1 2 3 4 5 6 7 8 9 10 11 12
This document is protected by copyright and design Rights. Any unauthorised reproduction would be an infringement and may lead to appropriate legal action
@ Ethical Power Connections Copyright
DNO CUSTOMER 132/33kV OUTDOOR COMPOUND CUSTOMER'S GRP - LV AREA
Do not scale from this drawing
ETX (33/0.4kV)
A A
A101 132kV A103 132kV A102 132kV A110 132kV Legend:
EARTH SWITCH DISCONNECTOR EARTH SWITCH CIRCUIT BREAKER
Serial cables (RS485, DNP3)
Ethernet cables (Cat-6a, IEC 61850)
Multicore cables
B Multipair cables B
Notes:
1. SCADA marshalling kiosk contains a Hitachi RTU530,
consisting of the following modules:
1.1. 1x 530CID02 - base unit with 2 ethernet ports
1.2. 4x 530BID01 R0001 - 16 binary inputs (24-60VDC)
1.3. 1x 530BOD01 R0001 - 8 relay outputs
1.4. 1x 750 datapoint and HMI license
C 2. SCADA marshalling kiosk Managed Network Switch and C
Redundancy Box are Moxa PT-510-SS-LC-HV and
PT-G503-PHR-PTP-HV respectively.
3. Ethernet network to be configured and managed as a
single VLAN.
PTX (132/33kV) 4. Unless stated otherwise, all Ethernet devices are to be
configured with a subnet mask of 255.255.0.0.
132kV RELAY PANEL 5. SNTP server clock IP addresses are:
A112 132kV A113 132kV A111 132kV 132/33kV TRANS.
EARTH SWITCH DISCONNECTOR EARTH SWITCH BUND PUMP 5.1. Primary source - Hopf 6890 (10.0.0.1)
5.2. Secondary source - Moxa PT-G503 (10.0.0.2)
D 6. Secondary SNTP server is also an SNTP client to the D
SUMP PUMP primary source. Time may not remain accurate if primary
MPR BUPR
STATION
DNO'S GRP CUSTOMER'S GRP - HV AREA 120Ω source fails, however priority is to maintain relative
synchronisation between IEC 61850 IEDs.
7. PPC to communicate with the RTU and IEDs over IEC
61850 MMS.
FIRE ALARM
E E
110VDC BCU
HMI PC
CUSTOMER'S
SCADA MK
33kV SW/GEAR
F F
H00 H02 H04 H06 H08 H10 H12
GNSS RED MANAGED
BCU TXPR BCU BCU AVC BCU BCU BCU BCU SCADA RTU
CLOCK BOX NETWORK SWITCH
G G
G99AC6
PANEL
PPC PANEL
H POI METER H
BY OTHERS IEC 61850 ARCHITECTURE UPDATED
01
DWG AW KF 21/09/23
FIRST ISSUE
00
TARIFF DEHUMIDIFIER DWG PF KF 21/06/23
METER
Description
MAIN REV
DESIGNED CHECKED APPROVED DATE
I TARIFF I
METER
CHECK
Unit 9. Dunchideock Barton . Dunchideock .
CONNECTION
DNO Exeter . Devon . EX2 9UA
CONTROL (t) 01726 218618
WALLBOX
INTERFACE PANEL www.ethical-power.com
J Project Title: SIZING JOHN J
Description: COMMUNICATION DIAGRAM
IEC 61850 ETHERNET COMMUNICATION SETTINGS NON-IEC 61850 ETHERNET COMMUNICATION SETTINGS DNP3 SERIAL COMMUNICATION SETTINGS
PANEL DEVICE IP ADDRESS MAC ADDRESS APPLICATION ID PANEL DEVICE IP ADDRESS DEVICE SLAVE ID Location co-ord: T. B. A.
33kV SWITCHGEAR - H00 BCU 10.0.1.01 01-0C-CD-01-00-01 01 PPC PANEL PPC 10.0.1.250 132kV RP - MPR 11 Site address: T. B. A
BCU 10.0.1.21 01-0C-CD-01-00-21 21 CLK - HOPF 6890 10.0.0.1 132kV RP - BUPR 12
33kV SWITCHGEAR - H02
K
TXPR 10.0.1.22 01-0C-CD-01-00-22 22 RBX - PT-G503 10.0.0.2 K
SCADA MARSHALLING KIOSK
BCU 10.0.1.41 01-0C-CD-01-00-41 41 RTU - RTU530 10.0.0.3
33kV SWITCHGEAR - H04
AVR 10.0.1.42 01-0C-CD-01-00-42 42 MNS - PT-510 10.0.0.4
33kV SWITCHGEAR - H06 BCU 10.0.1.61 01-0C-CD-01-00-61 61 PH101 - 7KE85 10.0.2.1 Drg No: EPC-0431-P-E-SCADA-001
33kV SWITCHGEAR - H08 BCU 10.0.1.81 01-0C-CD-01-00-81 81 G99AC6 PANEL PH201 - Q200 10.0.2.2 Scale: N.T.S.
33kV SWITCHGEAR - H10 BCU 10.0.1.101 01-0C-CD-01-01-01 101 RA001 - 8030HEPTA 10.0.2.3 Job No: 0431
L 33kV SWITCHGEAR - H12 BCU 10.0.1.121 01-0C-CD-01-01-21 121 MAIN METER 10.0.3.1 Drawn by: DWG
L
TARIFF METERING PANEL
CHECK METER 10.0.3.2 Checked by: PF
HMI PC HMI PC 10.0.4.1 Date: 21/06/2023
1 2 3 4 5 6 7 8 9 10 11 12