Fire Fighting Systems

By Mr. Suntixay MAHEUANGSY


Position: local operator
Fire Fighting Systems
CONTENT
1. Purpose of Fire Fighting Systems
2. Equipment Duty
3. Type Of fighting
1. Purpose Fire Fighting Systems

• A fire fighting system is probably the most impo


rtant of the building services, as its aim is to pro
tect human life and property when have fire for
helping to reduce damage large area and it will
create confident during working when it was ha
ppened fire and can extinguishing fire
2. Equipment Duty
Gate valve
Fire hose reel box

Fire hydrant Flashing strobe


light

Vertical indicator
post Exit sign circuit
Fire extinguisher,
For oil fire (Co2 Relief valve
fire extinguisher )

Fire extinguisher,
For general fire Sprinkler head
(Dry chemical fire (Pendent type )
extinguisher )

Discharge nozzle
(Pendent type) Sprinkler head
(Pendent type )
Sprinkler head
(Up-right type)

discharge lamp Smoke


and alarm speaker detector(DC 24V)

Manual switch Heat detector


Gas
Actuating set extinguishing
manual

CO2 Modular
FM-200 Modular

Alarm valve
Wet riser landing
valve

Fire gas
extinguishing Siren ,alarm bell
control panel
3. Type Of fire fighting

Fire fighting water system


The system start select switch on the main control panel must always be set p
osition for automatic start.
 Automatic Start: Water system will be automatically released into the prot
ected area, the pump is detected pressure in pipe when the pressure drop
with setting value it will work automatic
 Stopping after confirming extinction of a fire, the water mist system will be
stopped manually by cancelling the signal from the fire alarm system and
pressing the STOP button on the control panel or local point
  Electric Fire Pump (Jockey    Diesel Engine Fire Pump
pump)
Capacity pump: 11/h-100m 5.5 kw Capacity pump: 454/h -80m - 150 kw
Speed 2900 rpm Speed 2900 rpm
Efficiency:69% Efficiency:76%

Fire fighting system at XPXN Power House, there are 2 Diesel Engine Fire Pump
and 1 Electric Fire Pump to save the pressure in the pipe of Fire Fighting.
Breeching Inlet Relief Valve
The control panel
Control operate at decal pump
OPEN BY USE CABLE CONECT TWO POINT STOP AT MACHINE PULL TURNRIGHT
Linear heat detector
GAS FM200
Use in Control Room, LV Distribution Room, Battery Room, Switch gear Room, Diesel room.
When smoke or heat detector detect smoke or heat in room, It will send signal to FCP and
then FCP will send signal to actuating set after that actuating set will open valve at FM-200
modular, finally FM-200 will discharge to the room

Model : MFC - 150


Gross weight : 250.3 KG
Operating pressure of :25 BAR at 21ºC
Use temperature range of :0ºC ~54ºC
1.Push button Emergency Abort hold 3 s
2. Push button Reset
3.Push password 7654
4. Push button Enter 2 times
CO2 System

• CO2 Fire fighting system


 Actuating Cylinder Model: HQP4/6
Storage pressure :6 MPa
Max working pressure: 6.6 MPa
Operating temp range of : -20ºC ~ +50ºC

 Agent cylinder Model: EMP 70


Storage pressure :5,7 MPa
Max working pressure: 12.4 MPa
Operating temp range of : 0ºC ~ +50ºC
Procedure

Generator fire alarm

Temperature and smoke detector


generator electrical &
protection and generator Fire alarm signal, system
Fire alarm control panel
pit door is not opened fault out put
Gas extinguish control panel

Delay 30 seconds

Initial discharge (startup bottle action)

CO2 bottle end valve action( Initial discharge)


Fire extinguish agent
spraying displayed on Fire extinguish agent spraying
panel and DCS
Delay 60 seconds

Extended discharge startup bottle action

Fire extinguish agent spraying

Duration of delayed discharge 20 minute

Artificially confirm that the fire has been extinguished

Start up ventilation equipment for CO2 complete venting


Different fire pump and gas extinguish

fire pump
• It can in stall out door
• It have along time to used
• Price is cheaper

gas extinguish
• It can use with electric equipment
• In stall in door
• extinguish Quickly
• Relatively expensive
THANK YOU