You are on page 1of 38

Chapter 14

Gas-Vapor Mixtures and Air-Conditioning

Study Guide in PowerPoint

to accompany

Thermodynamics: An Engineering Approach, 7th edition


by Yunus A. engel and Michael A. Boles
We will be concerned with the mixture of dry air and water vapor. This mixture is
often called atmospheric air.

The temperature of the atmospheric air in air-conditioning applications ranges from


about 10 to about 50oC. Under these conditions, we treat air as an ideal gas with
constant specific heats. Taking Cpa = 1.005 kJ/kgK, the enthalpy of the dry air is
given by (assuming the reference state to be 0oC where the reference enthalpy is
taken to be 0 kJ/kga)

The assumption that the water vapor is an ideal gas is valid when the mixture
temperature is below 50oC. This means that the saturation pressure of the water
vapor in the air-vapor mixture is below 12.3 kPa. For these conditions, the enthalpy
of the water vapor is approximated by hv(T) = hg at mixture temperature T. The
following T-s diagram for water illustrates the ideal-gas behavior at low vapor
pressures. See Figure A-9 for the actual T-s diagram.

2
For more information and animations illustrating this topic visit the Animation
Library developed by Professor S. Bhattacharjee, San Diego State University, at
this link.
test.sdsu.edu/testhome/vtAnimations/index.html

The saturated vapor value of the enthalpy is a function of temperature and can be
expressed as

Note: For the dry air-water vapor mixture, the partial pressure of the water vapor in
the mixture is less that its saturation pressure at the temperature.

Pv Psat @Tmix 3
Consider increasing the total pressure of an air-water vapor mixture while the
temperature of the mixture is held constant. See if you can sketch the process on the
P-v diagram relative to the saturation lines for the water alone given below. Assume
that the water vapor is initially superheated.
P

When the mixture pressure is increased while keeping the mixture temperature
constant, the vapor partial pressure increases up to the vapor saturation pressure at
the mixture temperature and condensation begins. Therefore, the partial pressure of
the water vapor can never be greater than its saturation pressure corresponding to
the temperature of the mixture.

4
Definitions

Dew Point, Tdp

The dew point is the temperature at which vapor condenses or solidifies when cooled
at constant pressure.

Consider cooling an air-water vapor mixture while the mixture total pressure is held
constant. When the mixture is cooled to a temperature equal to the saturation
temperature for the water-vapor partial pressure, condensation begins.

When an atmospheric air-vapor mixture is cooled at constant pressure such that the
partial pressure of the water vapor is 1.491 kPa, then the dew point temperature of
that mixture is 12.95oC. Steam
375

325

275

225
T [C]

175

125 1.491 kPa

75

25
TDP
-25
0 2 4 6 8 10 12 5
s [kJ/kg-K]
Relative Humidity,
Mass of vapor in air m
v
Mass of in saturated air mg
Pv

Pg
Pv and Pg are shown on the following T-s diagram for the water-vapor alone.
Steam
125

75
T [C]

Tm 25 Pg = 3.169 kPa o Vapor State


Tdp Pv = 1.491 kPa

-25
0 2 4 6 8 10 12

s [kJ/kg-K]

Since Pv 1491
. kPa
Pg Pv , 1 or 100%, 0.47
Pg 3169
. kPa
6
Absolute humidity or specific humidity (sometimes called humidity ratio),
Mass of water vapor in air mv

Mass of dry air ma
PVM v / ( Ru T ) Pv M v
v

PaVM a / ( Ru T ) Pa M a
P Pv
0.622 v 0.622
Pa P Pv
Using the definition of the specific humidity, the relative humidity may be expressed
as
P 0.622Pg
and
(0.622 ) Pg P Pg
Volume of mixture per mass of dry air, v
V m R T /P
v m m m m
ma ma
After several steps, we can show (you should try this)

V RT
v va a m
ma Pa 7
So the volume of the mixture per unit mass of dry air is the specific volume of the dry
air calculated at the mixture temperature and the partial pressure of the dry air.

Mass of mixture
mv
m ma mv ma (1 ) ma (1 )
ma
m a
Mass flow rate of dry air,

Based on the volume flow rate of mixture at a given state, the mass flow rate of dry
air is

V m3 / s kga
m a 3

v m / kga s
Enthalpy of mixture per mass dry air, h

Hm Ha Hv ma ha mv hv
h
ma ma ma
ha hv
8
Example 14-1

Atmospheric air at 30oC, 100 kPa, has a dew point of 21.3oC. Find the relative
humidity, humidity ratio, and h of the mixture per mass of dry air.

Pv 2.548 kPa
0.6 or 60%
Pg 4.247 kPa

9
2.548 kPa kgv
0.622 0.01626
(100 2.548) kPa kga

h ha hv
C p , a T ( 25013
. 182
. T)
kJ kgv kJ
1005
. (30 C ) 0.01626
o
. 182
(25013 o
. (30 C ))
kga C
o
kga kgv
kJ
7171
.
kga

10
Example 14-2

If the atmospheric air in the last example is conditioned to 20oC, 40 percent relative
humidity, what mass of water is added or removed per unit mass of dry air?

At 20oC, Pg = 2.339 kPa.


Pv Pg 0.4(2.339 kPa ) 0.936 kPa
Pv 0.936 kPa
w 0.622 0.622
P Pv (100 0.936) kPa
kg
0.00588 v
kga
The change in mass of water per mass of dry air is

mv , 2 mv ,1
2 1
ma
mv , 2 mv ,1 kgv
(0.00588 0.01626)
ma kga
kgv
0.01038 11
kga
Or, as the mixture changes from state 1 to state 2, 0.01038 kg of water vapor is
condensed for each kg of dry air.

Example 14-3

Atmospheric air is at 25oC, 0.1 MPa, 50 percent relative humidity. If the mixture is
cooled at constant pressure to 10oC, find the amount of water removed per mass of
dry air.

Sketch the water-vapor states relative to the saturation lines on the following T-s
diagram.
T

s
At 25 C, Psat = 3.170 kPa, and with 1 = 50%
o

Pv ,1 1 Pg ,1 0.5(3.170 kPa ) 1.585 kPa


Tdp ,1 Tsat @ Pv 13.8o C
12
Pv ,1 15845
. kPa
w1 0.622 0.622
P Pv ,1 (100 15845
. ) kPa
kgv
0.01001
kga
Therefore, when the mixture gets cooled to T2 = 10oC < Tdp,1, the mixture is saturated,
and 2 = 100%. Then Pv,2 = Pg,2 = 1.228 kPa.
Pv ,2 1.228 kPa
w2 0.622 0.622
P Pv , 2 (100 1.228) kPa
kg v
0.00773
kg a
The change in mass of water per mass of dry air is
mv , 2 mv ,1
2 1
ma
kgv
(0.00773 0.01001)
kga
kg
0.00228 v
kga 13
Or as the mixture changes from state 1 to state 2, 0.00228 kg of water vapor is
condensed for each kg of dry air.

Steady-Flow Analysis Applied to Gas-Vapor Mixtures

We will review the conservation of mass and conservation of energy principles as


they apply to gas-vapor mixtures in the following example.

Example 14-3

Given the inlet and exit conditions to an air conditioner shown below. What is the
heat transfer to be removed per kg dry air flowing through the device? If the volume
flow rate of the inlet atmospheric air is 17 m3/min, determine the required rate of heat
transfer. Cooling fluid
In Out Insulated flow duct

Atmospheric
air

T2 = 20oC
T1 = 30oC

P2 = 98 kPa

P1 =100 kPa
1 = 80%
Condensate
at 20oC
2 = 95%

V&1 = 17m3/min 14
Before we apply the steady-flow conservation of mass and energy, we need to decide
if any water is condensed in the process. Is the mixture cooled below the dew point
for state 1?
Pv ,1 1 Pg ,1 0.8(4.247 kPa ) 3.398 kPa
Tdp ,1 Tsat @ Pv 26.01o C

So for T2 = 20oC < Tdp, 1, some water-vapor will condense. Let's assume that the
condensed water leaves the air conditioner at 20oC. Some say the water leaves at the
average of 26 and 20oC; however, 20oC is adequate for our use here.

Apply the conservation of energy to the steady-flow control volume


2 2
V V
Q net m i (h gz ) i W net m e (h gz ) e
inlets 2 exits 2
Neglecting the kinetic and potential energies and noting that the work is zero, we get

Q net m a1ha1 m v1hv1 m a 2 ha 2 m v 2 hv 2 m l 2 hl 2


Conservation of mass for the steady-flow control volume is

m m
inlets
i
exits
e

15
For the dry air:
m a1 m a 2 m a
For the water vapor:
m v1 m v 2 m l 2
The mass of water that is condensed and leaves the control volume is

m l 2 m v1 m v 2
m a ( 1 2 )
Divide the conservation of energy equation by m a , then
Q net
ha1 1hv1 ha 2 2 hv 2 ( 1 2 )hl 2
m a
Q net
ha 2 ha1 2 hv 2 1hv1 ( 1 2 )hl 2
m a
Q net
C pa (T2 T1 ) 2 hv 2 1hv1 ( 1 2 )hl 2
m a

16
Now to find the 's and h's.

0.622 Pv1 0.622(3.398)


1
P1 Pv1 100 3.398
kg v
0.02188
kg a
Pv 2 2 Pg 2
(0.95)(2.339 kPa ) 2.222 kPa
0.622 Pv 2 0.622(2.222)
2
P2 Pv 2 98 2.222
kgv
0.01443
kga

17
Using the steam tables, the h's for the water are
kJ
hv1 2555.6
kgv
kJ
hv 2 2537.4
kgv
kJ
hl 2 83.91
kg v

The required heat transfer per unit mass of dry air becomes

Q&net
C pa (T2 T1 ) 2 hv 2 1hv1 (1 2 ) hl 2
m&a
kJ kg v kJ
1.005 (20 30) o
C 0.01443 (2537.4 )
kg a C
o
kg a kgv
kg v kJ kg kJ
0.02188 (2555.6 ) (0.02188 0.01443) v (83.91 )
kg a kg v kg a kg v
kJ
28.73
kg a

18
The heat transfer from the atmospheric air is
Q&net kJ
qout 28.73
m&a kg a
The mass flow rate of dry air is given by V1
kJ m a
RaT1
0.287
kg a K
(30 273) K 3
m kPa
v1
v1
Pa1 (100 3.398) kPa kJ m3
17
m3 m&a min 18.89 kg a
0.90
kg a m3 min
0.90
kg a

kg kJ 1min 1kWs
Q&out m&a qout 18.89 a (28.73 )
min kg a 60s kJ
0.2843 Tons
9.04 kW 2.57 Tons of refrigeration
kW

19
The Adiabatic Saturation Process

Air having a relative humidity less than 100 percent flows over water contained in a
well-insulated duct. Since the air has < 100 percent, some of the water will
evaporate and the temperature of the air-vapor mixture will decrease.

20
If the mixture leaving the duct is saturated and if the process is adiabatic, the
temperature of the mixture on leaving the device is known as the adiabatic
saturation temperature.

For this to be a steady-flow process, makeup water at the adiabatic saturation


temperature is added at the same rate at which water is evaporated.

We assume that the total pressure is constant during the process.

Apply the conservation of energy to the steady-flow control volume


2 2
V V
Q net m i (h gz ) i W net m e (h gz ) e
inlets 2 exits 2
Neglecting the kinetic and potential energies and noting that the heat transfer and
work are zero, we get
m a1ha1 m v1hv1 m l 2 hl 2 m a 2 ha 2 m v 2 hv 2
Conservation of mass for the steady-flow control volume is

m m
inlets
i
exits
e

21
For the dry air: m a1 m a 2 m a
For the water vapor:
m v1 m l 2 m v 2
The mass flow rate water that must be supplied to maintain steady-flow is,

m l 2 m v 2 m v1
m a ( 2 1 )
Divide the conservation of energy equation by m a , then

ha1 1hv1 ( 2 1 )hl 2 ha 2 2 hv 2

What are the knowns and unknowns in this equation?

22
Solving for 1 ha 2 ha1 2 (hv 2 hl 2 )
1
(hv1 hl 2 )
C pa (T2 T1 ) 2 h fg 2

(hg1 h f 2 )
Pv1
Since 1 is also defined by 1 0.622
P1 Pv1

1 P1
We can solve for Pv1. Pv1
0.622 1

Pv1
Then, the relative humidity at state 1 is
1
Pg1
23
Example 14-4

For the adiabatic saturation process shown below, determine the relative humidity,
humidity ratio (specific humidity), and enthalpy of the atmospheric air per mass of dry
air at state 1.

24
Using the steam tables:
kJ
hf 2 67.2
kg v
kJ
hv1 2544.7
kg v
kJ
h fg 2 2463.0
kg v

From the above analysis


C pa (T2 T1 ) 2 h fg 2
1
(hg1 h f 2 )
kJ kg v kJ

o
1.005 o
16 24 C 0.0115 (2463.0 )
kg a C kg a kg v

kJ
(2544.7 67.2)
kg v
kg v
0.00822
kg a 25
We can solve for Pv1.
1 P1
Pv1
0.622 1
0.00822(100kPa)

0.622 0.00822
1.3 kPa
Then the relative humidity at state 1 is
Pv1 Pv1
1
Pg1 Psat @ 24o C
1.3 kPa
0.433 or 43.3%
3.004 kPa
The enthalpy of the mixture at state 1 is
h1 ha1 1hv1
C paT1 1hv1
kJ kg v kJ
1.005 (24 o
C ) 0.00822 2544.7
kg a o C kg a kg v
kJ
45.04 26
kg a
Wet-Bulb and Dry-Bulb Temperatures

In normal practice, the state of atmospheric air is specified by determining the wet-
bulb and dry-bulb temperatures. These temperatures are measured by using a device
called a psychrometer. The psychrometer is composed of two thermometers
mounted on a sling. One thermometer is fitted with a wet gauze and reads the wet-
bulb temperature. The other thermometer reads the dry-bulb, or ordinary,
temperature. As the psychrometer is slung through the air, water vaporizes from the
wet gauze, resulting in a lower temperature to be registered by the thermometer. The
dryer the atmospheric air, the lower the wet-bulb temperature will be. When the
relative humidity of the air is near 100 percent, there will be little difference between
the wet-bulb and dry-bulb temperatures. The wet-bulb temperature is approximately
equal to the adiabatic saturation temperature. The wet-bulb and dry-bulb
temperatures and the atmospheric pressure uniquely determine the state of the
atmospheric air.

27
The Psychrometric Chart

For a given, fixed, total air-vapor pressure, the properties of the mixture are given in
graphical form on a psychrometric chart.

The air-conditioning processes:

28
29
Example 14-5

Determine the relative humidity, humidity ratio (specific humidity), enthalpy of the
atmospheric air per mass of dry air, and the specific volume of the mixture per mass
of dry air at a state where the dry-bulb temperature is 24oC, the wet-bulb temperature
is 16oC, and atmospheric pressure is 100 kPa.

From the psychrometric chart read


44%
gv kgv
8.0 0.008
kga kga
kJ
h 46
kga
m3
v 0.853
kga
NOTE: THE ENTHALPY READ FROM THE PSYCHROMETRIC CHART
IS THE TOTAL ENTHALPY OF THE AIR-VAPOR MIXTURE PER UNIT
MASS OF DRY AIR. h= H/ma = ha + hv
30
Example 14-6

For the air-conditioning system shown below in which atmospheric air is first heated
and then humidified with a steam spray, determine the required heat transfer rate in
the heating section and the required steam temperature in the humidification section
when the steam pressure is 1 MPa.

31
The psychrometric diagram is
Psychrometric Diagram
0.050

0.045 Pressure = 101.3 [kPa]


0.040

0.035
0.8
Humidity Ratio

0.030 30 C
0.025 0.6

0.020 h3 =48 kJ/kga


20 C 0.4
0.015 h2 =37 kJ/kga
3
0.010 h1 =17 kJ/kga1 10 C
0.2
3 =0.0091kgv/kga
0.005 0C
1 = 2 =0.0049 kgv/kga
2
0.000
-10 -5 0 5 10 15 20 25 30 35 40
v1 =0.793 m^3/kga T [C]

Apply conservation of mass and conservation of energy for steady-flow to process


1-2.

Conservation of mass for the steady-flow control volume is

m m
inlets
i
exits
e 32
For the dry air
m a1 m a 2 m a
For the water vapor (note: no water is added or condensed during simple heating)
m v1 m v 2
Thus,
2 1
Neglecting the kinetic and potential energies and noting that the work is zero, and
letting the enthalpy of the mixture per unit mass of air h be defined as
h ha hv
we obtain
E in E out
Q in m a h1 m a h2
Q in m a (h2 h1 )

33
Now to find the m
a and h's using the psychrometric chart.
At T1 = 5oC, 1 = 90%, and T2 = 24oC:

The mass flow rate of dry air is given by


V1
m a
v1
34
m3
60
min kga 1 min kga
m a 3
75.66 1261
.
m min 60s s
0.793
kga
The required heat transfer rate for the heating section is

kga kJ 1kWs
Qin 1261
. (37 17)
s kga kJ
25.22 kW
This is the required heat transfer to the atmospheric air. List some ways in which this
amount of heat can be supplied.

At the exit, state 3, T3 = 25oC and 3 = 45%. The psychrometric chart gives

35
Apply conservation of mass and conservation of energy to process 2-3.

Conservation of mass for the steady-flow control volume is

m m
inlets
i
exits
e

For the dry air


m a 2 m a 3 m a
For the water vapor (note: water is added during the humidification process)

m v 2 m s m v 3
m s m v 3 m v 2
m s m a ( 3 2 )
kga kgv
1261
. (0.0089 0.0049)
s kga
kgv
0.00504
s 36
Neglecting the kinetic and potential energies and noting that the heat transfer and
work are zero, the conservation of energy yields

E in E out
m a h2 m s hs m a h3
m s hs m a (h3 h2 )
Solving for the enthalpy of the steam,

m a ( 3 2 )hs m a (h3 h2 )
h3 h2
hs
3 2

37
kJ
(48 37)
kg a
hs
kg v
(0.0089 0.0049)
kg a
kJ
2750
kg v

At Ps = 1 MPa and hs = 2750 kJ/kgv, Ts = 179.88oC and the quality xs = 0.985.

See the text for applications involving cooling with dehumidification, evaporative
cooling, adiabatic mixing of airstreams, and wet cooling towers.

38

You might also like