You are on page 1of 18

MINISTRY OF ENERGY

IRAN POWER DEVELOPMENT COMPANY

I.P.D.C.
PROJECT: ARDEBIL-EXT. GAS TURBINE POWER PLANT

FIRE FIGHTING SYSTEM PUMPS DATA SHEETS

IN HOUSE REVISION
D C B A 0 0

DOCUMENT REVISION

ISUUED FOR APPROVAL

SAP DESG.

SEP. 2009

M.N.

SEP. 2009

S.R. SEP. 2009

REV.

DESCRIPTION

DESG.

DATE

CHK.

DATE

APP.

DATE

REV.

DESCRIPTION

DATE

CHK.

DATE

APP. DATE

Client Doc. No.: TSM/AL-28/FF-M-31-DL0-001 MAPNA GROUP Contractor Doc. No.: SE Code: MF Code: File No.:

Rev. 0

Page 1 of 15

MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY

I.P.D.C.
PROJECT: ARDEBIL-EXT. GAS TURBINE POWER PLANT
PAGE

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53

0 X X

REVISION C D E

REMARKS

PAGE 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106

REVISION C D

REMARKS

X X X X X X X X X X X X X

Client Doc. No.: TSM/AL-28/FF-M-31-DL0-001 MAPNA GROUP Contractor Doc. No.: SE Code: MF Code: File No.:

Rev. 0

Page 2 of 15

MINISTRY OF ENERGY
IRAN POWER DEVELOPMENT COMPANY

I.P.D.C.
PROJECT: ARDEBIL-EXT. GAS TURBINE POWER PLANT

TABLE OF CONTENT
1. 2. 3.

PAGE

MAIN DIESEL FIRE PUMP............................................................................................................................................................4 MAIN ELECTRICAL FIRE PUMP ...............................................................................................................................................10 JOCKEY ELECTRICAL PUMP ...................................................................................................................................................14

Client Doc. No.: TSM/AL-28/FF-M-31-DL0-001 MAPNA GROUP Contractor Doc. No.: SE Code: MF Code: File No.:

Rev. 0

Page 3 of 15

PAGE

OF

15 SEP 2009 M.N. S.R.

DIESEL ENGINE DATA SHEET SI UNITS


1 APPLICABLE TO: 2 FOR 3 SITE 4 NO. REQ. 5 MANUFACTURER 6 NOTE: 7 9 11 12 13 14 16 17 18 19 20 21 23 24 25 26 27 28 29

CONTRACT No. : DOC. No. : PREPARED BY : REVISION

TSM/AL-28/FF-M-31-DL0-001 S.P. 0
UNIT SERVICE TYPE MODEL

DATE CHECKED BY :

PROPOSAL
ARDEBIL EXT. G.T.P.P. ARDEBIL EXT. TWO CLARKE

PURCHASE

APPR. BY : AS BUILT

FIRE FIGHTING JW6H-UF60


TAG NO.

INDICATES INFORMATION COMPLETED BY PURCHASER

BY MANUFACTURER

OPERATING CONDITIONS

39.5

BY MANUFACTURER OR PURCHASER

SITE DATA
M C C

DIESEL ENGINE POWER ( RATED/MAX. )

268

KW

10 SPEED:

1770
FROM

VARIABLE SPEED CONSTANT SPEED



OVERSPEED

1340 ALTITUDE AMBIENT TEMPERATURE , NORMAL


MAXI. MINI.

MAX ALLOWABLE WORKING SPEED

600 1760 2112 2400

TO

2400

RPM RPM RPM RPM

-37 96

RELATIVE HUMIDITY: MAX/MIN UNUSUAL CONDITIONS:


INSTALLATION:

15 OVER LOAD :
SITE POWER SPEED FREQUENCY- TIME RATED VOLTAGE ESTABLISHMENT TIME FULL LOAD ESTABLISHMENT TIME max. sound level 110dB (REV A) SEC SEC RPM KW

1760

RPM

ELECTRICAL AREA CLASSIFICATION:


CLOR OF WATER:

INDOOR OUTDOOR GRADE

HEATED UNHEATED MEZZANINE

UNDER ROOF PARTIAL SIDES UNDER GRADE


SAFE AREA

2184 PPM

AVAILABLE UTILITIES
COOLING WATER:
TEMP. INLET PRESS. INLET MIN RETURN STEAM: PRESSURE:MIN / MAX TEMPERATURE:MIN / MAX BARG C 15 C TEMP. RETURN 35 C BARG BARG BARG DESIGN MAX ALLOW DP

22 DIRECTION OF ROTATION (VIEW FROM COUPLING SIDE)

CW

CCW

APPLICABLE CODE & STANDARDS

ISO OTHER SHOP INSPECTION BY CONTROL AGENCY


TEST

NFPA-20 UL/FM

ASME / ANSI

SHOP TEST - INSPECTION

NON-WIT

WIT

30 STANDARD SHOP TEST 31 HYDROSTATIC TEST 32 MECHANICAL RUNNING & PERFORMANCE TEST 33 STARTING SYSTEM TEST 34 NOISE LEVEL TEST 35 SURFACE TEMPERATURE TEST 36 OVERSPEED TRIP DEVICE TEST 37 38 39 40 41 42 43

ELECTRIC SUPPLY (FOR BATTERY CHAGER):


CONTROL AC / DC VOLTS PHASE HERTZ

AC

220

50

PAINTING

POLYURETHANE ,RED COLOR RAL 3000

OTHER ( PLEASE SPECIFY ) FUEL OIL:

LUBE OIL: INSTRUMENT AIR: STARTING AIR: COOLING WATER:

UTILITY CONSUMPTION
Kg/KW. Hr LIT M3/Hr M /TIM M3/MIN
3

SHIPMENT

DOMESTIC EXPORT EXPORT BOXING REQUIRED OUTDOOR STORAGE MORE THAN 6 MONTHS
WIRING & INSTRUMENTATION

ACCESSORIES PROVIDED BY MANUFACTURER 44 BASE PLATE / SKID UNIT x SPECIAL TOOLS


45 FOUNDATION BOLTS 46 ENGINE FITTING BOLTS 47 FLYWHEEL & GUARD 48 EXHAUST SILENCER 49 COUPLING AND GUARD 50 COUPLING BOLTS 51 AIR DUCTING & SUPPORT 52 EXHAUST DUCTING & SUPPORT 53 PROTECTION DEVICE 54 STARTING SYSTEM 55 BARRING SYSTEM 56 ANTIVIBRATION DEVICE 57 SAFETY GUARD FOR FLYWHEEL & FAN 58 HEAT EXCHANGER 59 REMARKS: 60

x x x x x

BATTERY & CHARGER LOCAL CONTROL PANEL FUEL INTERCONNECTING PIPING WALKWAYS, LADDERS SPEED GOVERNING SYSTEM TURBOCHARGING SYSTEM INLET AIR FILTER & SUPPORT DAY FUEL TANK

x x x

STARTING SYSTEM
AIR STARTING

NUMBER OF TANKS CAPACITY PRESSURE NUMBER OF STARTS

ONE M3/H BAR

OVERSPEED SAFETY DEVICE OIL COOLER WATER COOLER FUEL COOLER

x BATTERY NO. OF BATTERY : 2 SETS x BATTERY CHARGER YES x STARTING: x LOCAL x MANUAL AUTO/MANUAL SELECTOR SWITCH

ELECTRIC STARTING 24
VOLTAGE

POWER

KW

REMOTE: MANUAL

AUTO

ALL CHECKS TO BE DURING STRING TEST .

*)Information must be given by manufacturer

PAGE

OF

15

DIESEL ENGINE DATA SHEET SI UNITS


CHARACTERISTICS
61

CONTRACT No. : DOC. No. : PREPARED BY : REVISION

TSM/AL-28/FF-M-31-DL0-001 S.P. 0

DATE CHECKED BY : APPR. BY :

SEP.2009 M.N. S.R.

CONTINUOUS USE

62 CYCLE: 63

EMERGENCY USE

4 STROKE
DOUBLE ACTING IN-LINE

AIR FILTER:

2 STROKE

SINGLE ACTING

64 CYLINDER ARRANGEMENT 65 66
NUMBER OF CYLINDERS CYLINDER BORE X STROKE

VEE

AIR INLET SYSTEM


SINGLE DRY

DUPLEX OIL BATH

TURBOCHARGING AIR COOLER: TYPE MANUFACTURER PIPING NUMBER

6 116 127
mm

EXPANSION JOINTS

67 EXHAUST & SUCTION VALVE: 68 69 70 71 72

ONE FOR EACH CYLINDER

15.7 : 1

TWO FOR EACH CYLINDER BARG BARG M/S @ RATED SPEED FRAME CYLINDER LINERS
CAST IRON ALLOY IRON PLATEAU FORGED STEEL ALLOY CAST IRON

MAIN EFFECTIVE PRESS. MAX. CYLINDER PRESS. PISTON SPEED COMPRESSION RATIO

MATERIAL
CRANKSHAFT CAMSHAFT CONNECTING ROD CROSSHEADS PISTONS PISTON RINGS
STEEL CROWN AL.S. TOP-PLASMA COATED FORGED STEEL STEEL HARDENED
FORGED STEEL ALLOY

73 COOLING SYSTEM: 74 75

AIR WATER

AIR/ WATER COOLED WATER / WATER COOLED M


3

TIE-ROD

CYLINDER-HEAD CROSSHEAD

COOLING WATER TANK CAPACITY:

76 WATER PUMP: 77 78 79 80 81

SHAFT DRIVEN

TURBOCHARGER NUMBER MANUFACTURER PRESSURE RATIO SPEED

SUPER CHARGER

MOTOR DRIVEN VALVES EXHAUST OIL COOLER:


TUBES

SECOND,TAPERED CAST IRON.3RD CHROMIUM FACED

NORMALLY ASPIRATED

SPARK ARRESTER SHELL OIL HEATING COIL

MODEL

OIL FILTER ELEMENTS

OIL LUBRICATING PIPING BEFORE / AFTER FILTER

1760

RPM

BOLTING

82 POWER TRANSMISSION: 83 84 85

FLEXIBLE COUPLING


SINGLE

RIGID COUPLING

V-BELT

MANUAL

BARRING SYSTEM
ELECTRICAL

HYDRAULIC

LUBRICATION
PRESSURE SYSTEM DUPLEX ENGINE PIPE OUTLET SILENCER EXPANSION JOINT

SPLASH SYSTEM

86 LUBE OIL FILTER: 87 OIL COOLER: 88 89 90 91 92 93 94 95 96

EXHAUST SYSTEM

SPARKED ARRESTER

SINGLE SHELL & TUBE TYPE RADIATOR TYPE

DUPLEX PLATE TYPE

FUEL
FUEL SUPPLY TO ENGINE BY : INJECTION PUMP:

OIL HEATER TYPE: POWER

2.5

ELECTRICAL KW

STEAM COIL
CONSUMPTION FLANGES IN/ * /


SINGLE

GRAVITY
SINGLE

OTHER EXPLOSION PROOF

FUEL OIL SUPPLY PUMP: FILTER:

PUMP
DUPLEX

SHAFT DRIVEN

KG/H / C

MOTOR DRIVEN

DUPLEX

FUEL SHUT OF VALVE

FUEL TANK CAPACITY:

RATING IN/ OUT

97 MINIMUM STARTING OIL TEMPERATURE 98

FUEL CHARACTERISTICS:
KIND OF FUEL: GASOIL

440 GALLONS
SEPARATED

FIXED TO THE SET

PUMPS:

MAIN

AUXILIARY

99 TYPE 100 FLOW 101 DRIVER 102 SPEED 103 POWER 104 MATERIAL 105 AUXILIARY PUMP: 106 107 108 109 110 REMARKS: 111
*)Information must be given by manufacturer RPM KW LIT/MIN

KINEMATIC VISCOSITY AT 100 F FLASH / POUR / CLOUD POINT SULPHUR ASH WATER AND SEDIMENTS SPECIFIC GRAVITY AT 60/60F CARBON RESIDUE

3.8 1 < 0.01

CST

C WT% WT% VOL%

WT%

PRELUBE

STARTING

STAND BY

CETANE INDEX

FUEL TO AIR RATIO SPECIFIC FUEL CONSUMPTION ACIDITY Lit./KW mgKOH/gr

PAGE

OF

15

DIESEL ENGINE DATA SHEET SI UNITS


AIR COOLED EXCHANGER (N/A)
112 113 114 115 116 117 118 119 120 121

CONTRACT No. : DOC. No. : PREPARED BY : REVISION

TSM/AL-28/FF-M-31-DL0-001 S.P. 0
SERVICE FLUID FLOW OPERATING TEMPERATU INLET / OUTLET WATER TEMPERATU INLET / OUTLET TEST PRESSURE FOULING FACTOR TOTAL AREA SHELL: DIAMETER TUBES: NUMBER PER SHELL DIAMETER FLANGES MM DIAMETER MM COOLING WATER

DATE CHECKED BY : APPR. BY :

SEP.2009 M.N. S.R.

WATER COOLED EXCHANGER


M /H
3

FLOW: AIR TEMPERATU INLET / OUTLET WATER TEMPERATU INLET / OUTLET TEST PRESSURE FOULING FACTOR TOTAL AREA TUBES: PLUNGER: INLET / OUTLET: DRAIN / VENT: DIAMETER mm DIAMETER LENGTH RATING FACE / /

C C BAR
2 M H C / kcal

/ /

/ /

/ /

122 FAN: 123 124 125 126 127 128 129


NO. REQ'D: CAPACITY SET(S) NM3/MIN

M3/H

25/60 25/60

C C BAR M2H C / kcal M

LENGTH

THICKNESS SERIAL

MM FACE

INLET / OUTLET DRAIN / VENT

* / * /

SUCTION TYPE SHAFT DRIVEN

/ /

THREADED

PUSHER TYPE MOTOR DRIVEN RPM

MATERIAL:
SHELL SHELL SHEETS CHANNEL-SHELL FLANGES

SPEED: MATERIAL: POWER:

kw

TUBES BAFFLES CHANNEL

CU-IN

130 BLADES: 131 132

FIXED PITCH MANUAL

VARIABLE AUTOMATIC

DIAMETER

133 POWER TRANSMISSION: 134 135 136 137 138 139 140 LOW LUB OIL PRES. 141 HIGH ENGINE WATER TEMP. 142 HIGH COOLING WATER TEMP. LEAVING THE 143 ENGINE JACKETS 144 LOW & HIGH FUEL LEVEL IN FUEL OIL DAILY TANK 145 146 LOW LUB OIL LEVEL SUMP. 147 BATTERY CHARGER FAILURE 148 HIGH CHARGED AIR TEMP. IN TURBOCHARGER 149 AND INTER-COOLED ENGINE 150 151 OVERSPEED 152 153 154 155 156 REMARKS: 157 158 159 160 161 162
ALARM

RIGID COUPLING TYPE TYPE Kw

DIMENSIONS
V-BELT NUMBER HEIGHT UNDER HOOK OVERALL DIMENSION (L X W X H) M M M DIMENSIONS FOR MAINTENANCE

BELTS: MOTOR: POWER

SPEED

RPM

INSTRUMENTATION
SHUTDOWN

DIFFERENTIAL PRESSURE SWITCH ON FILTER ENGINE SPEED INDICATOR TACHOMETER


PRESSURE GAUGES:

LUBE OIL
TEMPERATURE GAUGES:

COOLING WATER

BOOST AIR

COOLING WATER LUBE OIL EXHAUST GAS TEMPERATURE GAUGE (UP STREAM OF TURBO CHARGER) THERMOMETER AND THERMOWELL FOR EACH CYLINDER WEIGHTS
HEAVIEST PART FOR ERECTION HEAVIEST PART FOR MAINTENANCE WEIGHT OF ENGINE ONLY WEIGHT OF THE SET WEIGHT OF RADIATOR: EMPTY/WITH LIQUID WEIGHT OF WATER COOLED EXCHANGER : ALLOWABLE LOAD ON WALKWAYS

* * * *

KG KG KG KG KG

* * *

KG KG

This document is the property of MAPNA who will safeguard its rights according to the civil and penal provisions of the law

PAGE

OF

15

DIESEL ENGINE DATA SHEET SI UNITS

CONTRACT No. : DOC. No. : PREPARED BY : REVISION

TSM/AL-28/FF-M-31-DL0-001 S.P. 0

DATE CHECKED BY : APPR. BY :

JUN.2009 M.N. S.R.

GENERAL NOTES 163 164 1- THE WHOLE PACKAGE SHALL BE FULLY COMPLIANT WITH NFPA-20 . 165 2- MAXIMUM BRAKE HORSEPOWER SHALL COVER ANY FLOW FROM SHUT-OFF TO 150% RATED FLOW .ENGINE RATING 166 CONDITIONS AND DEDUCTIONS SHALL MEET NFPA-20 REQUIREMENTS . 167 3- TWO MEANS OF RECHARGING STORAGE BATTERIES SHALL BE PROVIDED .THE SECOND MEANS SHALL BE THE GENERATOR 168 OR ALTERNATOR SUPPLIED WITH THE ENGINE . 169 4- BATTERIES SHALL BE LEAD ACID TYPE . 170 5- DAILY FUEL TANK SHALL BE SIZED IN ACCORDANCE WITH NFPA-20 FOR CONTINUOUS OPERATION AT 150% RATED FLOW 171 OVER AN 8 HOUR PERIOD . 172 6- AUTOMATIC SHUTDOWN SHALL BE INITIATED BY ENGINE OVERSPEED ONLY . 173 7- THE CONTROLLER SHALL MEET THE REQUIREMENTS OF BOTH THE PRIME ELECTRICAL AND THE EMERGENCY 174 175 176 177 8- SCOPE OF SUPPLY INCLUDES : 178 179 - DIESEL ENGINE WITH AUXILIARIES AND LIFTING POINTS 180 - DIESEL ENGINE COOLING SYSTEM (HEAT EXCHANGER) 181 - DIESEL ENGINE LUBRICATING SYSTEM 182 - DIESEL ENGINE ELECTRIC STARTING SYSTEMS WITH BATTERY CHARGER 184 SUPPORT STAND AND MOUNTING FEET 185 - DIESEL ENGINE AIR INTAKE FILTERS WITH AIR SHUT-OFF VALVES 186 - EXHAUST PIPING ,FLEXIBLE CONNECTIONS ,SILENCERS WITH RAIN CAPS ,SPARK ARRESTER ,AND INSULATION ON ENGINE 187 MOUNTED ELEMENTS 188 - DIESEL ENGINE INSTRUMENTATION AND CONTROLS ,PROTECTION AND ALARMS 189 - INTERCONNECTING POWER AND CONTROL WIRING/CABLING BETWEEN ALL EQUIPMENTS WITHIN BASEPLATE/CABINETS 190 - SPARE PARTS FOR COMMISSIONING & 2 YEARS 191 - SPECIAL TOOLS ( NOT REQUIRED STATED BY VENDOR ) 192 - LIFTING FRAME AND SLINGS FOR ALL EQUIPMENT ON COMBINED BASEPLATE ( NOT REQUIRED STATED BY VENDOR ) 193 - OTHER COMPLEMENTARY ACCESSORIES FOR PROPER OPERATION OF ENGINE 194 - INSPECTION AND TESTING 195 - PRESERVATION AND EXPORT BOXING 196 - DOCUMENTATION 197 198 199 200 201 202 203 204 205 206 207 208 209 STARTING/SHUTDOWN SYSTEM .THE CONTROLLER SHALL ARRANGE THAT ,UPON RECEIPT OF A STARTING SIGNAL , START UP USING THE PRIME STARTING SYSTEM SHALL BE ATTEMPTED .

PAGE

OF

15

MAIN DIESEL FIRE PUMP DATA SHEET SI UNITS

CONTRACT No. : DOC. No. : PREPARED BY : REVISION

TSM/AL-28/FF-M-31-DL0-001 S.P. 0

DATE CHECKED BY : APPR. BY :

SEP.2009 M.N. S.R.

GENERAL 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
SITE DATA : RELATIVE DENSITY APPLICABLE TO: FOR SITE NO. REQ. MANUFACTURER NOTE:

PROPOSAL
ARDEBIL EXT. G.T.P.P. ARDEBIL TWO
PUMP SIZE

PURCHASE UNIT SERVICE TYPE

AS BUILT

FIRE FIGHTING CENTRIFUGAL/HORIZONTAL 10x8 M TAG NO. *

PATTERSON

MODEL

INDICATES INFORMATION COMPLETED BY PURCHASER


PURCHASER'S REQUIREMENTS
RAW WATER
NORMAL MAXIMUM MINIMUM

BY MANUFACTURER

10"

BY MANUFACTURER OR PURCHASER

CONSTRUCTION
NOZZLES SUCTION DISCHARGE BALANCE DRUM

LIQUID PUMPING TEMP. (C)

15 40 1 0.1

SIZE LOCATION FACING RATING

8" SIDE FF 150# 27


18

SIDE FF 150#

0.999 1

@ PUMP TEMP.

VAPOR PRESSURE @ MAXIMUM TEMP. (bara) VISCOSITY (CENTIPOISE)


3

@ PUMP TEMP.

480 RATED CAPACITY (m / h) 10 DISCHARGE PRESSURE (barg) 0.4 SUCTION PRESSURE (barg) MAX/RATED / 100 DIFFERENTIAL HEAD (m) 10 DIFFERENTIAL PRESSURE (bar) 1.755 HEAD LOSS FROM TANK TO PUMP SUCTION (mwc) 1.4 MINIMUM AVAILABLE STATIC SUCTION HEAD (mwc) 8. NPSH AVAILABLE@150%RATED CAPACITY(mwc) SITE AND UTILITY DATA
LOCATION :

HYDRAULIC TEST PRESSURE (barg) DESIGN PRESSURE (barG):

MAXIMUM ALLOWABLE WORKING PRESSURE AT RATED TEMP.(barG): SHUTT-OFF PRESSURE (barG): FLOW RATE / HEAD CURVE SUPPLIED : DRIVER SPEED (rpm) EFFICIENCY AT RATED CAPACITY : EFFICIENCY AT 150% RATED CAPACITY : MIN. CONTINUOUS FLOW (m / h)
3

18

11.0
YES

0.05

A02-112725

1770 76 86
MECHANICAL THERMAL

100m3/h

< 100 m3/h


107 209 4.9
STEEL

RATED POWER (KW): MAX. HEAD WITH RATED IMPELLER (m): MAX. POWER WITH RATED IMPELLER (KW): REQUIRED NPSH AT 150% RATED CAPACITY (m) : COOLING / HEATING PIPING : TUBE

OUTDOOR UNHEATED GRADE MEZZANINE ELECTRICAL AREA CLASSIFICATION


INDOOR HEATED CL GR
'

PARTIAL SIDES
UNDER ROOF DIV SAFE AREA
'

MATERIAL PIPE FLANGED

THREADED SEAL WELDED AUXILIARY PIPING:

WINTERIZATION REQ D

TROPICALIZATION REQ D
(mbara)

SOCKET - WELDED MATERIAL

STEEL

1340 860 (m) BAROMETER ALTITUDE -37 / 39.5 RANGE OF AMBIENT TEMPS: MIN/MAX 96 RELATIVE HUMIDITY: MAX./MIN. UNUSUAL CONDITIONS (2.1.23) DUST FUMES
CHLORIDE CONTENT:

(C) CASING MOUNTING (%) CENTERLINE

NEAR CENTERLINE FOOT VERTICAL

2184PPM

UTILITY CONDITIONS: DRIVERS (bar) (bar) DRIVERS CONTROL (C) (C) HEATING (barg) (barg) HEATING SHUTDOWN

STEAM: MIN MAX ELECTRICITY: VOLTAGE HERTZ PHASE COOLING WATER: TEMP. INLET PRESS. INLET PRESS. RETURN

VERTICAL BARREL (C) CASING SPLIT:* (C) CASING TYPE* SINGLE VOLUTE DIFFUSER IMPELLER MOUNTING:* BETWEEN BEARINGS AXIAL

BRACKET IN -LINE

SUMP OTHERS RADIAL

DOUBLE VOLUTE STAGGERED

230 50 1

230 50 1

OVERHUNG

25 10

(C)

TEMP. RETURN

60 4

(C) (barg) (barg)

DRAIN

VENT

PRESSURE GAUGE

CIRCULATING RELIEF VALVE

(barg) DESIGN (barg) MAX ALLOW DP

1/2"

1/2"

1/2"

PAGE

OF

15

MAIN DIESEL FIRE PUMP DATA SHEET SI UNITS


CONSTRUCTION (CONTINUED)

CONTRACT No. : DOC. No. : PREPARED BY : REVISION

TSM/AL-28/FF-M-31-DL0-001 S.P. 0
BARREL / CASE WEAR RINGS SHAFT

DATE CHECKED BY : APPR. BY :

SEP.2009 M.N. S.R. BRONZE STEEL STEEL

MATERIAL CAST IRON BRONZE CAST IRON


IMPELLER BASE / SKID

49 50
48 51 52 53 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102

NUMBER OF STAGES: BALANCING METHOD: IMPELLER DIAMETER (mm) RATED MIN. MAX.

STAINLESS STEEL(416SS) SLEEVE

444 mm 400 mm 458 mm FELXIBLE


MFR:

STUFFING BOX BEARING HOUSING REMARKS

TROTTLE BUSHING

54 COUPLING:

TYPE:

WEIGHTS *
STEEL
WEIGHT OF PUMP (kg) WEIGHT OF BASEPLATE (kg) WEIGHT OF MOTOR (kg)

SPACER LENGTH: MATERIAL

600 600 929 2129

BASEPLATE

TYPE: GROUTING HOLE:

STEEL

TOTAL WEIGHT (kg)

REMARKS

PUMP LENGTH (m):

SPECIAL DATA FOR VERTICAL PUMPS N/A N/A N/A


THREADED ENCLOSED

MINIMUM SUBMERGENCE (m):

MECHANICAL SEAL OR PACKING

MAXIMUM SUCTION HEIGHT (m): COLUMN PIPE: FLANGED

PACKING:

MANUFACTURER TYPE SIZE / MODEL

SOFT PACKING 1/2" Sq. 5

LINE SHAFT: OPEN GUIDE BUSHING LUBRICATOR: PUMP THRUST (N) AT MIN. FLOW UP

MECHANICAL SEAL

API CLASS CODE MANUFACTURER SIZE / MODEL

DOWN

GLAND : TYPE / MODEL QUENCH DRAIN MATERIAL:

SPLIT FLUSH VENT


YES

PRESSURE SWITCH SET POINTS - PUMP STOP POINT : MANUALLY

BORNZE

SEAL FLUSH PIPING PLAN REQUIRED CARBON STEEL TUBE THREADED SEAL WELDED STAINLESS STEEL PIPE FLANGED SOCKET - WELDED

- PUMP START POINT : ELECTRICAL PUMP START POINT MINUS 0.68 bar.g PAINTING

REMARKS

POLYURETHANE ,RED COLOR RAL 3000

BEARINGS AND LUBRICATION


BEARING TYPE 1 RADIAL. BEARING TYPE 2 RADIAL. LUBRICATION TYPE: GREASE OIL MIST FLINGER NO. OTHERS ( PLEASE SPECIFY )

NOTES
*)Information must be given by manufacturer

*
AXIAL

NO.

AXIAL

RING OIL FLOOD PRESSURE

APPLICABLE STANDARDS

ANSI B73.1-1978 UL/FM


TEST

ANSI B73.2-1975

NON -WIT

NFPA-20
WIT

INSPECTION AND TEST


HYDROSTATIC PERFORMANCE NPSH COMPLETE UNIT TEST

PAGE

10

OF

15

MAIN DIESEL FIRE PUMP DATA SHEET SI UNITS

CONTRACT No. : DOC. No. : PREPARED BY : REVISION

GT3/AL-28/FF-M-31-DL0-001 S.P. 0

DATE CHECKED BY : APPR. BY :

SEP.2009 M.N. S.R.

GENERAL NOTES 103 1- THE WHOLE PACKAGE SHALL BE FULLY COMPLIANT WITH NFPA-20 . 104 3- AN NPSH TEST IS ALSO REQUIRED AT 150% RATED FLOW . 105 4- FIRE PUMP CONTROLLER SHALL BE PROVIDED FOR EACH FIRE WATER PUMP .ENCLOSURE SHALL BE IP-44 . CONTROLLER SHALL BE LOCATEED ON THE COMMON ENGINE & PUMP BASEPLATE . 106 107 2-STAR ITEM SHOULD BE FILLED BY VENDOR 108 109 5- SCOPE OF SUPPLY INCLUDES : 110 111 - PUMP 112 - DIESEL ENGINE 113 - INTERCONNECTING POWER AND CONTROL WIRING/CABLING BETWEEN ALL EQUIPMENTS WITHIN BASEPLATE / CABINETS 114 - FLEXIBLE COUPLINGS & GUARDS 115 - COMMON BASEPLATE WITH ANCHOR POINTS ,LIFTING POINTS AND EARTH POINTS 116 - COMBINED MANUAL/AUTOMATIC FIRE PUMP CONTROLLER AND CONTROLLER PANEL 117 - GAUGE BOARD (s) 118 - MAIN 8"- SIZE RELIEF VALVE IN ACCORDING TO TABLE 2-20 OF NFPA-20 (6" IS REQUIRED WITH 6"X10" WASTE CONE) 119 - 1/2" AUTOMATIC AIR RELEASE VALVE 120 - SPARE PARTS FOR COMMISSIONING & 2 YEARS 121 - SPECIAL TOOLS 122 - OTHER COMPLEMENTARY ACCESSORIES FOR PROPER OPERATION OF PUMP 123 - INSPECTION AND TESTING 124 - PRESERVATION AND EXPORT BOXING 125 - SUCTION & DISCHARGE LINES PRESSURE GAUGES 126 - DOCUMENTATION 127 128 129 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150

PAGE

11

OF

15

MAIN ELECTRICAL FIRE PUMP DATA SHEET SI UNITS

CONTRACT No. : DOC. No. : PREPARED BY : REVISION

TSM/AL-28/FF-M-31-DL0-001 S.P. 0

DATE CHECKED BY : APPR. BY :

SEP.2008 M.N. S.R.

GENERAL 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
SITE DATA : RELATIVE DENSITY APPLICABLE TO: FOR SITE NO. REQ. MANUFACTURER NOTE:

PROPOSAL
ARDEBIL EXT. G.T.P.P. ARDEBIL ONE
PUMP SIZE

PURCHASE UNIT SERVICE TYPE

AS BUILT

FIRE FIGHTING

PATTERSON

MODEL

CENTRIFUGAL-HORIZONTAL 12x8 MAA TAG NO

INDICATES INFORMATION COMPLETED BY PURCHASER


PURCHASER'S REQUIREMENTS
RAW WATER
NORMAL MAXIMUM MINIMUM

BY MANUFACTURER

12" SIDE FF

BY MANUFACTURER OR PURCHASER

CONSTRUCTION
NOZZLES SUCTION DISCHARGE BALANCE DRUM

LIQUID PUMPING TEMP. (C)

15 45 1 0.1

SIZE LOCATION FACING RATING

8" SIDE FF

0.999 1

@ PUMP TEMP.

150#

150# 27
18

VAPOR PRESSURE @ MAXIMUM TEMP. (bara) VISCOSITY (CENTIPOISE)


3

@ PUMP TEMP.

955 RATED CAPACITY (m / h) 10.0 DISCHARGE PRESSURE (barg) 0.4 / SUCTION PRESSURE (barg) MAX/MIN 100 DIFFERENTIAL HEAD (m) 10 DIFFERENTIAL PRESSURE (bar) 2.169 HEAD LOSS FROM TANK TO PUMP SUCTION (mwc) MINIMUM AVAILABLE STATIC SUCTION HEAD (mwc) 1.4 9. NPSH AVAILABLE@150%RATED CAPACITY(mwc) SITE AND UTILITY DATA
LOCATION : INDOOR NPSHA@ 150% RATED FLOW (mwc): HEATED

HYDRAULIC TEST PRESSURE (barg) DESIGN PRESSURE (barG):

MAXIMUM ALLOWABLE WORKING PRESSURE AT RATED TEMP.(barG): SHUTT-OFF PRESSURE (barG): FLOW RATE / HEAD CURVE SUPPLIED : DRIVER SPEED (rpm) YES

18

11.8

0.05

A02-82834

1470

EFFICIENCY AT RATED CAPACITY : EFFICIENCY AT 150% RATED CAPACITY : MIN. CONTINUOUS FLOW (m3 / h) MAX. SOUND LEVEL 85 dB(REV A) RATED POWER (KW):

81 72
MECHANICAL THERMAL

100 100

*
118 379 7.3

MAX. HEAD WITH RATED IMPELLER (m): MAX. POWER WITH RATED IMPELLER (KW): REQUIRED NPSH AT 150% RATED CAPACITY (m) : COOLING / HEATING PIPING : TUBE MATERIAL

OUTDOOR UNHEATED GRADE MEZZANINE ELECTRICAL AREA CLASSIFICATION


CL GR
'

PARTIAL SIDES
UNDER ROOF DIV SAFE AREA
'

THREADED SEAL WELDED AUXILIARY PIPING:

WINTERIZATION REQ D

TROPICALIZATION REQ D
(mbara)

PIPE FLANGED SOCKET - WELDED MATERIAL

1340 860 (m) BAROMETER ALTITUDE - 37 / 39.5 RANGE OF AMBIENT TEMPS: MIN/MAX 96 RELATIVE HUMIDITY: MAX./MIN. UNUSUAL CONDITIONS (2.1.23) DUST FUMES
CHLORIDE CONTENTS

(C) CASING MOUNTING (%) CENTERLINE NEAR CENTERLINE FOOT VERTICAL

2184 PPM
HEATING (C) (C) CONTROL (barg) (barg) HEATING SHUTDOWN

UTILITY CONDITIONS: DRIVERS (bar) (bar) DRIVERS

STEAM: MIN MAX ELECTRICITY: VOLTAGE HERTZ PHASE

VERTICAL BARREL (C) CASING SPLIT: (C) CASING TYPE SINGLE VOLUTE DIFFUSER IMPELLER MOUNTING: BETWEEN BEARINGS AXIAL

BRACKET IN -LINE

SUMP OTHERS RADIAL

DOUBLE VOLUTE STAGGERED

6.6KV10% 50(-4%,+2%) 3

230 50 1

OVERHUNG

COOLING WATER: TEMP. INLET PRESS. INLET PRESS. RETURN

N/A N/A N/A

(C)

TEMP. RETURN

N/A N/A N/A

(C) (barg) (barg)

DRAIN

VENT

PRESSURE GAUGE

CIRCULATING RELIEF VALVE

(barg) DESIGN (barg) MAX ALLOW DP

1/2"

1/2"

1/2"

1"

PAGE

12

OF

15

MAIN ELECTRICAL FIRE PUMP DATA SHEET SI UNITS


CONSTRUCTION (CONTINUED)

CONTRACT No. : DOC. No. : PREPARED BY : REVISION

TSM/AL-28/FF-M-31-DL0-001 S.P. 0
BARREL / CASE WEAR RINGS SHAFT

DATE CHECKED BY : APPR. BY :

SEP.2009 M.N. S.R. BRONZE


STEEL STEEL

MATERIAL CAST IRON


*
IMPELLER BASE / SKID

49 50
48 51 52 53 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102

NUMBER OF STAGES: BALANCING METHOD: IMPELLER DIAMETER (mm) RATED MIN. MAX.

STAINLESS STEEL(416SS) SLEEVE * *

559 539 584 FLEXIBLE


MFR:

STUFFING BOX BEARING HOUSING REMARKS

TROTTLE BUSHING

54 COUPLING:

TYPE:

WEIGHTS
* STEEL
WEIGHT OF PUMP (kg) WEIGHT OF BASEPLATE (kg) WEIGHT OF MOTOR (kg)

SPACER LENGTH: MATERIAL

1000 500

BASEPLATE

TYPE: GROUTING HOLE:

FABRICATED STEEL

TOTAL WEIGHT (kg)

REMARKS

PUMP LENGTH (m):

SPECIAL DATA FOR VERTICAL PUMPS N/A N/A N/A


THREADED ENCLOSED

MINIMUM SUBMERGENCE (m):

MECHANICAL SEAL OR PACKING

MAXIMUM SUCTION HEIGHT (m): COLUMN PIPE: FLANGED

PACKING:

MANUFACTURER TYPE SIZE / MODEL

SOFT PACKING

LINE SHAFT: OPEN GUIDE BUSHING LUBRICATOR: PUMP THRUST (N) AT MIN. FLOW UP

1/2 Square/5

MECHANICAL SEAL

API CLASS CODE MANUFACTURER SIZE / MODEL

DOWN

GLAND: TYPE / MODEL QUENCH DRAIN MATERIAL:

FLUSH VENT

MANUFACTURER

MOTOR DRIVE ABB/SIEMENS


(KW)

*
HORIZONTAL FRAME SERVICE FACTOR KVOLTS/PHASE/HERTZ ROTATION ENCLOSURE STARTING METHOD LUBE VERTICAL THRUST CAPACITY UP

BRONZE

CLOCKWISE

* 1.0
/

1470

(RPM)

VERTICAL

SEAL FLUSH PIPING PLAN REQUIRED CARBON STEEL TUBE THREADED SEAL WELDED STAINLESS STEEL PIPE FLANGED SOCKET - WELDED

6.6KV10%

/ 50(-4%,+2%)

COUNTER CLOCKWISE

IP 55 DOL GREASE
(N) DOWN (N)

REMARKS

BEARING TYPE 1 RADIAL. BEARING TYPE 2 RADIAL. LUBRICATION TYPE: GREASE OIL MIST FLINGER

BEARINGS AND LUBRICATION * NO.

BEARINGS (TYPE / NUMBER): RADIAL THRUST

NO.

AXIAL

BALL BALL

/ /

AXIAL

PRESSURE SWITCH SET POINTS

RING OIL FLOOD PRESSURE

- PUMP STOP POINT : MANUALLY - PUMP START POINT : DUTY JOCKEY PUMP START POINT MINUS 0.68 bar.g PAINTING

APPLICABLE STANDARDS

ANSI B73.1-1978 UL/FM


TEST

ANSI B73.2-1975

NON -WIT

NFPA-20
WIT

INSPECTION AND TEST


HYDROSTATIC PERFORMANCE NPSH COMPLETE UNIT TEST

POLYURETHANE ,RED COLOR RAL 3001

OTHERS ( PLEASE SPECIFY )

NOTES
*)Information must be given by manufacturer

PAGE

13

OF

15

MAIN ELECTRICAL FIRE PUMP DATA SHEET SI UNITS

CONTRACT No. : DOC. No. : PREPARED BY : REVISION

TSM/AL-28/FF-M-31-DL0-001 S.P. 0

DATE CHECKED BY : APPR. BY :

SEP.2008 M.N. S.R.

GENERAL NOTES

103 1- THE WHOLE PACKAGE SHALL BE FULLY COMPLIANT WITH NFPA-20 . 104 106 CONTROLLER SHALL BE LOCATEED ON THE COMMON ENGINE & PUMP BASEPLATE . 107 3- ONE METERING DEVICE SHALL BE SUPPLIED FOR PUMP CAPACITY IN ACCORDING TO TABLE 2-20 OF NFPA-20 . 108 4- CONTROL PANEL IS FREE STANDING . 109 5- THE NOMINAL POWER OF ELECTRICAL MOTOR IS SELECTED BAISED ON DERATED CALCULATION FOR 42c 109 110 111 6- SCOPE OF SUPPLY INCLUDES : 112 113 - PUMP 114 - MOTOR DRIVER 115 - INTERCONNECTING POWER AND CONTROL WIRING/CABLING BETWEEN ALL EQUIPMENTS WITHIN BASEPLATE/CABINETS 116 - FLEXIBLE COUPLINGS & GUARDS 117 - COMMON BASEPLATE WITH ANCHOR POINTS ,LIFTING POINTS AND EARTH POINTS 118 - COMBINED MANUAL/AUTOMATIC FIRE PUMP CONTROLLER AND CONTROLLER PANEL 119 - GAUGE BOARD (s) 120 - * SIZE CIRCULATING RELIEF VALVE 121 - * SIZE AUTOMATIC AIR RELEASE VALVE 122 - *SIZE METERING DEVICE ON 10" SIZE TEST LINE 123 - SPARE PARTS FOR COMMISSIONING & 2 YEARS 124 - SPECIAL TOOLS ( NOT REQUIRED STATED BY VENDOR ) 125 - OTHER COMPLEMENTARY ACCESSORIES FOR PROPER OPERATION OF PUMP 126 - INSPECTION AND TESTING 127 - PRESERVATION AND EXPORT BOXING 128 - SUCTION & DISCHARGE LINES PRESSURE GAUGES 129 - DOCUMENTATION 130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147 148 149 150

PAGE

14

OF

15

JOCKEY ELECTRICAL PUMP DATA SHEET SI UNITS

CONTRACT No. : DOC. No. : PREPARED BY : REVISION

TSM/AL-28/FF-M-31-DL0-001 S.P. 0

DATE CHECKED BY : APPR. BY :

SEP.2009 M.N. S.R.

GENERAL 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47
SITE DATA : RELATIVE DENSITY APPLICABLE TO: FOR SITE NO. REQ. MANUFACTURER NOTE:

PROPOSAL
ARDEBIL G.T.P.P. ARDEBIL TWO
PUMP SIZE

PURCHASE UNIT SERVICE TYPE MODEL

AS BUILT

FIRE FIGHTING CENTRIFUGAL/VERTICAL


TAG NO.

INDICATES INFORMATION COMPLETED BY PURCHASER


PURCHASER'S REQUIREMENTS
RAW WATER
NORMAL MAXIMUM MINIMUM

BY MANUFACTURER

SIDE RF

BY MANUFACTURER OR PURCHASER

CONSTRUCTION
NOZZLES SUCTION DISCHARGE BALANCE DRUM

LIQUID PUMPING TEMP. (C)

15 40 1 0.1

SIZE LOCATION FACING RATING

DN32

DN25 SIDE RF

0.999 1

@ PUMP TEMP.

150

150

VAPOR PRESSURE @ MAXIMUM TEMP. (bara) VISCOSITY (CENTIPOISE)


3

@ PUMP TEMP.

6 RATED CAPACITY (m / h) 10.0 DISCHARGE PRESSURE (barg) 0.25 / 0.065 SUCTION PRESSURE (barg) MAX/MIN 100 DIFFERENTIAL HEAD (m) 10 DIFFERENTIAL PRESSURE (bar) 1.821 HEAD LOSS FROM TANK TO PUMP SUCTION (mwc) * MINIMUM AVAILABLE STATIC SUCTION HEAD (mwc) * NPSH AVAILABLE@150%RATED CAPACITY(mwc) SITE AND UTILITY DATA
LOCATION :

HYDRAULIC TEST PRESSURE (barg) DESIGN PRESSURE (barG): MAXIMUM ALLOWABLE WORKING PRESSURE AT RATED TEMP.(barG): SHUTT-OFF PRESSURE (barG):

25

15
YES

FLOW RATE / HEAD CURVE SUPPLIED : DRIVER SPEED (rpm) EFFICIENCY AT RATED CAPACITY : EFFICIENCY AT 150% RATED CAPACITY : MIN. CONTINUOUS FLOW (m3 / h) MAX. SOUND LEVEL 85 dB(REV A) RATED POWER (KW):

NO

2950 * *
MECHANICAL THERMAL

*
10 Barg
*

MAX. HEAD WITH RATED IMPELLER (m): MAX. POWER WITH RATED IMPELLER (KW):

INDOOR HEATED OUTDOOR UNHEATED GRADE MEZZANINE ELECTRICAL AREA CLASSIFICATION


CL GR
'

UNDER ROOF PARTIAL SIDES


DIV SAFE AREA
'

REQUIRED NPSH AT 150% RATED CAPACITY (m) : COOLING / HEATING PIPING : TUBE THREADED SEAL WELDED MATERIAL

WINTERIZATION REQ D

TROPICALIZATION REQ D
(mbara)

PIPE FLANGED SOCKET - WELDED MATERIAL

AUXILIARY PIPING:

980 (m) BAROMETER ALTITUDE - 37 39.5 RANGE OF AMBIENT TEMPS: MIN/MAX 96 RELATIVE HUMIDITY: MAX./MIN. UNUSUAL CONDITIONS : DUST FUMES
CHLORIDE CONTENTS

(C) CASING MOUNTING (%) CENTERLINE NEAR CENTERLINE FOOT VERTICAL

(VERTICAL INLINE PUMP)

BRACKET IN -LINE

2184 PPM

UTILITY CONDITIONS: DRIVERS (bar) (bar) DRIVERS CONTROL (C) (C) HEATING (barg) (barg) HEATING SHUTDOWN

AXIAL

SUMP OTHERS RADIAL

STEAM: MIN MAX ELECTRICITY: VOLTAGE HERTZ PHASE

VERTICAL BARREL (C) CASING SPLIT: (C) CASING TYPE SINGLE VOLUTE DIFFUSER IMPELLER MOUNTING: BETWEEN BEARINGS

400V10% 50(-4%,+2%) 3

DOUBLE VOLUTE STAGGERED

OVERHUNG

COOLING WATER : TEMP. INLET PRESS. INLET PRESS. RETURN

N/A N/A N/A

(C)

TEMP. RETURN

N/A N/A N/A

(C) (barg)

DRAIN

VENT

PRESSURE GAUGE

CIRCULATING RELIEF VALVE

(barg) DESIGN (barg) MAX ALLOW DP

(barg) *) Information must be given by manufacturer

PAGE

15

OF

15

JOCKEY ELECTRICAL PUMP DATA SHEET SI UNITS


CONSTRUCTION (CONTINUED)
NUMBER OF STAGES: 48 49 BALANCING METHOD: 50 IMPELLER DIAMETER (mm) RATED 51 MIN. 52 MAX. 53 54 COUPLING: TYPE: 55 56 SPACER LENGTH: 57 MATERIAL 58 59 BASEPLATE TYPE:

CONTRACT No. : DOC. No. : PREPARED BY : REVISION

TSM/AL-28/FF-M-31-DL0-001 S.P. 0
BARREL / CASE WEAR RINGS SHAFT STUFFING BOX BEARING HOUSING REMARKS

DATE CHECKED BY : APPR. BY :

SEP.2009 M.N. S.R.


SS SS

MATERIAL
CAST IRON SS
IMPELLER BASE / SKID SLEEVE TROTTLE BUSHING

MFR: WEIGHT OF PUMP (kg) WEIGHT OF BASEPLATE (kg) WEIGHT OF MOTOR (kg) TOTAL WEIGHT (kg)

WEIGHTS
* * * *

60 61 62 63 64 65 66 67 68 69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101 102 103 104 105 106

GROUTING HOLE: REMARKS

SPECIAL DATA FOR VERTICAL PUMPS


PUMP LENGTH (m): MINIMUM SUBMERGENCE (m):

MECHANICAL SEAL OR PACKING


PACKING: MANUFACTURER TYPE SIZE / MODEL MECHANICAL SEAL API CLASS CODE MANUFACTURER SIZE / MODEL

MAXIMUM SUCTION HEIGHT (m): COLUMN PIPE: FLANGED LINE SHAFT: OPEN GUIDE BUSHING LUBRICATOR: PUMP THRUST (N) AT MIN. FLOW UP DOWN THREADED ENCLOSED

GLAND: TYPE / MODEL QUENCH DRAIN MATERIAL:

FLUSH VENT

MOTOR DRIVE
MANUFACTURER

4
HORIZONTAL FRAME SERVICE FACTOR VOLTS/PHASE/HERTZ ROTATION ENCLOSURE STARTING METHOD LUBE VERTICAL THRUST CAPACITY UP CLOCKWISE

(KW)

400

2890-2910

(RPM)

VERTICAL

SEAL FLUSH PIPING PLAN REQUIRED CARBON STEEL TUBE THREADED SEAL WELDED STAINLESS STEEL PIPE FLANGED SOCKET - WELDED

DIRECT ON LINE
/

3 IP-55

50

COUNTER CLOCKWISE

REMARKS

(N) DOWN

(N)

BEARINGS AND LUBRICATION


BEARING TYPE 1 RADIAL. BEARING TYPE 2 RADIAL. LUBRICATION TYPE: GREASE OIL MIST FLINGER NO.

BEARINGS (TYPE / NUMBER): RADIAL THRUST

BALL BALL

/ /

NO.

AXIAL

AXIAL

PUMP PRESSURE SWITCH SET POINTS


- DUTY PUMP STOP POINT :

RING OIL FLOOD PRESSURE

CHURN PRESSURE + MINIMUM STATIC SUPPLY PRESSURE - DUTY PUMP START POINT : DUTY PUMP STOP POINT MINUS 0.68 bar.g - RESERVE PUMP STOP POINT : CHURN PRESSURE + MINIMUM STATIC SUPPLY PRESSURE - RESERVE PUMP START POINT : DUTY PUMP START POINT MINUS 0.34 bar.g

APPLICABLE STANDARDS

ANSI B73.1-1978 UL/FM

ANSI B73.2-1975 NFPA-20

PAINTING

POLYURETHANE ,RED COLOR RAL 3000

OTHERS ( PLEASE SPECIFY )

INSPECTION AND TEST


TEST HYDROSTATIC PERFORMANCE NPSH COMPLETE UNIT TEST NON -WIT WIT

GENERAL NOTES
1- SUCTION & DISCHARGE LINES PRESSURE GAUGES SHALL BE SUPPLIED . *)Information must be given by manufacturer

Patterson Pump Company Ltd


P. O. Box 72083, Helioupolis 16310, Athens, Greece Tel.: +30 210-965-0511 Fax: +30 210-965-1467

E-mail: pattpump@otenet.gr

6 October 2009 MAPNA Power Plants Construction & Development Co. Tehran, Iran Attention : MR. H. A. GOLSORKHI Contract Manager for Mechanical Systems RRQ-330 ARDEBIL GTPP (Extension Phase)

Our Ref. Project

: :

TECHNICAL CLARIFICATIONS
Dear Mr. Golsorkhi, With regards to your mail of October 5, please see our response below: MAPNA Comments October 5, 2009
1. The curve of pumps shall be submitted as

Patterson Response October 6, 2009


Please see attached curve for Q = 4200 GPM and Q = 2100 GPM. Please note that pumps are UL listed, FM approved for Q = 4000 GPM and Q = 2000 GPM. The derating power for 1340 m is 0.86. Engine site power at 1340 m elevation is : 360 x 0.86 = 310 HP. The max pump power is 280 HP. Each package is provided with 440 gallon fuel tank. One flow meter is provided. One pressure relief valve for each diesel package is provided (total 2 pcs).

per required capacity in data sheets (4200 & 2100 GPM not 4000 & 2000 GPM) and specified operation point on curve.
2. Altitude correction factor for ARDEBIL site

shall be considered in selection of diesel pumps.


3. Fuel daily tank for each diesel pump shall

be considered.
4. Flow meter for test line and relief valve for

diesel pump shall be considered. 5. Below mention tests shall be done under witness: a) Standard Shop Test b) Hydrostatic Test c) Mechanical Running & Performance Test

Provided. Provided. Performance test for all main pumps provided. Mechanical running test is done in the field by our Service Engineer. We can perform mechanical running test for pump with diesel engine and controller at the factory for one hour.

PATTERSON PUMP COMPANY LTD Technical Clarifications 6 October 2009 Our Ref.: RRQ-330 Page 2 of 2

MAPNA Comments October 5, 2009 d) NPSH Performance Test

Patterson Response October 5, 2009


If NPSH A > NPSH R by more than 1 m, the NPSH test is not required. Our pumps have NPSH R 3.5 m and NPSH A is over 7 m and the difference is 3.5 m or more. Therefore, no NPSH test is required. Please note that in order for fire pumps to be UL listed and FM approved, they need to have low NPSH R.

Should you require any further clarifications, please do not hesitate to contact our office. On behalf of PATTERSON PUMP COMPANY LTD Very truly yours,

ARIS GEORGAKIS Regional Sales Manager


vp