Professional Documents
Culture Documents
2
TABLE OF CONTENTS
Overview of Firefighting
Single Line Diagram
Pumps & Pump Room
Sprinklers Systems
3
OVERVIEW OF FIREFIGHTING
1. Air ( Oxygen )
2. Fuel ( Flammable Material )
3. Heat ( sufficient heat to raise
the material to its ignition
temperature )
4
OVERVIEW OF FIREFIGHTING
5
OVERVIEW OF FIREFIGHTING
Fire Fighting
Systems
Manual Automatic
Manual Siamese
Cabinet Fire hydrant
extinguisher connection
Sprinklers
SYS
6
OVERVIEW OF FIREFIGHTING
7
SINGLE LINE DIAGRAM
Pump
Tank Siamese
Room
connection
Automatic
Sprinklers
systems
8
Pump
Room
9
PUMP ROOM
Delivered water from tank to firefighting
systems
Cabinet
Tank
Pump
Room
Sprinklers
10
PUMP ROOM
Centrifugal
Horizontal &
Vertical
Types of
Pumps
Horizontal &
Positive Vertical
displacement
11
PUMP ROOM
Horizontal Centrifugal Pump
Vertical centrifugal pump
12
Centrifugal pump
Impeller
Overhung between
bearing
13
CENTRIFUGAL PUMPS
Working mechanism of centrifugal pump
14
GENERATION OF CENTRIFUGAL FORCE
First
The liquid Step
enter :
the suction
nozzle and then into
Conversion eye of
Motor
impeller
Energy Into
Kinetic
When the Energy
impeller rotates it
spins the liquid sitting in the
cavities between the vanes
outward and provides centrifugal
acceleration
15
GENERATION OF CENTRIFUGAL FORCE
16
FORMULA :-
17
FACT
One fact that must always be
remembered: A pump does
not create pressure, it only
provides flow. Pressure is a
just an indication of the
amount of resistance to flow.
18
1-Rotating components comprised of an
impeller and the shaft
Impeller
direction of mechanical
suction type construction
flow
Radial
Mixed
Axial Double-
Single-
Closed
Open
flow suction
23
CENTRIFUGAL PUMP PARAMETERS
Capacity :-
D e fi n i t i o n : -
C a p a c i t y m e a n s t h e fl o w r a t e w i t h w h i c h l i q u i d
is moved or pushed by the pump to the desired
point in the process.
It is commonly measured in either gallons per
minute (gpm) or cubic meters per hour
(m3/hr). The capacity usually changes with the
changes in operation of the process.
1 - P ro c e s s l i q u i d ch a ra c te r i s t i c s i . e .
d e n s i t y, v i s c o s i t y
2 - S i ze o f th e p u m p a n d i t s i n l e t a n d
o u tl e t s e c t i o n s
3 - Im p e l l e r s i ze
4 - Im p e l l e r ro ta t i o n a l s p e e d R P M
5 - S i ze a n d s h a p e o f ca v i t i e s b e t we e n th e
va n e s
6 - P u m p s u c t i o n a n d d i s ch a rg e
te m p e ra t u re a n d p re s s u re c o n d i t i o n s
25
FORMULA :-
26
CENTRIFUGAL PUMP PARAMETERS (HEAD)
HEAD:-
S i g n i fi c a n c e o f u s i n g t h e “ h e a d ” t e r m
i n s t e a d o f t h e “ p r e s s u r e” t e r m
27
CENTRIFUGAL PUMP PARAMETERS (HEAD)
The same head term is used to measure the
k i n e t i c e n e r g y c r e a t e d b y t h e p u m p.
In other words, head is a measurement of the
height of a liquid column that the pump
could create from the kinetic energy imparted
to the liquid
28
CENTRIFUGAL PUMP PARAMETERS (HEAD)
The main reason for using head instead of
pressure to measure a centrifugal pump's
energy is that the pressure from a pump will
c h a n g e i f t h e s p e c i fi c g r a v i t y ( w e i g h t ) o f t h e
liquid changes, but the head will not change.
Since any given centrifugal pump can move a
l o t o f d i ff e r e n t fl u i d s , w i t h d i ff e r e n t s p e c i fi c
gravities, it is simpler to discuss the pump's
head and forget about the pressure.
29
FACT
A given pump with a given
impeller diameter and
speed will raise a liquid to a
certain height regardless of
the weight of the liquid.
30
FORMULA :-
32
DEFINITION :-
1-STATIC SUC TION HEAD, HS
33
DEFINITION :-
2-STATIC DISCHARGE HEAD, HD
34
DEFINITION :-
What is Static Head?
In a pumping system, this head represents
the energy required to raise the liquid from
the pump centerline to the point in the pipe
that the liquid needs to be raised
35
DEFINITION :-
3-FRICTION HEAD, HF
36
37
DEFINITION :-
38
DEFINITION :-
5-VELOCITY HEAD, HV
It i s th e e q u i va l e n t h e a d i n f e e t th ro u g h
wh i ch th e wa te r wo u l d h a ve to fa l l to
a c q u i re th e s a m e ve l o c i t y,
39
DEFINITION :-
6-PRESSURE HEAD HP
S uct i o n P re ss ure He a d e x i s t s
b e ca u s e th e s uct i o n ta n k i s u nd e r
a p ress u re o th er th a n a t m o s ph er i c.
It i s th e pre ss ure a c t i ng o n th e s ur fa ce
o f th e l i qui d i n th e s u ct i o n ta n k .
T h i s press ure ca n b e po s i t i ve ( a b ove
a t m o s ph e r i c) o r ne g a t i ve ( va c uu m ) .
40
DEFINITION :-
7-TOTAL SUCTION HEAD HS
T h i s i s c a l l e d To t a l S y s t e m S u c t i o n H e a d . T h i s i s
a l s o s o m e t i m e s c a l l e d To t a l D y n a m i c S u c t i o n
Head.
The equation to calculate this head requirement
.Suction static head is positive when there is a
fl o o d e d s u c t i o n a n d n e g a t i v e w h e n t h e r e i s a
suction lift.
Pressure head is zero if the tank is atmospheric.
It is added when above zero gauge pressure and
subtracted when under vacuum.
Ve l o c i t y h e a d t h e o r e t i c a l l y i s p a r t o f t h e S y s t e m
Suction Head equation. In practical application,
it is rarely considered as its value is minimal
41
DEFINITION
8-TOTAL DISCHARGE HEAD HD
42
DEFINITION :-
9-TOTAL DIFFERENTIAL HEAD HT
TOTAL HEAD SYSTEM
TOTAL DYNAMIC HEAD
HT=HD-HS
43
PUMP PERFORMANCE CURVE
Total dynamic Head
Increasing capacity
decreasing Head
Capacity 44
10-NET POSITIVE SUCTION HEAD REQUIRED (NPSHR)
46
DEFINITION
Efficiency
47
DEFINITION Best Efficiency point
48
DEFINITION
Power Requirements
49
50
PUMP SELECTION
pss.jnlp
51
PUMP OPERATIONS
Pumps operates by : -
Electric Engines
Diesel Engines
52
PUMP ROOM CONTENTS
Pump Room
54
PUMP ROOM SPECIFICATIONS
Any pump can be used to be Firefighting pumps as
long as matching :-
1. NFPA (National Fire Protection Association)
2.LPC (Loss Prevention Council )
Manufacturing of pumps should be according to
1. American specs ANSI (American National Standards
Institute )
2. British specs BS (British Standard )
3. Germany specs DIN (Diameter Nominal )
55
PUMP ROOM SPECIFICATIONS
It should delivered with pumps test
certification from manufacturer states about
testing the pumps with its control panels
56
NFPA (NATIONAL FIRE PROTECTION ASSOCIATION )
58
NFPA 20
The pump is required to demonstrate its
ability to achieve 65% of rated pressure when
flowing at 150% of rated capacity
59
60
NFPA20
Gallon per minute according to NFPA20
61
INSTALLATION OF PUMP
62
INSTALLATION OF PUMP ROOM
63
INSTALLATION OF PUMP ROOM
Suction Line
Discharge Line
Check Line
64
INSTALLATION OF PUMP ROOM
65
66
67
INSTALLATION OF PUMP ROOM
pump room.dwg
Pump Room 2.dwg
AutoCAD Drawings
Pump Room (Electric ).dwg
pump Room (Diesel ).dwg
Pump Room 3d.dwg
68
GALLERY
Gallery
69
Concentric reducer
70
Check Valve
71
Diesel pump fuel tank
72
Air Vent on discharge line
73
Concentric & eccentric reducers
74
Sprinklers
Systems
75
There are 4 main types of systems :-
Wet Pipe
Dry Pipe
Pre-Action
Deluge
76
WET PIPES SYSTEM
Wet pipe sprinkler systems contain water in the
riser and piping at all times. As soon as a
sprinkler head activates due to the heat of a fire,
water is immediately discharged through the
open head .
77
78
WET PIPE SYSTEM COMPONENTS
MAIN CONTROL VALVE
Butterfly Valve
OBJECTIVE :-
Shut down
system for
service
79
WET PIPE SYSTEM COMPONENTS
CONTROL VALVE
80
When the fire
protection system is
initially being
pressurized, water
will flow
into the system until
the water supply and
system pressure
become equalized,
and the torsion
Spring closes the
Clapper in the Alarm
Check Valve. Once
the pressures have
stabilized
81
2
Leakage in
System
Restriction
INLET
Assembly
OUTLET
Flow Inlet < Flow Outlet
(1)
Flow Inlet > Flow Outlet
1 (2)
82
FIRE,FIRE
ALARM
83
84
CHECK VALVE SYMBOL
CHECK VALVE
85
WET PIPE SYSTEM COMPONENTS
86
87
88
89
90
91
92
DRY PIPES SYSTEM
Dry pipe sprinkler systems contain air (or
sometimes nitrogen) in the riser and piping at
all times. The air (or nitrogen) is under pressure
and this pressure maintains a "differential dry
pipe valve" in the closed position
93
DRY PIPES SYSTEM
94
DRY PIPES SYSTEM
95
96
97
PROCEDURE
When one or more automatic sprinklers operate in response
to a fire, air pressure within the system piping is relieved
through the open sprinklers.
When the air pressure is sufficiently reduced, the water
pressure overcomes the differential holding the Clapper
Assembly closed and the Clapper Assembly swings clear of
the water seat,
This action permits water flow into the system piping and
subsequently to be discharged from any open sprinklers. Also,
with the Clapper Assembly open, the intermediate chamber is
pressurized and water flows through the alarm port.
98
PROCEDURE
After a valve actuation and upon subsequent closing of a
system main control valve to stop water flow, the Clapper
Assembly will latch open Latching open of the DPV-1 will
permit complete draining of the system through the main
drain port. During the valve resetting procedure and after
the system is completely drained, the external reset knob
can be easily depressed to externally unlatch the Clapper
Assembly
. As such, the Clapper Assembly is returned to its normal
set position to facilitate setting of the dry pipe sprinkler
system, without having to remove the Hand hole Cover.
99
100
101
PREACTION PIPES SYSTEM
A Preaction System is a sprinkler system
employing closed automatic sprinklers
connected to a piping system that contains air
or nitrogen that may or may not be
pressurized. A supplemental detection system
(release line) is installed in the same area as
the sprinklers
102
NFPA 13 DEFINES THREE BASIC TYPES OF
PREACTION SYSTEMS:
Single Interlocked: Admits water to sprinkler
piping upon operation of detection devices
only.
Double Interlocked: Admits water to
sprinkler piping upon operation of both the
detection devices and automatic sprinklers
103
PREACTION SYSTEMS:
Non-Interlocked: Admits water to sprinkler
piping upon either operation of detection
devices or automatic sprinklers.
104
PREACTION SYSTEMS:
105
PREACTION SYSTEMS:
In accordance with NFPA 13,
the preaction sprinkler system piping and fire
detection devices shall be automatically supervised
where there are more than 20 sprinklers on the
systems. This is accomplished with air or nitrogen gas
under pressure within the sprinkler piping. If the
integrity of the sprinkler piping is compromised, the
pressure will be reduced activating a supervisory
pressure switch that transmits the signal to the release
control panel and/or fire alarm panel.
106
PREACTION SYSTEMS:
Single Interlocked
107
PREACTION SYSTEMS:
Double Interlocked
114
PREACTION SYSTEMS:
. The double interlock preaction system
utilizes a detector system and pressurized air
or nitrogen in the sprinkler system piping.
This system is arranged so that the deluge
valve will open only when both pressure is
reduced in the sprinkler piping and the
detection system operates.
115
PREACTION SYSTEMS:
If the detection system operates due to
damage or malfunction, the valve will not
open, but an alarm will sound. If the sprinkler
piping is damaged or sprinkler is broken, the
valve will not open but a supervisory alarm
will sound. The operation of both a sprinkler
and a detector (or release) is required before
the valve will open, allowing water to enter the
system piping.
116
DELUGE SYSTEMS:
A deluge system is similar to a pre-action system except the
sprinkler heads are open and the pipe is not pressurized
with air. Deluge systems are connected to a water supply
through a deluge valve that is opened by the operation of a
smoke or heat detection system. The detection system is
installed in the same area as the sprinklers. When the
detection system is activated water discharges through all
of the sprinkler heads in the system. Deluge systems are
used in places that are considered high hazard areas such as
power plants, aircraft hangars and chemical storage or
processing facilities. Deluge systems are needed where high
velocity suppression is necessary to prevent fire spread
126
DELUGE SYSTEMS:
Deluge System with Electric actuated
127
DELUGE SYSTEMS:
Deluge System with wet pilot actuated
134
DELUGE SYSTEMS:
Deluge System with Dry pilot actuated
141
ZONE CONTROL VALVE ( FLOOR C V )
148