Hilti PROFIS Engineering 3.0.

91

www.hilti.com.au
Company: Page: 1
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 11 Mar 2024 Date: 11/3/2024
Fastening Point:

Specifier's comments:

1 Input data
Anchor type and size: HUS4-H 8 h_nom1
Return period (service life in years): 50
Item number: 2293134 HUS4-H 8x45 5/-/-
Effective embedment depth: hef = 32.3 mm (hef,ETA = 30.6 mm), hnom = 42.0 mm
Material: Carbon Steel
Approval No.: ETA-20/0867
Issued I Valid: 14/7/2022 | -
Proof: Design Method AS 5216:2021, Mechanical ETA-20/0867
Stand-off installation: eb = 0.0 mm (no stand-off); t = 3.0 mm

Ledger Angle :
R L1 x L2 x tL1 x tL2 x l = 70.0 mm x 30.0 mm x 3.0 mm x 3.0 mm x 70.0 mm;

Load Point Height: hpl = 35.0 mm


Base material: 2
cracked concrete, 32MPa, f'c = 32.00 N/mm ; h = 250.0 mm, User-defined partial material safety
factor gc = 1.500
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: No reinforcement or Reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
no longitudinal edge reinforcement
Reinforcement to control splitting acc. to AS5216:2021 / SA TS 101:2015, 6.2.5.2 (b) present

R
- The anchor calculation is based on a rigid baseplate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

1
Hilti PROFIS Engineering 3.0.91

www.hilti.com.au
Company: Page: 2
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 11 Mar 2024 Date: 11/3/2024
Fastening Point:

1.1 Load combination


Case Description Forces [kN] / Moments [kNm] Seismic Fire Max. Util. Anchor [%]
1 Combination 1 N = 0.000; Vx = 0.000; Vy = 0.900; no no 56
Mx = 0.000; My = 0.000; Mz = 0.000;

2 Load case/Resulting anchor forces

Anchor reactions [kN]


Tension force: (+Tension, -Compression)
y
Anchor Tension force Shear force Shear force x Shear force y
Compression
1 2.561 0.900 0.000 0.900
1 x
max. concrete compressive strain: 0.30 [‰]
max. concrete compressive stress: 9.04 [N/mm ]
2

resulting tension force in (x/y)=(0.0/0.0): 0.000 [kN]


resulting compression force in (x/y)=(35.0/27.3): 2.561 [kN]

Anchor forces are calculated based on the assumption of a rigid baseplate.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

2
Hilti PROFIS Engineering 3.0.91

www.hilti.com.au
Company: Page: 3
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 11 Mar 2024 Date: 11/3/2024
Fastening Point:

3 Tension load ((AS 5216:2021, Section 6.2))


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel failure* 2.561 24.000 11 OK
Pull-out failure* 2.561 4.638 56 OK
Concrete Breakout failure** 2.561 9.308 28 OK
Splitting failure** N/A N/A N/A N/A

* highest loaded anchor **anchor group (anchors in tension)

3.1 Steel failure

N* £ NRd,s = f Ms,N · NRk,s AS 5216:2021, Table 3.4.2.1

NRk,s [kN] f Ms,N NRd,s [kN] N* [kN]


36.000 0.667 24.000 2.561

3.2 Pull-out failure

N* £ NRd,p = f Mp · y c · NRk,p AS 5216:2021, Table 3.4.2.1

NRk,p [kN] yc f Mp NRd,p [kN] N* [kN]


5.500 1.265 0.667 4.638 2.561

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

3
Hilti PROFIS Engineering 3.0.91

www.hilti.com.au
Company: Page: 4
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 11 Mar 2024 Date: 11/3/2024
Fastening Point:

3.3 Concrete Breakout failure

N* £ NRd,c = f Mc · NRk,c AS 5216:2021, Table 3.4.2.1


0 A
NRk,c = NRk,c · 0c,N · y s,N · y re,N · y ec1,N · y ec2,N · y M,N AS 5216:2021, Eq. 6.2.3.1
Ac,N
0 1,5
NRk,c = k1 · √f'c · hef AS 5216:2021, Eq. 6.2.3.2
0
Ac,N = scr,N · scr,N AS 5216:2021, Eq. 6.2.3.3
c
y s,N = 0.7 + 0.3 · 1.00 AS 5216:2021, Eq. 6.2.3.4
ccr,N £
1
y ec1,N = 1.00 AS 5216:2021, Eq. 6.2.3.6
2 · eN,1 £
1+ (scr,N )
1
y ec2,N = 1.00 AS 5216:2021, Eq. 6.2.3.6
2 · eN,2 £
1+ (scr,N )
2·z
y M,N = 2.0 - 1.00 AS 5216:2021, Clause 6.2.3.7
3·h ³ ef

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] fc,cyl [N/mm ]
9,390 9,390 48.4 96.9 32.00

ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N


0.0 1.000 0.0 1.000 1.000 1.000
0
z [mm] y M,N k1 NRk,c [kN] f Mc NRd,c [kN] N* [kN]
12.3 1.746 7.700 7.996 0.667 9.308 2.561

Group anchor ID
1

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

4
Hilti PROFIS Engineering 3.0.91

www.hilti.com.au
Company: Page: 5
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 11 Mar 2024 Date: 11/3/2024
Fastening Point:

4 Shear load ((AS 5216:2021, Section 7.2))


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel failure (without lever arm)* 0.900 15.040 6 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout failure** 0.900 5.331 17 OK
Concrete edge failure in direction ** N/A N/A N/A N/A

* highest loaded anchor **anchor group (relevant anchors)

4.1 Steel failure (without lever arm)

V* £ VRd,s = f Ms,V · VRk,s AS 5216:2021, Table 3.4.3.1


0
VRk,s = k7 · VRk,s AS 5216:2021, Eq. 7.2.2.2(1)

0
VRk,s [kN] k7 VRk,s [kN] f Ms,V VRd,s [kN] V* [kN]
18.800 0.800 18.800 0.800 15.040 0.900

4.2 Pryout failure

V* £ VRd,cp = f Mc · VRk,cp AS 5216:2021, Table 3.4.3.1


VRk,cp = k8 · NRk,c AS 5216:2021, Eq. 7.2.4.1(1)
0 A
NRk,c = NRk,c · c,N
0
· y s,N · y re,N · y ec1,N · y ec2,N · y M,N AS 5216:2021, Eq. 6.2.3.1
Ac,N
0 1,5
NRk,c = k1 · √f'c · hef AS 5216:2021, Eq. 6.2.3.2
0
Ac,N = scr,N · scr,N AS 5216:2021, Eq. 6.2.3.3
c
y s,N = 0.7 + 0.3 · 1.00 AS 5216:2021, Eq. 6.2.3.4
ccr,N £
1
y ec1,N = £ 1.00 AS 5216:2021, Eq. 6.2.3.6
1+ ( 2 · eV,1
scr,N )
1
y ec2,N = £ 1.00 AS 5216:2021, Eq. 6.2.3.6
1+ ( 2 · eV,2
scr,N )
y M,N =1 AS 5216:2021, Clause 6.2.3.7

2 0 2 2
Ac,N [mm ] Ac,N [mm ] ccr,N [mm] scr,N [mm] k8 fc,cyl [N/mm ]
9,390 9,390 48.4 96.9 1.000 32.00

ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N y M,N


0.0 1.000 0.0 1.000 1.000 1.000 1.000
0
k1 NRk,c [kN] f Mc VRd,cp [kN] V* [kN]
7.700 7.996 0.667 5.331 0.900

Group anchor ID
1

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

5
Hilti PROFIS Engineering 3.0.91

www.hilti.com.au
Company: Page: 6
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 11 Mar 2024 Date: 11/3/2024
Fastening Point:

5 Combined tension and shear loads (AS 5216:2021, Section 8.1.1, 8.1.2)
Steel failure

bN bV a Utilization bN,V [%] Status


0.107 0.060 2.000 2 OK

a a
bN + bV £ 1.0

Concrete failure

bN bV a Utilization bN,V [%] Status


0.552 0.169 1.500 48 OK

a a
bN + bV £ 1.0

6 Displacements (highest loaded anchor)


Short term loading:

NSk = 1.897 [kN] dN = 0.0730 [mm]


VSk = 0.667 [kN] dV = 0.0810 [mm]
dNV = 0.1090 [mm]
Long term loading:

NSk = 1.897 [kN] dN = 0.2189 [mm]


VSk = 0.667 [kN] dV = 0.1246 [mm]
dNV = 0.2519 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements
are valid without friction between the concrete and the baseplate! The gap due to the drilled hole and clearance hole tolerances are not
included in this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

6
Hilti PROFIS Engineering 3.0.91

www.hilti.com.au
Company: Page: 7
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 11 Mar 2024 Date: 11/3/2024
Fastening Point:

7 Warnings
• The anchor design methods in PROFIS Engineering require rigid baseplates per current regulations (AS 5216:2021, ETAG 001/Annex C,
EOTA TR029 etc.). This means load re-distribution on the anchors due to elastic deformations of the baseplate are not considered - the
baseplate is assumed to be sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Engineering
calculates the minimum required baseplate thickness with CBFEM to limit the stress of the baseplate based on the assumptions explained
above. The proof if the rigid baseplate assumption is valid is not carried out by PROFIS Engineering. Input data and results must be
checked for agreement with the existing conditions and for plausibility!
• In general, the conditions given in ETAG 001, Annex C, section 4.2.2.1 and 4.2.2.3 b) are not fulfilled because the diameter of the clearance
hole in the fixture acc. to Annex 3, Table 3 is greater than the values given in Annex C, Table 4.1 and AS5126 for the corresponding
diameter of the anchor. Therefore the design resistance for anchor groups is limited to twice the steel resistance (of a single anchor) in
accordance with the approval.
• Checking the transfer of loads into the base material is required in accordance with AS 5216:2021, Appendix C!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.2.2.1 of AS 5216:2021! For larger
diameters of the clearance hole, see section 2.2 of SA TS 101: 2015!
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to
be followed to ensure a proper installation.
• For the determination of the y re,v (concrete edge failure) the minimum concrete cover defined in the design settings is used as the concrete
cover of the edge reinforcement.
• Load transfer from supplementary reinforcement to the structural member shall be verified by the responsible structural engineer.
• With supplementary reinforcement and post-installed anchors, please ensure that in the jobsite the rebars are not drilled through.
• The characteristic bond resistances depend on the return period (service life in years): 50

Fastening meets the design criteria!

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

7
Hilti PROFIS Engineering 3.0.91

www.hilti.com.au
Company: Page: 8
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 11 Mar 2024 Date: 11/3/2024
Fastening Point:

8 Installation data
Ledger Angle: L1 x L2 x tL1 x tL2 x l = 70.0 mm x 30.0 mm x 3.0 mm x 3.0 mm x Anchor type and size: HUS4-H 8 h_nom1
2
70.0 mm; Steel: Custom baseplate material; E = 200,000.00 N/mm ; fyk =
2
235.00 N/mm
Hole diameter in the fixture: df = 12.0 mm Item number: 2293134 HUS4-H 8x45 5/-/-
Plate thickness (input): 3.0 mm Maximum installation torque: -
Recommended plate thickness: not calculated Hole diameter in the base material: 8.0 mm
Drilling method: Hammer drilled Hole depth in the base material: 52.0 mm
Cleaning: Clean the drill hole. Under the conditions - according to fastener size Minimum thickness of the base material: 82.0 mm
and drilling direction - given in the ETA and MPII (IFU), the cleaning of the drill
hole may be omitted.

Hilti HUS screw anchor with 40 mm embedment, 8 h_nom1, Steel galvanized, installation per ETA-20/0867

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Manual blow-out pump • SIW 6-A22 Impact Screw Driver
• Properly sized drill bit

y
35.0 35.0

15.0

15.0
13.5

1
x
15.0

15.0

35.0 35.0

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y
1 0.0 0.0 - - - -

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

8
Hilti PROFIS Engineering 3.0.91

www.hilti.com.au
Company: Page: 9
Address: Specifier:
Phone I Fax: | E-Mail:
Design: Concrete - 11 Mar 2024 Date: 11/3/2024
Fastening Point:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas
and security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be
strictly complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior
to using the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you
put in. Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by
you. Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with
regard to compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to
interpret norms and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability
for a specific application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for
the regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do
not use the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software
in each case by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or
damaged data or programs, arising from a culpable breach of duty by you.

Input data and results must be checked for conformity with the existing conditions and for plausibility!
PROFIS Engineering ( c ) 2003-2024 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan

You might also like