SUSUTAN VOLTAN
&
PENGIRAAN

CAW. KEJ. ELEKTRIK, IP JKR MALAYSIA


KENAPA SUSUT VOLTAN?

 Semua kabel mempunyai


rintangan.
 Apabila arus mengalir melalui
kabel tersebut, akan terhasil susut
voltan. Ini berpandukan kepada
formula
V=IxR

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


JUMLAH SUSUT VOLTAN

Requirement of IEE Wiring Regulation


525-01-01
‘The voltage drop between the
origin of the installation (usually
the supply terminals) and terminals
of the fixed current – using
equipment does not exceed 4% of
the nominal voltage of the supply’

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


SUSUT VOLTAN (BANGUNAN)

 Susut voltan tidak boleh melebihi


4% daripada nominal voltage

 4% of 1Φ – 4% of 240 V
(9.6 Volt)

 4% of 3 Φ – 4% of 415 V
(16.6 Volt)

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


CONTOH PENGIRAAN

1. MSB DB LOAD
3.5% drop 0.5% drop

2. MSB SSB DB LOAD


2% drop 1.5% drop 0.5% drop

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


CONTOH PENGIRAAN

3. MSB SSB FP DB LOAD


0.5% drop

voltage drop 3.5%

4. MSB FP SSB DB LOAD


0.5% drop

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


SUSUTAN VOLTAN
Susutan Voltan berkait Rapat
dengan Saiz Kabel
VD = vd x In x L
1000
VD - jumlah susut voltan
Vd - susut voltan kabel
mV/A/m(rujuk jadual)
In - kadar arus breaker (A)
L - panjang kabel (meter)
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Submain Kabel Ke DB

 Maksimum saiz kabel hanya 35


mm2
 60 A DP/TPN/4P MCCB
 Review pembahagian 4% susut
voltan

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


SAIZ KABEL

Boleh menanggung arus


rekabentuk, Ib
Arus keupayaan kabel, Iz
mestilah lebih besar atau sama
dengan arus pemutus litar, In

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


SAIZ KABEL

In > Ib
Iz > In
Iz > In > Ib
In – Arus Pemutus Litar
Iz – Arus Keupayaan Kabel
Ib – Arus Rekabentuk
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
JENIS KABEL

 PVC, PVC/PVC
– Rujuk jadual - thermoplastic
 XLPE, XLPE/PVC (>25 mm2)
– Rujuk jadual - thermosetting
 PVC/SWA/PVC
 XLPE/SWA/PVC (>25 mm2)
 Fire Rated Cable
– MIMS (Mineral Insulated Mineral
– Sheathed Copper Conductor)
– MICC (Mineral Insulated Copper Clad
Copper Conductor)
CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA
Kaedah Pemasangan Kabel
 GI Conduit – PVC
 Galvanised/H.D.G. Trunking – PVC
 Hot Dipped Galvanised Perforated
Cable Tray – PVC/PVC, XLPE/PVC,
PVC/SWA/PVC,XLPE/SWA/PVC
 Hot Dipped Galvanised Cable
Ladder – PVC/PVC, XLPE/PVC,
PVC/SWA/PVC,XLPE/SWA/PVC

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


Contoh Pengiraan………

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


SUSUT VOLTAN (LUAR BANGUNAN)

 Susut voltan tidak boleh melebihi


20V daripada nominal voltage

 Lampu akhir mendapat 220V

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


CONTOH PENGIRAAN

1. MSB Last
CLCB
CL
abaikan 20V

Susutan Voltan 20V

2. Last
MSB FP
CL
?V ?V

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


CONTOH PENGIRAAN

Susutan Voltan 20V

3. MSB FP CLCB Last


CL
?V ?V ?V

Di Pondok
Pengawal

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


Formula Susutan Voltan

VD1 = vd x L x I x no. of lantern


1000
VD - jumlah susut voltan
vd - susut voltan kabel mV/A/m(rujuk
jadual)
I - arus lampu (A)
L - panjang kabel (meter)

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


SUSUT VOLTAN LAMPU JALAN
Voltage drop di kira pada setiap jarak
antara tiang-tiang lampu
Bagi pemasangan 1 fasa :
VDn = vd x L x I x no. of
lantern
1000
VD1 = (vd x L x I x 16)/1000
VD2 = (vd x L x I x 15)/1000
dan seterusnya…sehingga
VD16 = (vd x L x I x 1)/1000

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


Kabel Lampu Kawasan

 Kabel Bawah Tanah


2C 6 mm2 PVC/SWA/PVC
2C 10 mm2 PVC/SWA/PVC
2C 16 mm2 PVC/SWA/PVC
 Tertakluk kepada satu kabel masuk
dan satu kabel keluar sahaja
 Elak guna 1 kabel masuk dan 2
kabel keluar

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


Jumlah Susut Voltan

 VD = Vd1 + Vd2 + ……..+ Vd16


= 20V
 Hanya untuk Contoh Pengiraan
No. 1
 Berbeza untuk Contoh Pengiraan
No. 2 & 3

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


Lantern Lampu Kawasan

 70W SON
 Control Gear
 Choke
 Ignitor
 Capacitor
 Remote/Integral Control Gear

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


Compound Lighting Control Board

 Dalam bilik suis/Pondok Pengawal


 Sebelah MSB
 2 set timer
 7pm to 12 am
 7pm to 7am
 Alternate circuit
 Elak letak di luar bangunan

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


Tiang Lampu Kawasan
 Galvanised
 Octagonal/round tapered
 Hot Dipped Galvanised
 Fiber
 Decorative
 Twin service door
 3.5m – 5m mounting height
 Jarak 15m – 20m

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


Junction Box

 Konvensional
 Modular

CAWANGAN KEJURUTERAAN ELEKTRIK, IBU PEJABAT JKR MALAYSIA


LOGO

CAW. KEJ. ELEKTRIK, IP JKR MALAYSIA

You might also like