Earthing
• Connecting above ground non conducting metal part
to below ground buried metal is earthing or
grounding.
• Protect human against electric shock, protect
equipment from over voltage, provide safe path for
lighting currents and prevent accumulation of static
charges.
• Topologies
i. AC Substation grounding.[IEEE-80-1992]
ii. Generating station grounding.[IEEE-665-1995]
iii. Industrial and commercial power system
grounding.[IEEE-142-2007]
AC Substation grounding
Definitions
3.1 auxiliary ground electrode:A ground electrode with certain design or operating
constraints. Its primary function may be other than conducting the ground fault
current into the earth.
3.2 continuous enclosure:A bus enclosure in which the consecutive sections of the
housing along the same phase conductor are bonded together to provide an
electrically continuous current path throughout the entire enclosure length. Cross-
bondings, connecting the other phase enclosures, are made only at the extremities
of the installation and at a few selected intermediate points.
3.3 dc offset: Difference between the symmetrical current wave and the actual current
wave during a power system transient condition. Mathematically, the actual fault
current can be broken into two parts, a symmetrical alternating component and a
unidirectional (dc) component. The unidirectional component can be of either
polarity, but will not change polarity, and will decrease at some predetermined
rate.
3.4 decrement factor: An adjustment factor used in conjunction with the
symmetrical ground fault current parameter in safety-oriented grounding
calculations. It determines the rms equivalent of the asymmetrical current wave
for a given fault duration, t f, accounting for the effect of initial dc offset and its
attenuation during the fault.
• 3.5 effective asymmetrical fault current:
• The rms value of asymmetrical current wave, integrated over the
• interval of fault duration (see Figure 1).Where IF is the effective asymmetrical fault
current in A. I f is the rms symmetrical ground fault current in A . D f is the
decrement factor IF = Df × I f.
• 3.6 enclosure currents:
Currents that result from the voltages induced in the metallic
enclosure by the current(s) flowing in the enclosed
conductor(s).
3.7 fault current division factor: A factor representing the
inverse of a ratio of the symmetrical fault current to that
portion of the current that flows between the grounding grid
and surrounding earth.
• S f= Ig/3I0 Where S f is the fault current division factor Ig is the
rms symmetrical grid current in Amps.
I0 is the zero-sequence fault current in Amps.
3.11 ground current:
A current flowing into or out of the earth or its equivalent serving as a ground.
3.12 ground electrode:
A conductor imbedded in the earth and used for collecting ground current from or
dissipating ground current into the earth.
3.13 ground mat:
A solid metallic plate or a system of closely spaced bare conductors that are
connected to
and often placed in shallow depths above a ground grid or elsewhere at the earth’s
surface, in order to obtain
an extra protective measure minimizing the danger of the exposure to high step or
touch voltages in a critical
operating area or places that are frequently used by people. Grounded metal
gratings, placed on or above the
soil surface, or wire mesh placed directly under the surface material, are common
forms of a ground mat.
3.14 ground potential rise (GPR):
The maximum electrical potential that a substation grounding grid may
attain relative to a distant grounding point assumed to be at the potential of remote
earth. This voltage, GPR is equal to the maximum grid current times the grid
resistance.(GPR=IG X Rg).
The different potential at different parts of the person experiencing the GPR
creates problem. GPR can be plotted using computer programs. It varies with
earthing grid configuration.
• 3.15 ground return circuit: A circuit in which the earth or an equivalent
conducting body is utilized to complete the circuit and allow current circulation
from or to its current source.
• 3.19 maximum grid current: A design value of the maximum grid current,
defined as follows:
IG = Df × Ig.
• Where IG is the maximum grid current in Amps,
Df is the decrement factor for the entire duration of fault (tf ) given in
sec,
Ig is the rms symmetrical grid current in A.
• 3.20 mesh voltage: The maximum touch voltage within a mesh of a ground
grid.
• 3.21 metal-to-metal touch voltage: The difference in potential between
metallic objects or structures within the substation site that may be bridged by
direct hand-to-hand or hand-to-feet contact.
• 3.23 Step voltage: The difference in surface potential experienced by a
person bridging a distance of 1 m with the feet without contacting any
grounded object.
• 3.24 Touch voltage: The potential difference between the ground potential
rise (GPR) and the surface potential at the point where a person is standing
while at the same time having a hand in contact with a grounded structure.
• 3.25 Transferred voltage: A special case of the touch voltage where a
voltage is transferred into or out of the substation from or to a remote point
external to the substation.
• 3.26 Transient enclosure voltage (TEV): Very fast transient phenomena,
which are found on the grounded enclosure of GIS systems. Typically,
ground leads are too long (inductive) at the frequencies of interest to
effectively prevent the occurrence of TEV. The phenomenon is also known
as transient ground rise (TGR) or transient ground potential rise (TGPR).
Figure —Basic shock situations
[B34] Dalziel, C. F., and Massogilia, F. P., “Let-go currents and voltages,” AIEE
Transactions on PowerApparatus and Systems, vol. 75, part II, pp. 49–56, 1956.
Permissible currents
CURRENT Effect
(mA for 0.01 -
1sec)
AC(50- DC
60)Hz
Hand to Hand 0.5 2 Startle reaction
Strong muscular
5 25
reaction
100 350
Ventricular fibrillation
IEC 60479-2 (1987-03), Effect of current passing through human body—Part II: Special aspects.
• The energy absorbed by the body as described by the following equation:
SB=(IB)2 x ts ---------1
[B32] Dalziel, C. F., and Lee, R. W., “Reevaluation of lethal electric currents,” IEEE
Transactions on Industry and General Applications, vol. IGA-4, no. 5, pp. 467–476, Oct. 1968.
Touch and step Voltage calculation
The current, Ib, flows from one foot F1 through the body of the person to the other foot F2.
ZTh = 2Rf = 6ƿ.
Rf is the ground resistance of one foot (with presence of the substation grounding system ignored) in
Ω.
Estep = IB(RB + 6.0ρ).
Correction factor for foot resistance
• Gravel is put on the surface of the substation to
increase the foot contact resistance.
• Rf= (ƿ/4b)Cs
• Cs=1-0.09[(1- ƿ/ƿs) /(2hs+0.09)].
• ℎs = height of gravel assumed as 100mm.
• ƿs = resistivity of gravel , range from 1000 to 5000 Ω-m.
• ƿ = soil resistivity (100 Ω-m).
• Cs= will be approximately 0.7 to 0.8.
[B143] Thapar, B., Gerez, V., and Kejriwal, H., “Reduction factor for the ground resistance of
the foot insubstation yards,” IEEE Transactions on Power Delivery, vol. 9, no. 1, pp. 360–368,
Jan. 1994.
Step and touch voltage criteria
• Estep = (RB + 2Rf ) ⋅ IB
• Etouch = (RB + Rf ⁄ 2) ⋅ IB
• SB=(IB)2 x ts
50 kg(110 lb) SB = 0.0135
70 kg (155 lb) SB = 0.0246
• Estep50= (1000 + 6Cs ⋅ ρs)0.116/ts ½ .
• Estep70= (1000 + 6Cs ⋅ ρs)0.157/ts ½ .
• Etouch50= (1000 + 1.5Cs ⋅ ρs)0.116/ts ½.
• Etouch70= (1000 + 1.5Cs ⋅ ρs)0.157/ts ½.
Estep is the step voltage in V
Etouch is the touch voltage in V
Cs is determined from Equation
ρs is the resistivity of the surface material in Ω·m
ts is the duration of shock current in seconds
If no protective surface layer is used, then Cs =1 and ρs = ρ.
The metal-to-metal touch voltage limits are derived from the touch voltage
equations, Metal-to-metal contact,
both hand-to-hand and hand-to-feet, will result in ρs = 0.
Therefore the total resistance of the accidental circuit is equal to the body resistance,
RB.
• Emm-touch50= 116/ts ½..
• Etmm-touch70= 157/ts ½..
E mm is the metal-to-metal touch voltage in V.
The actual step voltage, touch voltage, or metal-to-metal touch voltage should be
less than the respective maximum allowable voltage limits to ensure safety
Conductor
• Basic requirements:
i. Have sufficient conductivity, so that it will not contribute substantially to local voltage
differences.
ii. Resist fusing and mechanical deterioration under the most adverse combination of a
fault magnitude and duration.
iv. Be able to maintain its function even when exposed to corrosion or physical abuse.
v. The ultimate value of current used to determine the conductor size should take into
account the possibility of future growth. It is less costly to include an adequate margin
in conductor size during the initial design than to try to reinforce a number of ground
leads at a later date
Choice of material for conductors
and related corrosion problems
• Copper
i. Copper is a common material used for grounding. Copper
conductors, in addition to their high conductivity.
ii. Have the advantage of being resistant to most underground
corrosion because copper is cathodic with respect to most other
metals that are likely to be buried in the vicinity.
iii. Costly and theft issue.
• Aluminium
i. Less costly.
ii. Aluminium itself may corrode in certain soils. The layer of
corroded aluminium material is nonconductive for all practical
grounding purposes.
iii. Gradual corrosion caused by alternating currents may also be a
problem under certain conditions.
• Steel
i. Steel may be used for ground grid conductors and rods. Such a
design requires that attention is paid to the corrosion of the steel.
ii. Use of a galvanized or corrosion resistant steel, in combination
with cathodic protection, is typical for steel grounding systems.
• Other considerations
i. Insulation of the sacrificial metal surfaces with a coating such as
plastic tape, asphalt compound, or both.
ii. Routing of buried metal elements so that any copper-based
conductor will cross water pipe lines or similar objects made of
other uncoated metals as nearly as possible at right angles, and
then applying an insulated coating to one metal or the other where
they are in proximity. The insulated coating is usually applied to
the pipe.
iii. Cathodic protection using sacrificial anodes or impressed current
systems.
iv. Use of non-metallic pipes and conduits.
Conductor sizing factors
I is the rms current in kA
Amm2 is the conductor cross section in mm2
Tm is the maximum allowable temperature in °C
Ta is the ambient temperature in °C
Tr is the reference temperature for material constants in °C
αo is the thermal coefficient of resistivity at 0 °C in 1/°C
αr is the thermal coefficient of resistivity at reference temperature Tr in 1/°C
ρr is the resistivity of the ground conductor at reference temperature Tr in μΩ-cm
Ko 1/αo or (1/αr) – Tr in °C
tc is the duration of current in s
TCAP is the thermal capacity per unit volume from Table 1, in J/(cm3·°C)
TCAP [cal/(cm3 · °C)] = specific heat (SH) [cal/(gram · °C)] x specific weight SW
(gram/cm3).
TCAP [J/(cm3 ·°C)] = 4.184 (J/cal) · SH [(cal/(gram · °C)] · SW (gram/cm3).
Material constants
IEEE Std 80-2000
• Akcmil = I ⋅ K f .(tc )1/2.
• Where
• Akcmil is the area of conductor in
kcmil
• I is the rms fault current in kA
• tc is the current duration in s
• Kf is the constant from Table 2 for
the material at various values of
• Tm(fusing temperature or limited
conductor temperature ) and using
ambient temperature (Ta) of 40°C.
Table-2
Asymmetrical currents
• Fault current consist of DC component in the beginning and this reduces with time. Because
of this DC component the peak value of current and RMS value changes. To take this into
account the term decrement factor (Df) is used.
• DC offset will result in mechanical forces and absorbed energy being almost four times the
value than for an equivalent symmetric current case.
• The effect of dc offsets can be neglected if the duration of the current is greater than or equal
to 1 s or the X/R ratio at the fault location is less than 5.
• IF =I f × Df
• IF representing the effective value of an asymmetrical current integrated over the entire fault
duration tf.
• Ta =DC offset time constant =L/R
• tf= Duration of fault in s
Typical values of Df
Ig = S f × I f
Zeq - is equivalent impedance of the ground wire and tower resistance per span.
Zs - is the self impedance of the transmission line ground conductor per span.
Rt - is the tower footing resistance.
Rg – station ground resistance.
Soil model
• Electrical conduction in soils is essentially electrolytic so its resistance
varies with temperature, moisture and salt composition. To determine the
actual soil resistivity, tests such as those described in IEEE Std 81-1983
should be performed at the site.
• Resistivity measurements
• The Wenner four-pin method
Sverak, J. G., “Simplified analysis of electrical gradients above a ground grid; Part I—How good is the present IEEE
method?” IEEE Transactions on Power Apparatus and Systems, vol. PAS-103, no. 1, pp. 7–25, Jan. 1984
Mesh voltage (Em)
• [for grids with no ground rods or few not located at the corner.]
• na =2 ⋅ LC/Lp.
• nb = 1 for square grids
• nc = 1 for square and rectangular grids
• nd = 1 for square, rectangular and L-shaped grids
A is the area of the grid in m2
Lx is the maximum length of the grid in the
x direction in m
Ly is the maximum length of the grid in the
y direction in m
Dm is the maximum distance between any
two points on the grid in m
Sverak, J. G., “Simplified analysis of electrical gradients above a ground grid; Part I—
How good is the present IEEE method?” IEEE Transactions on Power Apparatus and
Systems, vol. PAS-103, no. 1, pp. 7–25, Jan. 1984
Step procedure