OUTDOOR
EQUIPMENTS
OR
COUPLING DEVICES
OUTDOOR EQUIPMENTS
•Coupling Capacitor
•Wave Trap
•LMU( Line Matching Unit)
•Drainage Coil
•Lightning Arrestor
•Earthing Switch
OUTDOOR EQUIPMENTS
0.5 mH
Coupling
2200 Pf
Capacitor •Coupling capacitor offers low
To Power Equipment impedance for HF signal & very high
impedance for Power frequency
•The capacitance depends upon the
LMU Line Voltage
P
L
•CVT can perform the function of CC
C
C
COUPLING
CAPACITOR
CVT
OUTDOOR EQUIPMENTS
0.5 mH
Coupling
2200 Pf
Capacitor •Line Matching Unit is basically a
To Power Equipment Matching transformer
•Matching transformer is designed for
maximum power transfer of carrier
LMU signal to the EHT line
P
L
•It also gives Electrical Isolation from
C
C
the EHT circuit
C0-axial cable
EHT line
CC
LMU
Matching Transformer
PLCC
Eqpt.
Tuning Device
Earth
LMU
OUTDOOR EQUIPMENTS
0.5 mH
Coupling
2200 Pf
Capacitor •Drainage Coil provides path for
To Power Equipment <100mA leakage Power frequency current.
•DC offers high impedance for Carrier
signal
DC
LMU
50mH
•It also provides second earthing for
P
L CC.
C •DC along with MT guarantee a
C
continuity of earth connection
OUTDOOR EQUIPMENTS
0.5 mH
Coupling
2200 Pf
Capacitor •Lightning Arrestor protects the PLCC
To Power Equipment <100mA equipment from power system
abnormalities.
•It limits voltage surges coming from
LMU LA power line at the terminals of the
P DC
L coupling device.
C
C
•1kV LA is usually used
OUTDOOR EQUIPMENTS
0.5 mH
Coupling
2200 Pf
Capacitor •Earthing Switch is used for safely
To Power Equipment <100mA working in the LMU and accessories
during maintenance.
LMU LA
P DC
L E/S
C
C
OUTDOOR EQUIPMENTS
STATION A STATION B
1. Phase to Ground
2. Phase to Phase
3. Inter Circuit Coupling
PHASE TO GROUND
S T S T
A A
T I T I
O O
NA N B
S T S T
A A
T I T I
O O
NA N B
Balancing Transformer
LMU
B PHESE
EARTH PLCC
LMU
Next phase
EARTH
INTERCIRCUIT COUPLING
S T S T
A A
T I T I
O O
NA N B
TESTS
1. Construction Check
2. Insulation Resistance Measurement
3. Power frequency withstand voltage test
4. Capacitance and tangent of loss angle measurement
Construction Check
Dimensions
Accessories
Finishing
Name plates
Terminal marking etc. with approved drawings
Insulation Resistance Measurements
Specified limits
Capacitance - + 5%
Tan Delta – Not more than 0.5%
Standard capacitance
220kV- 2200pf
110kV-4400pf
66kV -8800pf
LMU
TESTS
Routine tests
1. Construction Check
2. Power frequency Voltage test
3. Composite loss
4. Return loss
5. Impulse voltage test (type)
Construction Check
Construction
Appearance
Dimensions
Name plates
Terminal marking etc. with approved drawings
Power frequency withstand test
Definition:
It is the loss caused by the coupling device and associated coupling
capacitors (assumed as no loss) terminated by nominal line side and
equipment side impedance.
The Nominal Line side Impedances
75ohms Unbalanced or
150ohms balanced
Any other value shall be specified by the purchaser
Composite Loss measuring Circuit
Z2
Level LMU
osc
Z1
Vo EQPT SIDE LINE SIDE V
LMDU c
Z2
Level LMU
osc
Z1
Vo EQPT SIDE LINE SIDE V
LMDU c
Definition
It is the reflection of signal power resulting from the insertion of a
device in a transmission line. It is usually expressed as a ratio in dB
relative to the transmitted signal power.
BASIC TEST CIRCUIT
SIGNAL GENERATOR
SPLITTING TRANS
Vo
C
LMU
LMDU Z2
Z1 J HV LV
E
V
C- Capacitance of CC
V, Vo- High impedance Voltmeters
J- Interrupter
Return loss Measurement
SIGNAL GENERATOR
SPLITTING TRANS
Vo
C
Z1 HV Z2
J LV
V
E
MEASURING
HV
Z1 FIELD
E LMU LV Z2
LMDU
C
OSC
C- Capacitance of CC
Z1- Nominal Line side impedance (600 ohms)
Z2- Nominal equipment side impedance (75ohms)
SLM reading directly gives the return loss
It should be greater than 12dB
Measurement shall be carried out for several frequencies in the available bandwidth
THIS IS IN ACCORDANCE WITH CLAUSE 12.2 IEC 481(1974)
Impulse Voltage Test
Impedance between primary and earth shall not be greater than 20ohms
Current carrying capacity:
Continuous- 1A r m s
Short time – 50A for 0.2 Sec
Power rating- 650W approx
Inductance of DC-50mH
LA Rating
Composite loss
Return loss
Power frequency with stand
TESTING OF WAVE TRAPS
Construction
Appearance
Dimensions
Name plates
Terminal marking etc. with approved drawings
Tapping & Rated tapping loss
Definition
Z1
S1
WT
SLM
LEV Z1
OSC
2
1 3
L
Z1
S1
WT
SLM
LEV Z1
OSC
2
1 3
L
THE RATED TAPPING LOSS IS THE LOSS WITH THE PURE RESISIVE
COMPONNENT ONLY WHICH IS DETERMINED BY ADDING
CAPACITOR & INDUCTOR
TAPPING LOSS/RATED TAPPING LOSS SHOULD NOT EXCEED 2.6 dB
BLOCKING IMPEDANCE
BLOCKING IMPEDANCE IS
Z1/{ANTILOG(RTL/20)-1}/2