field of power failure investigations on
capital electrical assets and network blackouts. He has performed numerous
VII. RECOMMENDATION failure investigations on assets up to 400kV. He has extensive experience in
the field of installation, testing, commissioning, and maintenance of capital
The results and discussions suggest that the manufacturers electrical equipment. In 2007 Ashutosh Sharma joined KEMA as Senior
who use the dry lubricating compound to use the same with Consultant with his enriched experience in the field of asset management and
caution. Manufacturer of power transformers should conduct delivered projects covering skills related to asset condition assessment
material compatibility tests to study the impact of starting from development of the asset health assessment data templates,
formulation of the health assessment knowledge rules to derive the health
construction materials on the solid insulation to determine index, calculation of health index.
whether there will be any issue with the performance of the He is an active member of CIGRE in the Gulf Region. He is a
transformers during tests or later in service. professionally certified project manager from 2009 and gained his
qualification from Project management Institute, USA. http://www.pmi.org.

VIII. ACKNOWLEDGMENT Hemang Thakkar is currently working with Emirates Global


Aluminium (EGA) as a Senior Manager - Energy and Electrical Projects.
The authors gratefully acknowledge the support provided He has extensive experience in the field of Electrical Power Systems
by EGA for collaborating on this experiment and for the involving various high voltage, medium voltage and low voltage electrical
contributions of Electrical Maintenance Department Staff of equipment and systems.
His experience covers design, engineering, studies, electrical protection
EGA, who helped in the experimental set up and collection of systems, maintenance aspects, failure assessments, electrical safety audits
samples for the tests. and many other aspects in power stations, transmission, and distribution
systems, in Oil & Gas and many other industries.

You might also like