Professional Documents
Culture Documents
10.1 The one-line diagram for a power system is given in the following figure.
The parameters of the generators and transformers are given as:
G1 and G2: 100MVA, 20kV, X 1 X 2 20%, X 0 6% and X N =5%.
Transformers T1 and T2: 100MVA, 20 / 345Y kV and X=10%
Line (on bases 100MVA, 345kV): X 1 X 2 10%, X 0 25% .
A bolted single line-to-ground fault occurs on phase a at bus 2. Vf=100 .
Transmission Line
jX N
Solution:
a) Sequence networks: Z(1) , (0)
th Z th j 0.3 / / j 0.4 j 0.1714 Z th j 0.35 / / j 0.1 j 0.0778
(2)
100 100
j 0.15
1
The Thevenin equivalent circuits as viewed from bus 2:
j 0.1714 I(1)
fa
j 0.1714 I(2)
fa
j 0.0778 I(0)
fa
Ifa I(1)
fa I fa I fa
(2) (0)
V2f(2)
100 100
Superposition
100 100
2
The positive sequence current flowing from T1 to fault bus 2:
j 0.1 j 0.1 j 0.2
a
I(1) 2.3776 900 =1.3586 900 pu
( j 0.1 j 0.1 j 0.2) ( j 0.1 j 0.2)
j 0.15
I(2)
a,G1 I (2)
a 130 0
1.3586( 90 0
30 0
) 1.3586 60 0
2.3532900 pu
3
10.2 A bolted double line-to-ground fault between phase b and c occurs at
bus 2 in the power system shown in question 10.1.
a) Calculate sequence currents at the fault points;
b) Calculate the phase-to-ground voltages at bus 3.
Solution:
a) For the bolted double line-to-ground fault at bus 2:
j 0.1714 I(1)
fa
j 0.1714 I(2)
fa
j 0.0778 I(0)
fa
Vf
fa
I(1) j4.4462
Z(1)
th Z (2)
th / /Z (0)
th
Z(0)
1
I (2)
fa Ifa (0) th (2) j1.3881
Zth Zth
Z(2)
1
I (0)
fa Ifa (0) th (2) j3.0581
Zth Zth
b) The voltage at bus 3:
The positive sequence current flowing from bus 2 to bus 3:
1 2 3 4
j 0.1 j 0.1 j 0.1
j 0.1 j 0.1 j 0.1
j 0.20 j 0.2 j 0.20
j 0.2 (1) I(1)
I fa
fa
+ +
10 0
100
- -
(a) Positive-sequence
j 0.1 j 0.2
a23
I(1) j 4.4462 =j1.9055pu
( j 0.1 j 0.1 j 0.2) ( j 0.1 j 0.2)
4
The negative sequence current flowing from bus 2 to bus 3:
j 0.1 j 0.1 j 0.1
j 0.2 j 0.20
I(2)
fa
j 0.1 j 0.2
a23
I(2) j1.3881= j 0.5949pu
( j 0.1 j 0.1 j 0.2) ( j 0.1 j 0.2)
j 0.15
j 0.1
a23
I(0) j 3.0581= j 0.6796pu
( j 0.25 j 0.1) j 0.1
5
10.3 A double line fault between phase b and c with the fault impedance
Xf=0.1pu occurs at bus 1 in the power system shown in question 10.1.
a) Calculate the phase currents through transmission line. (Students:
calculate phase currents from the sequence currents)
b) Calculate the phase-to-ground voltages at bus 3. (Students: calculate
phase voltages from the sequence voltages)
c) Calculate the phase-to-ground voltages at bus 4 considering phase
shift caused by Y-∆ transformer. (Students: partial calculation)
Solution:
Sequence networks:
1 j 0.1 2 3 4
j 0.1
j 0.1 j 0.1 j 0.1 j 0.1
j 0.20 j 0.2 j 0.20
j 0.2
+ +
100 100
- -
j 0.15
6
a) The phase current through transmission line:
1 2 3 4
j 0.1 j 0.1 j 0.1 j 0.1 j 0.1 j 0.1
j 0.2 j 0.20 j 0.2 j 0.20
I(1)
fa I(2)
fa
100 100
(b) Negative-sequence
(2) (2)
Ia23 Ia12 30 =0.741 120 pu=-0.3705-j0.6417pu
o o
a23 0
I(0)
a1g 0
I(0)
7
b) The phase voltages at bus 3
The sequence voltages at bus 3:
V3(1) =1.000 ( j 0.1 j 0.1) I(1)
a23 I a1g j 0.2 ? pu
(1)
(2) (2)
Ia4g Ia2330
o
a4g 0
I(0)