BOX / ENCLOSURES ID NUMBERS GENERAL BOX, ENCLOSURE AND ACCESSORIES ENCLOSURE CODE SYSTEM ID. PLANT NO.
DESCRIPTION
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
A. Certification & 3rd Party Listing - General Purpose Boxes & Enclosures
B. Certification & 3rd Party Listing & Labeling - Explosion Proof Boxes & Enclosures
Page 1 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Equipment Marking:
Equipment shall be marked to show the environment for which it has
been evaluated. Unless otherwise specified or allowed in NEC 500.8(C)
(6), the marking shall include the information specified in (C)(1) through
(C)(5) (See Below):
SAES-P-104
B3 (1) Class
Sec. 4.1
(2) Division
(3) Material Classification Group
(4) Equipment Temperature
(5) Ambient Temperature Range
[NFPA 70, NEC 500.8(C)]
Equipment Temperature:
The marking shall specify the temperature class or operating
temperature at a 40°C ambient temperature, or at the higher ambient
temperature if the equipment is rated and marked for an ambient
temperature of greater than 40°C. SAES-P-104
B4
Exception: Equipment of the non–heat-producing type, such as junction Sec. 4.1
boxes, conduit, and fittings, and equipment of the heat-producing type
having a maximum temperature not more than 100°C shall not be
required to have a marked operating temperature or temperature class.
[NFPA 70, NEC 500.8(C)(4)]
Equipment Temperature:
The temperature class, if provided, shall be indicated using the
temperature class (T Codes) shown in Table 500.8(C) (Attachment 2).
SAES-P-104
B5 Equipment for Class I and Class II shall be marked with the maximum
Sec. 4.1
safe operating temperature, as determined by simultaneous exposure to
the combinations of Class I and Class II conditions.
[NFPA 70, NEC 500.8(C)(4)]
Class I Temperature:
The temperature marking specified in Table 500.8(C) (Attachment 2)
SAES-P-104
B6 shall not exceed the ignition temperature of the specific gas or vapor to
Sec. 4.1
be encountered.
[NFPA 70, NEC 500.8 (D)(1)]
Page 2 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
C. Material Requirements
New and Unused: General Boxes, Enclosures and accessories shall be Schedule G
C1
new and unused. Sec. 2
Free of Damage: General Boxes and Enclosures and accessories shall Schedule Q
C3
be free of damage. Att. lV
Page 3 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Drainage Openings:
Type 2, 3R, and 3RX enclosures shall have provisions for drainage.
Drainage openings shall not be less than 3.2 mm in diameter (1/8 inch in
diameter) or more than 6.4 mm in diameter (1/4 inch in diameter) unless
baffled or provided with a drainage fitting. SAES-P-104
C10
For Type 2, 3R, and 3RX enclosures that also meet the requirements of Sec. 4.1
other enclosure types, the drainage openings shall be closed by a
removable plug. The enclosure shall meet the requirements of the other
enclosure types with the plug installed.
[NEMA 250 Sec. 3.6.3]
An enclosure shall completely enclose all live parts that may be housed SAES-P-104
C12
in it. [UL 50 Sec. 6.1.1 and NEMA 250 Sec. 1.2] Sec. 4.1
Verify that all junction boxes, pull boxes, and conduit bodies are correct
SAES-P-104
C14 (size/ type) in according to NEC 314.16 and table 314.6(A) (Attachment
Sec. 4.1
5). [NFPA70, NEC 314.16]
Page 4 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Factory sealed multigang push button and similar control stations having
SAES-P-104
an internal volume exceeding 2,000 cm³ are exempted from the
D7 Sec. 7.8.1
requirement of providing with Type 300 Series stainless steel breather
Exception 2
and drain fittings, or a combination breather and drain fitting.
Remotely Controlled:
Devices are operated electrically from a pilot-type control console or
SAES-P-104
D10 panel. Pilot control panels either shall be part of the switchboard or shall
Sec. 4.1
be permitted to be at another location.
[NFPA 70, NEC 520.26(B)]
Pilot Light:
A pilot light shall be provided within the enclosure and shall be connected
to the circuit supplying the board so that the opening of the master switch
SAES-P-104
D11 does not cut off the supply to the lamp. This lamp shall be on an
Sec. 4.1
individual branch circuit having overcurrent protection rated or set at not
over 15 amperes.
[NFPA 70, NEC 520.53(G)]
Page 5 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
When pilot lights are specified on the design drawings, Separate red and SAES-P-116
D15
green colored lights shall be used to indicate motor operation status. Sec. 7.4.2 (b)
Pilot light fixture design shall be able to withstand continuous shorting of SAES-P-116
D16
the lamp terminals without affecting controller functionality. Sec. 7.4.2 (c)
Pilot light lamps shall be high density LED (Light Emitting Diode) type SAES-P-116
D17
providing a light intensity similar to an incandescent fixture. Sec. 7.4.2 (d)
The voltage rating of the indicating lights shall not be less than the
nominal voltage of a circuit to which it is connected, as specified on the SAES-P-104
D19
design drawings and Purchase Order. Sec. 4.1
[NFPA 70, NEC 110.4]
Pilot lights and pushbuttons shall meet the requirements of NEMA ICS 5, 16-SAMSS-512
D20
Part 5. Sec. 16.1.6
16-SAMSS-512
D21 Pilot lights and pushbuttons shall be heavy duty and oil tight.
Sec. 16.1.6 (a)
16-SAMSS-512
D23 Pushbuttons contact ratings shall be a minimum of A600/P600.
Sec. 16.1.6 (c)
E. Boxes and Enclosures - Class I, Division 2 or Zone 2 - Pushbutton Installation and Pre-commission
Class I, Division 1:
In Class I, Division 1 locations, switches, circuit breakers, motor
controllers, and fuses, including pushbuttons, relays, and similar devices,
SAES-P-104
E1 shall be provided with enclosures, and the enclosure in each case,
Sec. 4.1
together with the enclosed apparatus, shall be identified as a
complete assembly for use in Class I locations.
[NFPA 70, NEC 501.115(A)]
Isolating Switches:
Fused or unfused disconnect and isolating switches for transformers or
capacitor banks that are not intended to interrupt current in the normal SAES-P-104
E2
performance of the function for which they are installed shall be Sec. 4.1
permitted to be installed in general-purpose enclosures.
[NFPA 70, NEC 501.115(B)(2)]
Page 6 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Fuses:
For the protection of motors, appliances, and lamps, other than as
provided in 501.115(B)(4), standard plug or cartridge fuses shall be
permitted, provided they are placed within enclosures identified for the
location; or fuses shall be permitted if they are within general-purpose
enclosures, and if they are of a type in which the operating
SAES-P-104
E3 element is immersed in oil or other approved liquid, or the operating
Sec. 4.1
element is enclosed within a chamber hermetically sealed against the
entrance of gases and vapors, or the fuse is a nonindicating, filled,
current-limiting type.
[NFPA 70, NEC 501.115(B)(3)]
Protection Techniques:
Nonincendive circuit, nonincendive equipment and nonincendive
component protection techniques shall be permitted for equipment in SAES-P-104
E8
Class I, Division 2; Class II, Division 2; or Class III, Division 1 or 2 Sec. 4.1
locations.
[NFPA 70, NEC 500.7(F,G,H)]
Inadequate Ventilation:
In a Class I, Division 1 location that is so classified due to inadequate
SAES-P-104
E11 ventilation, electrical equipment suitable for Class I, Division 2 locations
Sec. 4.1
shall be permitted.
[NFPA 70, NEC 500.7(K)(1)]
Page 7 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Interior of a Building:
In a building located in, or with an opening into, a Class I, Division 2
location where the interior does not contain a source of flammable gas or SAES-P-104
E12
vapor, electrical equipment for unclassified locations shall be Sec. 4.1
permitted.
[NFPA 70, NEC 500.7(K)(2)]
F. Boxes and Enclosures - Class I, Division 1 or Zone 1 - Conduit Seals for Pushbutton Enclosures installation and
Pre-commissioning
Entering Enclosures:
Conduit seals shall be located in each conduit entry into an
explosionproof enclosure where either of the following apply:
(1) The enclosure contains apparatus, such as switches, circuit
breakers, fuses, relays, or resistors, that may produce arcs, sparks, or
high temperatures that are considered to be an ignition source in normal
SAES-P-104
F2 operation.
Sec. 4.1
(2) The entry is metric designator 53 (trade size 2) or larger and the
enclosure contains terminals, splices, or taps.
For the purposes of this section, high temperatures shall be considered
to be any temperatures exceeding 80 percent of the autoignition
temperature in degrees Celsius of the gas or vapor involved.
[NFPA 70, NEC 501.15(A)(1)]
Exception to 501.15(A)(1)(1):
Seals shall not be required for conduit entering an enclosure where such
switches, circuit breakers, fuses, relays, or resistors comply with one of
the following:
(1) Are enclosed within a chamber hermetically sealed against the
entrance of gases or vapors
SAES-P-104
F3 (2) Are immersed in oil in accordance with 501.115(B)(1)(2)
Sec. 4.1
(3) Are enclosed within a factory-sealed explosionproof chamber located
within the enclosure, identified for the location, and marked “factory
sealed” or equivalent, unless the enclosure entry is metric designator 53
(trade size 2) or larger
(4) Are in nonincendive circuits
[NFPA 70, NEC 501.15(A)(1)]
Conduit seals shall be installed within 450 mm (18 in.) from the
enclosure. Only explosionproof unions, couplings, reducers, elbows,
capped elbows, and conduit bodies similar to L, T, and Cross types that SAES-P-104
F5
are not larger than the trade size of the conduit shall be permitted Sec. 4.1
between the sealing fitting and the explosionproof enclosure.
[NFPA 70, NEC 501.15(A)(1)]
Page 8 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Pressurized Enclosures:
In each conduit entry into a pressurized enclosure where the conduit is
not pressurized as part of the protection system. Conduit seals shall be
SAES-P-104
F6 installed within 450 mm (18 in.) from the pressurized enclosure.
Sec. 4.1
[NFPA 70, NEC 501.15(A)(2)]
Conductor Fill:
The cross-sectional area of the conductors permitted in a seal shall not
SAES-P-104
F9 exceed 25 percent of the cross-sectional area of a rigid metal conduit of
Sec. 4.1
the same trade size unless it is specifically identified for a higher
percentage of fill. [NFPA 70, NEC501.15(C)(6)]
Fittings:
Enclosures for connections or equipment shall be provided with an
integral means for sealing, or sealing fittings listed for the location shall SAES-P-104
F11
be used. Sealing fittings shall be listed for use with one or more specific Sec. 4.1
compounds and shall be accessible.
[NFPA 70, NEC 501.15(C)(1)]
Compound:
The compound shall provide a seal against passage of gas or vapors
through the seal fitting, shall not be affected by the surrounding SAES-P-104
F12
atmosphere or liquids, and shall not have a melting point of less than Sec. 4.1
93°C (200°F).
[NFPA 70, NEC 501.15(C)(2)]
Thickness of Compounds:
Except for listed cable sealing fittings, the thickness of the sealing
compound in a completed seal shall not be less than the metric SAES-P-104
F13
designator (trade size) of the sealing fitting expressed in the units of Sec. 4.1
measurement employed, and in no case less than 16 mm (5⁄8 in.).
[NFPA 70, NEC 501.15(C)(3)]
Page 9 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Assemblies:
In an assembly where equipment that may produce arcs, sparks, or high
temperatures is located in a compartment separate from the
compartment containing splices or taps, and an integral seal is provided
SAES-P-104
F15 where conductors pass from one compartment to the other, the entire
Sec. 4.1
assembly shall be identified for the location. Seals in conduit connections
to the compartment containing splices or taps shall be provided in Class
I, Division 1 locations where required by 501.15(A)(1)(2).501.5(A)(1)(2).
[NFPA 70, NEC 501.15(C)(5)]
G. Explosionproof Enclosures and Cable Seals, Class I, Division 1 - Installation and Pre-commissioning
At Terminations:
Cable shall be sealed at all terminations. The sealing fitting shall comply
with 501.15(C). Multiconductor Type MC-HL cables with a gas/vaportight
continuous corrugated metallic sheath and an overall jacket of
SAES-P-104
G2 suitable polymeric material shall be sealed with a listed fitting after
Sec. 4.1
removing the jacket and any other covering so that the sealing compound
surrounds each individual insulated conductor in such a manner as to
minimize the passage of gases and vapors.
[NFPA 70, NEC 501.15(D)(1)]
Page 10 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
H. General Boxes and Enclosures - Class I, Division 1 or Zone 1 - Hazardous Location Enclosures installation and
Pre-commissioning
Wiring Method:
In Class I, Division 1 locations, the wiring of Threaded rigid metal conduit SAES-P-104
H2
or threaded steel intermediate metal conduit shall be permitted. Sec. 4.1
[NFPA 70, NEC 501.10(A)(1a)]
Page 11 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Grounding:
Wiring and equipment in Class I, Division 1 and 2 locations shall be
SAES-P-104
H13 grounded as specified in Article 250 and in accordance with the
Sec. 4.1
requirements of 501.30(A) and (B).
[NFPA 70, NEC 501.30]
Page 12 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Bonding:
The locknut-bushing and double-locknut types of contacts shall not be
depended on for bonding purposes, but bonding jumpers with proper
fittings or other approved means of bonding shall be used. Such means
SAES-P-104
H14 of bonding shall apply to all intervening raceways, fittings, boxes,
Sec. 4.1
enclosures, and so forth between Class I locations and the point of
grounding for service equipment or point of grounding of a separately
derived system.
[NFPA 70, NEC 501.30(A)]
Surge Protection:
In Class I, Division 1, surge arresters, surge-protective devices, and
capacitors shall be installed in enclosures identified for Class I, Division 1 SAES-P-104
H18
locations. Surge-protective capacitors shall be of a type designed for Sec. 4.1
specific duty.
[NFPA 70, NEC 501.35]
Increased safety (protection type "e") motors and terminal boxes are not
permitted in Zone 1 locations.
SAES-P-100
H19 Commentary Note:
Sec. 8.3.3
The "e" protection method is acceptable if it is used in combination with
the "d" protection method, if d" is the primary protection method.
Page 13 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Equipment suitable for Class 1, Zone 0 locations may be used in Class 1, SAES-P-100
H21
Division 1 locations. Sec. 8.3.2
REMARKS:
Page 14 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
REFERENCE DOCUMENTS:
1. Schedule G - Material, Tools and Equipment (Pro Forma MP-IK-LS Contract), March 2006
2. Schedule Q - Quality Requirements (Pro Forma Contract), November 2003 and February 2008
3. NFPA 70 - National Electrical Code (NEC), 2008
4. SAES-P-104 - Wiring Methods and Materials, January 2008
5. SAES-P-100 - Basic Power System Design Criteria, June 2007
6. SAES-P-116 - Switchgear and Control Equipment, March 2008
7. 16-SAMSS-512 - Switchracks and Factory Built Assemblies – Low Voltage, May 2007
8. ANSI/IEC 60529 - Degrees of protection provided by enclosures (IP Code), 2001
9. NEMA ICS 6 - Industrial Control & Systems Enclosures -1993 (R 2006)
10. NEMA 250 - Enclosures for Electrical Equipment (1000 Volts Maximum), 2008
11. UL 50 - Enclosures for Electrical Equipment, Non-Environmental Considerations, September 2007
ATTACHMENTS:
1. Attachment 1: Table 2 - Certification Agencies for Equipment in Hazardous Areas - SAES-P-100
2. Attachment 2: Table 500.8(C) - Classification of Maximum Surface Temperature - NFPA 70
3. Attachment 3: Table 2-1 & Table 2-2 - Guides for Comparing Specific Applications of Enclosures - NEMA 250
4. Attachment 4: Specific Enclosure Types - NEMA 250
5. Attachment 5: Table 314.16(A) - Metal Boxes - NFPA 70
6. Attachment 6: Arrangement of the IP Code - IEC 60529
7. Attachment 7: Elements of the IP Code and their Meanings - IEC 60529
NOTES:
1. Approved - Acceptable to the authority having jurisdiction (i.e., Saudi Aramco ID).
2. Identified - Recognizable as suitable for the specific application by a qualified testing laboratory (i.e., listing and/or labeling).
3. Listed - Equipment and materials included in a list published by an approved qualified organization concerned with evaluation of products or
services, that maintains periodic inspection of production of listed equipment or materials or periodic evaluation of services, and whose listing
states that the equipment, material, or services either meets appropriate designated standards or has been tested and found suitable for a
specified purpose.
4. Labeled - Equipment or materials to which has been attached a label, symbol, or other identifying mark of an approved qualified organization
concerned with product evaluation, that maintains periodic inspection of production of labeled equipment or materials, and by whose labeling
the manufacturer indicates compliance with appropriate standards or performance in a specified manner.
Page 15 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Attachment 1: Table 2 - Certification Agencies for Equipment in Hazardous Areas - SAES-P-100
Page 16 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Page 17 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Attachment 2: Table 500.8(C) - Classification of Maximum Surface Temperature - NFPA 70
Page 18 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Page 19 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Attachment 3: Table 2-1 & Table 2-2 - Guides for Comparing Specific Applications of Enclosures - NEMA 250
Page 20 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Page 21 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Attachment 4: Specific Enclosure Types - NEMA 250
Page 22 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Attachment 4: Specific Enclosure Types - NEMA 250
Page 23 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Attachment 4: Specific Enclosure Types - NEMA 250
Page 24 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Attachment 5: Table 314.16(A) - Metal Boxes - NFPA 70
Page 25 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Page 26 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Attachment 6: Arrangement of the IP Code - IEC 60529
Page 27 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Page 28 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Attachment 7: Elements of the IP Code and their Meanings - IEC 60529
Page 29 of 30
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - JUNE 2008) Rev 3 30-Jun-08
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
General Boxes Enclosures - Pushbutton and Pilot Light
SAIC-P-3010 1-Dec-09 ELECT
Control Stations & Accessories - Material Receiving
Page 30 of 30