Professional Documents
Culture Documents
According to insulation
Vulcanised Indian rubber[VIR]
The drawing are prepared with details for execution of work and
All installation shall comply with the provisions of the Indian Electricity
rules 1956
The successful tender shall be responsible for obtaining the approval of the
Distribution boards
Wiring cables
Earthling materials
Installation
Point wiring
The point wiring shall start from distribution /sub
Accessibility &Intial cost
In a selected wiring system there should be facilities for
maintenance cost
The other factors in addition to above to be kept in view
under plaster and VIR (or) PVC cables are drawn after wards by means of a GI wire opf size of about 18 SWG in damp situation the
conditics can be spaced from the walls by means of small wander blocks fixed below the pipe at regular intervals the conduits should be
electrically and mechanically continuous and connected to earth at some suitable points
The conduit used for this purpose of two types (i) light gauge (ii) heavy gauge (screwed type) conduit light gauge is not permitted the In
this system of wiring steel tubes known are conduits as installed on the surface of walls by means of saddles or pipe hooks (or) barried
under plaster and VIR (or) PVC cables are drawn after wards by means of a GI wire opf size of about 18 SWG in damp situation the
conditics can be spaced from the walls by means of small wander blocks fixed below the pipe at regular intervals the conduits should be
electrically and mechanically continuous and connected to earth at some suitable points
Countinue…
The conduit used for this purpose of two types (i) light gauge (ii) heavy gauge (screwed type) conduit light gauge is not permitted the In this
system of wiring steel tubes known are conduits as installed on the surface of walls by means of saddles or pipe hooks (or) barried under plaster
and VIR (or) PVC cables are drawn after wards by means of a GI wire opf size of about 18 SWG in damp situation the conditics can be spaced
from the walls by means of small wander blocks fixed below the pipe at regular intervals the conduits should be electrically and mechanically
continuous and connected to earth at some suitable points. the conduit used for this purpose of two types (i) light gauge (ii) heavy gauge
medium voltage ( voltage higher than 250v ) screwed conduit is used for all medium voltage (250 to 600v) circuits and in places where good
mechanical protection and absolute protection from moisture in general the finish of being a smooth coat of enamel both on the inside and
outside surface of the tube galvanidhed conduit is also employed conduit size is started in termes of its outer diameter the smallest size is 12mm
and the next size 19mm, 31mm and 50mm . the largest standard size is 63mm . PVC conduit pipes are also available now and or increasingly
being employed in place of steel conduits PVC conduits are cheaper in cost and the labour time saved maybe as much as25% compare tothe time
taken in installing steel conduit such conduit are resistant to acid , alkasis , oil moisture the main draw back of PVC conduit is its movement due
to variation in temperature so PVC is not suitable for using in location to fire lazard
Internal wiring
1, looping system
2,tree system
Advantages of conduit wiring system
It provides protection against mechanical damage
circuit etc
Replacement and attention of defective wiring is easy
The energy shall not be supplied, transformed, converted or used or continued to be supplied, transformed, converted
I. The following controls of requisite capacity to carry and break the current after the point of commencement of
supply
a linked switch with fuse(s) or a circuit breaker by low and medium voltage consumers.
a linked switch with fuse(s) or a circuit breaker by HV consumers having aggregate installed
transformer/apparatus capacity up to 1000 KVA to be supplied at voltage upto 11KV and 2500 KVA at higher
a circuit breaker by HV consumers having an aggregate installed transformer/apparatus capacity above 1000 KVA
and supplied at 11 KV and above 2500 KVA supplied at higher voltages (above 11 KV and not exceeding 33KV)
Provided that the linked switch on the primary side of the transformer may be of such capacity as to
carry the full load current and to break only the magnetising current of the transformer.
(A) having a capacity 5000 KVA and above and installed before the commencement of the Indian
(B) having a capacity of 1000 KVA and above and installed before the commencement of the Indian
Electricity (Amendment – 1) Rules, 2000; a circuit breaker shall be provided.] Provided further that the
provision of linked switch on the primary side of the transformer shall not apply to the unit auxiliary
A supplier may affix one or more seals to any cut-out and to any meter,
The consumer shall use all reasonable means in his power to ensure that no such
The word ‘supplier’ shall for the purpose of this rule include a State Government
when any meter, maximum demand indicator or other apparatus is placed upon a
consumer’ s premises by such Government.
57.Meters, maximum demand indicators
and other apparatus on consumer’s
premises
(1)Any meter or maximum demand indicator or other apparatus placed upon a consumer’ s premises in
accordance with section 26 shall be of appropriate capacity and shall be deemed to be correct if its limits of
error are within the limits specified in the relevant Indian Standard Specification and where no such
specification exist, the limits of error do not exceed 3 per cent above or below absolute accuracy at all loads in
(2)No meter shall register at no load.
(3) Every supplier shall provide and maintain in proper condition such suitable apparatus as may be
prescribed or approved by the Inspector for the examination, testing and regulation of meters used or intended
to be used in connection with the supply of energy. Provided that the supplier may with the approval of the
Inspector and shall, if required by the Inspector, enter into a joint arrangement with any other supplier for the
purpose aforesaid.
(4)Every supplier shall examine, test and regulate all meters, maximum demand
indicators and other apparatus for ascertaining the amount of energy supplied before
their first installation at the consumer’ s premises and at such other intervals as may be
(5) Every supplier shall maintain a register of meters showing the date of the last test,
the error recorded at the time of the test, the limit of accuracy after adjustment and
final test, the date of installation, withdrawal, reinstallation, etc., for the examination
in cases where the voltage normally exceeds 125 volts and of systems at medium voltage
2(a) Neutral conductor of a 3 phase, 4 wire system and the middle conductor of a 2 phase, 3-
wire system shall be earthed by not less than two separate and distinct connections with a
minimum of two different earth electrodes or such large number as may be necessary to bring
the earth resistance to a satisfactory value both at the generating station and at the sub-station.
The earth electrodes so provided, may be inter-connected to reduce earth resistance. It may also
be earthed at one or more points along the distribution system or service line in addition to any
connection with earth which may be at the consumer’ s premises.
(b) In the case of a system comprising electric supply lines having concentric cables, the
external conductor of such cables shall be earthed by two separate and distinct connections
with earth.
(c) The connection with earth may include a link by means of which the connection may be
generating station only, and the current from the middle conductor to earth shall be
continuously recorded by means of a recording ammeter, and if any time the current exceeds
one-thousandth part of the maximum supply current immediate steps shall be taken to improve
the insulation of the system.
(ii) Where the middle conductor is earthed by means of a circuit-breaker with a resistance
connected in parallel, the resistance shall not exceed 10 Ohms and on the opening of the
circuit-breaker, immediate steps shall be taken to improve the insulation of the system, and the
circuit-breaker shall be reclosed as soon as possible.
(iii) The resistance shall be used only as a protection for the ammeter in case of earths on the
system and until such earths are removed. Immediate steps shall be taken to locate and remove
the earth.
(e) In the case of an alternating current system, there shall not be inserted in the connection
with earth any impedance (other than that required solely for the operation of switch-gear or
instruments), cut-out or circuit-breaker, and the result of any test made to ascertain whether the
current (if any) passing through the connection with earth is normal, shall be duly recorded by
the supplier.
(f) No person shall make connection with earth by the aid of, nor shall he keep it in contact
with, any water main not belonging to him except with the consent of the owner thereof and of
the Inspector.
(g) Alternating current systems which are connected with earth as aforesaid may be electrically
interconnected: Provided that each connection with earth is bonded to the metal sheathing and
metallic armouring (if any) of the electric supply lines concerned.
(2) The frame of every generator, stationary motor,
portable motor, and the metallic parts(not intended as
conductors) of all transformers and any other
apparatus used for regulating or controlling energy
and all medium voltage energy consuming apparatus
shall be earthed by the owner by two separate and
distinct connections with earth.
Looping in system
Fig shows a simple looping in method which is commonly used
the phase [or] live conductors are looped in switch board and
neutrals are looped either in switch borad or from light or fan .
It will be seen that the live terminal of the loads [lamps and fan]
are connected through switch and neutral for next load is looped
in previous lamp/fan point .
In this system no point are made in the run of wire or cable
Looping out with a junction box
Advantages&Disadvantages of looping
system
Advantages:
Junction boxes are not required
Fault location is easy
Disadvantages:
Length of cable required is more
Tree system
In this system from the main switch rising mains are run to every floor rising
mains are of copper or aluminium strips which group from the main switch to all
floors .
the rising mains are usually provided in the centre of the load for the purpose of
economy .at each floor rising mains are connected to economy boards to sub
board .
sub circuits are taken from the sub boards the sub circuits are used for wiring the
portion of the load in accordance with the method explained in articles 3 and4
Ring system
In this systems a pair of conductors are run through all the rooms .
The ring circuit is brought back to the main board with this system wiring is
required to be done suitable fuse wire is each plug and exiting roses if the both
ends of the conductors are ending are ending on the same main sub load
There may be saving of copper because the current can be fed both sides but
capacity the both ends of the ring circuits terminate in a seprate switch
Lamp circuits
The lamp circuits used for house wiring are quite simple and they are generally controlled from one point
But in staircase wiring it is necessary to control the lamp circuit from two points at the top and bottom of the
staircase
simalary in halls or corridors or bedrooms it may be necessary to control the lamp from more than two points
1, simple circuit
4. pilot circuit
5. miscellous circuits
Simple circuits (bedroom and staircase
lighting)
In bedroom a light is required at the dressing table which
The blades of the double pole switch are made of the two links