Professional Documents
Culture Documents
Syllabus
TRANSFORMER
In core type transformers, the steel core
laminations are in the shape of 'L' , and
these laminations are placed one above
the other alternatively.
Laminations
In shell type transformers, the steel core
laminations are in the shape of 'E and I'
and placed similar to that of core type.
Types of laminations
Windings
Transformer windings are made of solid copper
or aluminium strip conductors.
The coils used are wound on the limbs and are
insulated from each other.
It carries the current and produces the flux
necessary for the functioning of the transformer.
Core type
Controls leakage
Sectional view of transformer
d d
V2 N 2 . V1 N1 .
dt dt
Dividing the above equations we get,
V2 N2
.
V1 N1
Assuming that there is no power loss,
V2 I 2 V1 I1.
V2 I1 N 2
10/07/21
K. K - transformation ratio
V1 I 2 N1
EMF Equation of a transformer
Let N1= No. of primary turns
Now,
llly,
E2 = 4.44fN2Фm ……(6)
EMF equation of transformer - contd
If ip is sinusoidal, the flux produced also sinusoidal, i.e
= m sin 2ft ……(7)
d m sin 2ft
therefore v1 N1
dt
v1 = N12fmcos 2ft = N12fmsin (2ft + /2) ……(8)
Queries????????
Power Transmission (CONTENT BEYOND
SYLLABUS)
10/07/21
Transformer – On load condition
Transformer on load assuming no
voltage drop in the winding
10/07/21
Phasor diagram of transformer with
lagging p.f load
10/07/21
Phasor diagram of transformer with
leading p.f load
10/07/21
Equivalent circuit of a
transformer
No load equivalent circuit:
10/07/21
Equivalent circuit parameters referred to
primary and secondary sides respectively
10/07/21
Contd.,
• The effect of circuit parameters shouldn’t be changed while
transferring the parameters from one side to another side
• It can be proved that a resistance of R2 in sec. is equivalent
to R2/k2 will be denoted as R2’(ie. Equivalent sec. resistance
w.r.t primary) which would have caused the same loss as
R2 in secondary,
I 12 R2' I 22 R2
2
I2
R
'
2
R2
I1
R2
2
k
Transferring secondary parameters
to primary side
10/07/21
Equivalent circuit referred to
secondary side
•Transferring primary side parameters to secondary side
10/07/21
equivalent circuit w.r.t primary
where
10/07/21
Approximate equivalent circuit
• Since the noload current is 1% of the full load
current, the nolad circuit can be neglected
10/07/21
Transformer Tests
•The performance of a transformer can be calculated on the basis of
equivalent circuit
•The four main parameters of equivalent circuit are:
- R01 as referred to primary (or secondary R02)
- the equivalent leakage reactance X01 as referred to primary
(or secondary X02)
- Magnetising susceptance B0 ( or reactance X0)
- core loss conductance G0 (or resistance R0)
•The above constants can be easily determined by two tests
- Oper circuit test (O.C test / No load test)
- Short circuit test (S.C test/Impedance test)
•These tests are economical and convenient
- these tests furnish the result without actually loading the
transformer
10/07/21
Open-circuit Test
In Open Circuit Test the transformer’s secondary winding is open-circuited, and
its primary winding is connected to a full-rated line voltage.
V0
Core loss Woc V0 I 0 cos 0 R0
Iw
Woc
cos 0 V0
V0 I 0 X0
I
I c or I w I 0 cos 0
I
G0 w
• Usually conducted on I m or I I 0 sin 0 I 02 -I w2 V0
H.V side I0 I
I 0 V0 Y0 ; Yo B0
• To find V0 V0
(i) No load loss or core Woc
Woc V02 G 0 ; Exciting conductance G 0
loss V02
(ii) No load current Io & Exciting susceptance B0 Y02 G02
which is helpful in
finding Go(or Ro ) and Bo
10/07/21
(or Xo )
Short-circuit Test
In Short Circuit Test the secondary terminals are short circuited, and the
primary terminals are connected to a fairly low-voltage source
The input voltage is adjusted until the current in the short circuited
windings is equal to its rated value. The input voltage, current and power is
measured.
10/07/21
Transformer Voltage Regulation and
Efficiency
The output voltage of a transformer varies with the load even if the input
voltage remains constant. This is because a real transformer has series
impedance within it. Full load Voltage Regulation is a quantity that compares
the output voltage at no load with the output voltage at full load, defined by
this equation:
Vs
At noload k
Vp
V S ,nlVS , fl VP / k VS , fl
Regulation up 100% Regulation up x 100%
VS , fl VS , fl
V S ,nlVS , fl VP / k VS , fl
Regulation down 100% Regulation down x 100%
VS ,nl
VS ,nl
10/07/21
Voltage regulation of Transformer
no - load voltage full - load voltage
Voltage regulation
no - load voltage
Vs N s
recall
Vp N p
N
Secondary voltage on no-load V2 V1 2
N1
V2 is a secondary terminal voltage on full load
Substitute we have N2
V1 V2
N1
Voltage regulation
N2
V1
N1
10/07/21
Transformer Phasor Diagram
To determine the voltage regulation of a transformer, it is necessary
understand the voltage drops within it.
10/07/21
56
Transformer Phasor Diagram
Ignoring the excitation of the branch (since the current flow through the
branch is considered to be small), more consideration is given to the series
impedances (Req +jXeq).
Voltage Regulation depends on magnitude of the series impedance and the
phase angle of the current flowing through the transformer.
Phasor diagrams will determine the effects of these factors on the voltage
regulation. A phasor diagram consist of current and voltage vectors.
Assume that the reference phasor is the secondary voltage, VS. Therefore
the reference phasor will have 0 degrees in terms of angle.
Based upon the equivalent circuit, apply Kirchoff Voltage Law,
VP
VS Req I S jX eq I S
k
10/07/21
57
Transformer Phasor Diagram
For lagging loads, VP / a > VS so the voltage regulation with lagging loads is > 0.
10/07/21
58
Transformer Phasor Diagram
For lagging loads, the vertical components of Req and Xeq will partially
cancel each other. Due to that, the angle of VP/a will be very small, hence
we can assume that VP/k is horizontal. Therefore the approximation will
be as follows:
10/07/21
Transformer Phasor Diagram
With a leading power factor, VS is higher than the referred VP so VR < 0
10/07/21
60
Voltage regulation
Lagging P.F. VP/ k > VS V.R. > 0
10/07/21
Voltage regulation for Lagging Power Factor
Voltage Regulation for Leading Power
Factor
Formula: voltage regulation
In terms of secondary values
0 V2 V2 I 2 R02 cos 2 I 2 X 02 sin 2
% regulation
0 V2 0 V2
V1 V1
where ' ' for lagging and '-' for leading
10/07/21
Transformer Efficiency
Transformer efficiency is defined as (applies to motors, generators and
transformers):
Pout
100%
Pin
Pout
100%
Pout Ploss
Types of losses incurred in a transformer:
Copper I2R losses
Hysteresis losses
Eddy current losses
Therefore, for a transformer, efficiency may be calculated using the following:
VS I S cos
x100%
PCu Pcore VS I S cos
10/07/21
Losses in a transformer
Core or Iron loss:
Copper loss:
10/07/21
Condition for maximum
efficiency
10/07/21
Contd.,
10/07/21
AUTO TRANSFORMER
At some occasions it is desirable to change voltage
level only by a small amount
i.e. may need to increase voltage from 110 to 120 V
or from 13.2 to 13.8 kV
This may be due to small increase in voltage drop
that occur in a power system with long lines
In such cases it is very expensive to hire a two full
winding transformer, however a special transformer
called: ”auto-transformer” can be used
AUTO TRANSFORMER
• A step-down auto-transformer :
• IH=ISE
• IL=ISE+IC
AUTO TRANSFORMER
• In step-up autotransformer:
VC / VSE = NC / NSE (1)
NC IC = NSE ISE (2)
voltages in coils are related to terminal voltages as
follows:
VL=VC (3)
VH=VC+VSE (4)
current in coils are related to terminal currents:
IL=IC+ISE (5)
IH=ISE (6)
AUTO TRANSFORMER
• Voltage & Current Relations in Autotransformer
• VH=VC+VSE
• since VC/VSE=NC/NSE VH=VC+ NSE/NC . VC
• Noting that: VL=VC
VH=VL+ NSE/NC . VL= (NSE+NC)/NC . VL
• VL / VH = NC / (NSE+NC) (7)
• Current relations:
• IL=IC+ISE employing Eq.(2) IC=(NSE / NC)ISE
• IL= (NSE / NC)ISE + ISE, since ISE=IH
IL= (NSE / NC)IH +IH = (NSE + NC)/NC . IH
IL / IH = (NSE + NC)/NC (8)
AUTO TRANSFORMER
Apparent Power Rating Advantage of Autotransformer
Note : not all power transferring from primary to
secondary in autotransformer pass through windings
Therefore if a conventional transformer be reconnected as
an autotransformer, it can handle much more power than
its original rating
The input apparent power to the step-up autotransformer
is : Sin=VLIL
And the output apparent power is:
Sout=VH IH
AUTO TRANSFORMER
And :
Sin=Sout=SIO
Apparent power of transformer windings:
SW= VCIC=VSE ISE
This apparent power can be reformulated:
SW= VCIC=VL(IL-IH) =VLIL-VLIH
employing Eq.(8) SW= VLIL-VLIL NC/(NSE+NC)
=VLIL [(NSE+NC)-NC] /(NSE+NC)=SIO NSE /(NSE+NC)
SIO / SW = (NSE+NC) / NSE (9)
AUTO TRANSFORMER
Internal Impedance of an Autotransformer
Another disadvantage: effective per unit
impedance of an autotransformer w.r.t. the related
conventional transformer is the reciprocal of power
advantage
This is a disadvantage where the series impedance
is required to limit current flows during power
system faults (S.C.)
Example of Variable Auto-Transformer
All day efficiency
output in kWh
all day ( for 24 hours)
Input in kWh
•All day efficiency is always less than the commercial efficiency
10/07/21
Transformer Voltage Regulation and
Efficiency - Tutorial
(a) Find the equivalent circuit referred to H.V. side
(b) Find the equivalent circuit referred to L. V. side
(c) Calculate the full-load voltage regulation at 0.8 lagging PF, 1.0 PF,
and at 0.8 leading PF
(d) Find the efficiency at full load with PF 0.8 lagging
SOLUTION:
Open circuit impedance angle is:
POC 50
OC cos 1
cos 1
84
VOC I OC 2300 0.21
Excitation admittance is:
I OC 0.21
YE 84 84 9.13 10 5 84
VOC 2300
0.0000095 j 0.0000908
Transformer Voltage Regulation and
Efficiency
• Impedance of excitation branch referred to primary:
1
RC 105k
0.0000095
1
XM 11k
0.0000908
• Short Circuit Impedance angle:
PSC 160
SC cos 1 cos 1 55.4
VSC I SC 47 6