Controls
Controls
Controlling equipment
w e
y z
x
Control loop
y w
Y PI x
Building Technologies
.......
Type of controls
PI Control
PID Control
PD Control
Building Technologies
.......
PI-controller
X1
X2
Y2
W
Y1
Building Technologies
.......
2-Position control
2P control
1
Output
0
Actual value
Set-point
Building Technologies
.......
3-Position control
Building Technologies
.......
0…10V control
Building Technologies
.......
Q/Q100
Application a-value
Preheater 0.3...0.5
Reheater 0.15..0.3..0.5
a<1
Cooling coil 0.4..0.8
Heat exchanger 0.5...1.0 1)
a=1 "Flow control" approx. 1.0
1) depending on the
construction
V/V100
Building Technologies
.......
Valve characteristic
Water at 5..30°C
Flow
Water gauge
pv100 = 1 bar
10 m
kv100
kvs in m3/h
ar
e e
lin tag
e n
e rc
a lp
q u
e
Stroke
H100
Building Technologies
.......
Pv =1
a =1 Pv =1
a =1
H/H100 H/H100
Building Technologies
.......
Model
Building Technologies
.......
Rangeablity Sv
0,2
0,1
kvo Linear
Equal percentage kvr
kvr
0,2 0,4 Stroke 0,1 Stroke
[H/H] [H/H100]
Motoric and electrohydraulic valves have an Curve shows no discontinuity (the gain comes
Sv = 50..150 fromzero when valve is opening)
The rangeability is defined as ration of the flow of the fully open valve to the minimal
controllable flow in the valve !
Building Technologies
.......
Degree of difficulty S
Tu : Time lag
Time Tg : Recovery time
Tu Tg
R S
Stroke jump e.g. 20%
t=0
Building Technologies
.......
Controlled system Tu Tg S 1) No 2)
District heating 20 40 secs 0.5 2 mins B1
Boiler return temperature control 0.5 2 mins 1 5 mins B4
Supply water (injection circuit) 10 20 secs 30 60 secs C1
Supply water (injection circuit with 10 20 secs 30 60 secs C11
through port valve)
Supply water (mixing circuit) 3) 10 20 secs 30 60 secs 0.2...0.4 C2
Supply air control 4) 10 40 secs 30 120 secs 0.15...0.5 D1
Supply air control with cascade 1 5 mins 10 30 mins D11
Extract air control 5) 1 5 mins 10 60 mins 0.1...0.3 D12
Radiator 6) 5 15 mins 1 2.5 hrs 0.05..0.2 D2
Floor heating 0.5 2 hrs 3 24 hrs D23
1) Details from Recknagel
2) According to application recommendation
3) From Recknagel : Supply water temperature
4) „ „ : Supply air temperature
5) „ „ : Extract air temperature
6) „ „ : Room temperature
Building Technologies
.......
50
40
30
Qmin out
25
20
15
10 B
8.7
8
• Valve authority Pv
• Rangeability Sv
5
4
3.1
B'
• a-value
3
Pv
1 1.0
0.80
0.60
0.50
A' A
0.40
0.30
Building Technologies
.......
y w
x
Tu
S
Tg
pv100[kPa]
Pv
pv 0 [kPa] qactual
a
q max
Building Technologies