AND LOGIC

L1
SW 1(N.O) SW 2(N.O)

Lump

SW1 only turned on lamp will be no light.


SW2 only turned on lamp will be no light.
When both SW1 AND SW2 are turned on lamp will be light.
OR LOGIC

L1
SW 1(N.O)

Lump
SW 2(N.O)

When SW1 OR SW2 are turned on lamp will be light.


NOT LOGIC

SW 1(N.C)
L1

Lump

When SW1 is NOT turned off lamp will be light.


NAND LOGIC

SW 1(N.C)
L1

Lump
SW 2(N.C)

When SW1 is NOT turned off lamp will be light.


When SW2 is NOT turned off lamp will be light.
When both SW1 AND SW2 NOT turned off lamp will be light.
NOR LOGIC

SW 1(N.C) SW 2(N.C)
L1

Lump

When SW1 is turned off lamp will be NO light.


When SW2 is turned off lamp will be NO light.
When SW1 OR SW2 turned off will be NO light.
ON-DELAY LOGIC

T1
SW 1(N.O)
Timer 〇sec

L1
T 1(N.O)

Lump

When SW1 turned on T1(timer) will be working.


After timer count up(ON-DELAY) L1 will be light.
OFF-DELAY LOGIC

SW 1(N.O) T 1(N.C)
R1

R 1(N.O)
T1 Timer 〇sec

L1

Lump

When SW1 turned on R1(relay) will be working then hold to T1 and L1.
After timer count up(OFF-DELAY) L1 lighting will be turn off.
PB3 : On for AH
PB1 : On for AH PB4 : Off for AH
PB2 : Off for AH Mg2 : Magnetic contactor 1. When press to PB1 How working each device?
Mg1 : Magnetic contactor for AS
for AH L2 : Lump for AS
L1 : Lump for AH T2 : Timer number 2
T1 : Timer number 1
U V W
PB1 PB2 Mg2 TH T1
Mg1

Mg1
L1

T1

Mg1 Mg2
PB3 PB4 Mg1 TH T2
M g2

Mg2
L2

T2 TH

Motor
PB1 : On for AH PB3 : On for AH
PB2 : Off for AH PB4 : Off for AH
1. Press to PB1
Mg1 : Magnetic contactor Mg2 : Magnetic contactor
2. Magnetic contactor1 activate
for AH for AS
Lump1 righting
L1 : Lump for AH L2 : Lump for AS
Timer1 activate
T1 : Timer number 1 T2 : Timer number 2
U V W
PB1 PB2 Mg2 TH T1
Mg1

Mg1
L1

30sec
T1

Mg1 Mg2
PB3 PB4 Mg1 TH T2
M g2

Mg2
L2

30sec
T2 TH

Motor Motor turn to ahead


PB1 : On for AH PB3 : On for AH
PB2 : Off for AH PB4 : Off for AH
3. Mg1 contactor activate (NO close : NC open)
Mg1 : Magnetic contactor Mg2 : Magnetic contactor
1)Self-holding
for AH for AS
L1 : Lump for AH L2 : Lump for AS
T1 : Timer number 1 T2 : Timer number 2
U V W
PB1 PB2 Mg2 TH T1
Mg1

Mg1
L1

1)Self-holding
30sec
T1

Mg1 Mg2
PB3 PB4 Mg1 TH T2
M g2

Mg2
L2

30sec
T2 TH

Motor Motor turn to ahead


PB1 : On for AH PB3 : On for AH
PB2 : Off for AH PB4 : Off for AH
4. During motor turn to ahead press to PB3
Mg1 : Magnetic contactor Mg2 : Magnetic contactor
2)Interlock working then can not start Astrn
for AH for AS
L1 : Lump for AH L2 : Lump for AS
T1 : Timer number 1 T2 : Timer number 2
U V W
PB1 PB2 Mg2 TH T1
Mg1

Mg1
L1

1)Self-holding
30sec
T1

Mg1 Mg2
PB3 PB4 Mg1 TH T2
M g2

Mg2 2)Interlock
L2

30sec
T2 TH

Motor Motor turn to ahead


PB1 : On for AH PB3 : On for AH
PB2 : Off for AH PB4 : Off for AH
4. During motor turn to ahead press to PB2
Mg1 : Magnetic contactor Mg2 : Magnetic contactor
Mg1 : off , L1 : off , T1 : off , Mg1 contact off
for AH for AS
5. Stop motor turning (ahead)
L1 : Lump for AH L2 : Lump for AS
T1 : Timer number 1 T2 : Timer number 2
U V W
PB1 PB2 Mg2 TH T1
Mg1

Mg1
L1

1)Self-holding
30sec
T1

Mg1 Mg2
PB3 PB4 Mg1 TH T2
M g2

Mg2 2)Interlock
L2

30sec
T2 TH

Motor Motor turn is stop


PB1 : On for AH PB3 : On for AH
PB2 : Off for AH PB4 : Off for AH
6. When over load
Mg1 : Magnetic contactor Mg2 : Magnetic contactor
1)TH NC contact active
for AH for AS
L1 : Lump for AH L2 : Lump for AS
T1 : Timer number 1 T2 : Timer number 2
U V W
PB1 PB2 Mg2 TH T1
Mg1

Mg1
L1

1)Self-holding
30sec
T1

Mg1 Mg2
PB3 PB4 Mg1 TH T2
M g2

Mg2 2)Interlock
L2

30sec
T2 TH

Motor Motor turn to ahead


PB1 : On for AH PB3 : On for AH
PB2 : Off for AH PB4 : Off for AH
7. During motor turn to ahead TH active
Mg1 : Magnetic contactor Mg2 : Magnetic contactor
Mg1 : off , L1 : off , T1 : off , Mg1 contact off
for AH for AS
8. Stop motor turning (ahead) by 3) Safety interlock(TH)
L1 : Lump for AH L2 : Lump for AS
T1 : Timer number 1 T2 : Timer number 2
U V W
PB1 PB2 Mg2 TH T1
Mg1

Mg1
3)Safety Interlock
L1

1)Self-holding
30sec
T1

Mg1 Mg2
PB3 PB4 Mg1 TH T2
M g2

Mg2 2)Interlock
L2

30sec
T2 TH

Motor Motor turn is stop


PB1 : On for AH PB3 : On for AH
PB2 : Off for AH PB4 : Off for AH
9. After 30sec.
Mg1 : Magnetic contactor Mg2 : Magnetic contactor
1)T1 active
for AH for AS
L1 : Lump for AH L2 : Lump for AS
T1 : Timer number 1 T2 : Timer number 2
U V W
PB1 PB2 Mg2 TH T1
Mg1

Mg1
3)Safety Interlock
L1

1)Self-holding
30sec
T1

Mg1 Mg2
PB3 PB4 Mg1 TH T2
M g2

Mg2 2)Interlock
L2

30sec
T2 TH

Motor Motor turn to ahead


PB1 : On for AH PB3 : On for AH
PB2 : Off for AH PB4 : Off for AH
10. During motor turn to ahead T1 active
Mg1 : Magnetic contactor Mg2 : Magnetic contactor
Mg1 : off , L1 : off , T1 : off , Mg1 contact off
for AH for AS
8. Stop motor turning (ahead) by 4) Self kill circuit (T1)
L1 : Lump for AH L2 : Lump for AS
T1 : Timer number 1 T2 : Timer number 2
4) Self kill circuit U V W
PB1 PB2 Mg2 TH T1
Mg1

Mg1
3)Safety Interlock
L1

1)Self-holding
30sec
T1

Mg1 Mg2
PB3 PB4 Mg1 TH T2
M g2

Mg2 2)Interlock
L2

30sec
T2 TH

Motor Motor turn is stop