Isolated
110V
LIMS power up......
When the key switch and start key is set to
on.......
Ships
input To DC circuits
supply
To AC & DC LIMS
and TRACO PSU
Isolated
110V
RL1
contacts
make
RL1
energises
Ships
input To DC circuits
supply
Hold on
Isolated
110V
RL1
contacts
make
CON5
energises
CON5 contacts
make
Ships
input To DC circuits
supply
Isolated
110V
CON5 contacts
makes
When the AC remote switch is set to on.......
Ships
input To DC circuits
supply
To AC & DC LIMS
and TRACO PSU
AC remote
Isolated switch
110V
Con 2
energises
Energising RLZ to energise RL2.......
RLZ contacts
make
RLZ
energises
Ships
input To DC circuits
supply
To AC & DC LIMS
and TRACO PSU
RL2 contacts
make
RL2
energises
RL2
contacts
make
3 phase supply
for Sorenson for
DC
So far......
AC supplies initiated
LIMs initiated and stable
DC supply initiated awaiting DC master switch to be made to energise
contactor 1
When the DC remote switch is set to on.......
Ships
input To DC circuits
supply
DC remote
switch
Con 1
energises
Con 1 contacts
make
Con 4
energises
Con 4 contacts
open
Con 4 contacts
close
AC & DC monitoring.......
Ships
input To DC circuits
supply
AC monitoring
DC monitoring
If a DC fault causes the LIM to trip.......
Relay in LIM
operates
CON4 de-
energises
CON4 contacts
close
CON4 contacts
open
If a AC fault causes the AC & DC LIM’s to
trip.......
Relay in LIM
operates
CON5 de-
energises
Ships
input To DC circuits
supply
CON5 contacts
open
CON5 contacts
open
CON4 de-
energises
CON4 contacts
close
CON4 contacts
open
AC and DC current and voltage indication.......
Voltage
Current
sensing