Philippine Grid Code: What?
Philippine Grid Code: What?
• During Single Outage Contingencies (N-1), the RMS values of the voltages
shall not result in an Under-voltage or Overvoltage at any Connection
Point.
• The Transmission Network Provider shall consider the maximum estimated
Voltage Swell in the selection of the Voltage ratings of Grid Equipment.
Power Quality Standards
Power Factor
• Distribution Utilities and Large Customers shall maintain a Power
Factor at the Connection Point within the range 0.90 lagging and 0.95
leading.
• The Transmission Network Provider shall correct transmission and
substation bus Reactive Power Demand to a level that will
economically reduce the Technical Loss of the Grid.
Power Quality Standards
Harmonics (sinusoidal voltages and currents having frequencies
that are integral multiples of the fundamental Frequency)