Professional Documents
Culture Documents
Relay
Tawsif H. Chowdhury
Terminologies used in Protective Relaying
Pick Up:
A relay is said to be picked up when it moves from the OFF position to ON
position. Thus, when relay operates it is said that relay has picked up.
Pick up Value:
It is the minimum value of an actuating quantity at which relay starts
operating. In most of the relays actuating quantity is current in the relay coil
and pick up value of current is indicated along with the relay.
Terminologies used in Protective Relaying
Time Delay:
The time taken by relay to operate after it has sensed the fault is
called time delay of relay.
Relay Timing
An important characteristic of a relay is its time of operation. By ‘the
time of operation’ is meant length of the time from the instant when the
actuating element is energised to the instant when the relay contacts are
closed. Sometimes it is desirable and necessary to control the operating
time of a relay. For this purpose, mechanical accessories are used with
relays.
(i) Instantaneous relay:
• An instantaneous relay is one in which no intentional time delay is
provided. In this case, the relay contacts are closed immediately after
current in the relay coil exceeds the minimum calibrated value. The
instantaneous relays have operating time less than 0·1 second.
Relay timing
Current Setting:
Current setting is the setting of current(pick-up current) in a relay at which we want to
operate that relay.
The current setting of relay is expressed in percentage ratio of relay pick up current to
rated secondary current of CT.
• By the use of tapping on the relay coil the current setting values are obtained.
• The tap values are expressed in terms of percentage full load rating of CT with which relay is
associated.
• Tapping of a transformer means the connection point along the transformer winding to select the
suitable number of terms.
• By Tapping, you can get different turns ratio and be able to control output & voltage regulation.
.
For example,
suppose, we want that, an over current relay should operate when the system current
just crosses 150% of rated current.
Plug Setting Multiplier of Relay
• Plug setting multiplier of relay is referred as ratio of fault current in the relay to its pick up
current.
• Suppose we have connected on protection CT of ratio 200/1 A and current setting is 150%.
• Now, suppose fault current in the CT primary is 1000 A. Hence, fault current in the CT secondary
i.e. in the relay coil is, 1000 × 1/200 = 5A
and you have to calculate actual time of operation for PSM 10.
• From time / PSM graph of the relay as shown below, we can see
• That means, the moving parts of the relay take total 4 seconds
is 0.1 here, actually the moving parts of the relay have to travel
only 0.1 × 100% or 10% of the total travel distance, to close the
relay contacts.
• Hence, actual operating time of the relay is 4 × 0.1 = 0.4 sec. i.e.
10% of 4 sec.
Advantages:
1. Each circuit has two dedicated breakers.
2. Has flexibility in permitting feeder circuits to be connected to either
bus.
3. Any breaker can be taken out of service for maintenance.
4. High reliability.
• Disadvantages
1. Most expensive.
2. Would lose half of the circuits for breaker failure if circuits are not
connected to both buses.
Math