Professional Documents
Culture Documents
Lecture 8
Symmetrical Components
Prepared By
Kazi Firoz Ahmed
Sr. Assistant Professor, Dept. of EEE
American International University-Bangladesh (AIUB)
Email: k.firoz@aiub.edu
Sequence Impedance and Sequence Network
a
Ia
Zn The generator voltage (E a , Eb ,
+
Ea
- Ec ) are of positive sequence only,
I - - since the generator is designed
Eb
n
c b to supply balanced three-phase
+ Ec +
Ib voltage.
Ic
Sequence Networks of Unloaded Generators
a Reference -
Z1 -
+ Ia1 Ea
- E +
V a1 Ea Ia 1 Z1
a
Eb
V a1
- Z1
c + b
Z+ -
E
Z1
c
+
1
Ib a
1 I a1
Ia Positive-sequence
network
a Reference
-
Z2 Ia 2
Z
Va 2 Ia 2Z 2
Z2 Ib
2
Va 2
c Z2 2
+
b I
c a
2 Ia2
Negative-sequence
network
Sequence Networks of Unloaded Generators
Reference
a Ic1
-
Zn 3Zn I a 0 Z 0
Ia 0 V a 0
Z g0
Z0 V a0
I a 0 (Z g 0 3Z n )
a0
Z Ia 0 Zg0
3I
c
g0 3I a I n
Z g0 b +
Ia 0 a 0
Ia 0
Zero-sequence
network
Example 11.6. A salient-pole generator without dampers is rated 20 MVA, 13.8kV and has a
direct=axis subtransient reactance of 0.25 per unit. The negative-and-zero-sequence reactance are,
respectively, 0.35 and 0.10 per unit. The neutral of the generator is solidly grounded. With the
generator operating unloaded at rated voltage with E a n 1.00 per unit , a single line-to-
0
ground fault occurs at the machine terminals, which then have per-
unit
V avoltages V
0 to ground, 1.013 1 0 2 .25 0 V 1.013
102 .25 0
b
Determine the subtransient current in the generator and the line-t0-linec voltages for subtransient
conditions due to the fault. a
Ia
Zn Ia In
+
E an Figure 11.15
- n
- E bn
c + E cn + b
-
Ib 0
Ic 0
Sequence Networks of Unloaded Generators
E
an (1.0 j0) ( 0 . 6 4 3 j0) j1.43per unit
I (1 ) a
(1)
V a
Z1 j 0.2 5
(0)
(1)
I a I ( 2)
a 3I (0)
a j4.29
The base current is 20,000 ( 3 1 3 . 8 ) 837 A and so the subtransient current in line a is
13.8
Vab 1.01 3 77.7 0 8.0577.7 0
kV
13.8
Vbc 1.980 3 270 0 15.78270 0
kV
13.8
Vc a 1.01 3 102 .30 8.05102 .30
kV
Sequence Networks of Unloaded Generators
Before the fault the line voltages were balanced and equal to 13.8kV. For comparison with the line
voltages after the fault occurs, the prefault voltages, with Van Ean as reference, are given as
M1
T1 T p
k l m n
r
M 2
Example of Positive and Negative-Sequence Network
j 0 .0 8 5 7 j 0 .0 8 1 5 j 0 .0 9 1 5
k l m n
j 0 .0 2 p r
j 0 .2 7 4 5 j0.5490 (Positive)
+
+ +
Eg
E
- E - m 2
- m1
Reference bus
j 0 .5 4 9 0
(Negative)
j 0 .0 2 j 0 .2 7 4 5
p q
m n
k l
j 0 .0 8 5 7 j 0 .0 8 1 5 j 0 .0 9 1 5
Zero sequence Network
1 . Zero-sequence network currents will flow only if a return path exists.
2 . The reference bus of the zero-sequence network is the ground.
Z Z Z Z
N N
Z Z
Reference R
N N
Z
Zero sequence Network
R
Z Z
I n 3I a 0
N 3Z n
Nn Z
Z
N
Ia 0
R
Z Z
Z Z
Zero sequence Network
Zn R T
3Zn
Q S
Z g0
M N
P R
T
(Zero-Sequence)
Zero sequence Network
Q S M
P N
Z g1 R T
+ Z g2
+
E g1 -
- E g1
(Positive-Sequence)
M
R T
N
P
Q S
(Negative-Sequence)
Zero sequence Network
Example 11.9. Draw the zero-sequence network for the system described in Example 6.1. Assume
zero-sequence network for the generator and motors of 0.05 per unit. A current-limiting reactor of
0.4 is in each of the each of the neutrals of the generator and the large motor. The zero-sequence
Generator: X 0 0.05 p er un i t
1 3.2 2
Motor 1: 0.05( 2 0 0 ) (1 3.8 ) 0 . 0 6 8 6 p e r u n i t
300
X 0
Motor 2: 1 3.2 2
0.05(1 0 0 ) (1 3.8 ) 0 . 1 3 7 2 p e r u ni t
300
X0
(20) 2
Base Z 1.333
300
(13.8) 2
Base Z 0.635
300
Zero sequence Network
0.4
3 Z n 3(1.3 3 3 ) 0 .9 0 0 p e r unit
0 .4
3 Z n 3( ) 1 .8 9 0 p e r unit
0 .6 3 5
1.5 6 4
Z 0 1 7 6.3 0 .5 4 45 p e r unit
End