SL. NO. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18
DESCRIPTION DG RATING FAULT LEVEL SYSTEM VOLTAGE PRIMARY FAULT CURRENT CT PRIMARY CURRENT CT SECONDARY CURRENT CT RATIO SECONDARY FAULT CURRENT RELAY BURDEN (MAX) MAX LENGTH OF CABLE BETWEEN CT & JUNCTION POINT PHASE SIDE MAX LENGTH OF CABLE BETWEEN CT & JUNCTION POINT NEUTRAL SIDE SIZE OF CABLE RESISTANCE OF CABLE RESISTANCE OF MAIN CT LEAD RESISTANCE PHASE FAULT LEAD RESISTANCE EARTH FAULT 3 PHASE FAULT CURRENT L-L & L-G FAULT CURRENT
SYMBOL
UNITS kVA MVA kV Amps Amps Amps Amps VA km km mm2 Ohms/km Ohms Ohms Ohms Amps Amps Volts % Amps Nos Amps Amps Amps mA Volts Ohms Ohms
DG 2000 11.11 0.415 15458 1600 1.00 1600 9.66 1.0 0.05 0.05 2.50 9.50 3.40 0.95 0.95 15458 15458 84.05 0.30 0.30 5 1113 1335.56 0.83 106.94 42.03 11.11 140.09 1600/1 84 3.40 107 129 P0 04.07.07
TWO DG'S WILL BE COME INTO PICTURE WHEN THERE IS A FAULT B/W REF CT AND BUSBAR
F Vs Ifp Ip Is N Ifs Lp Ln a e RCT Rlp Rle If Ill/Ilg KPV PMS IR (+)m Imax Ieff Ie Vr R1 R2
19 KNEE POINT VOLTAGE 20 RELAY SETTING 21 RELAY SETTING CURRENT NO. OF CTs IN PARALLEL FOR THE PARTICULAR ZONE 22 OF DIFFERENTIAL PROTECTION 23 MAX CURRENT IN ANY CIRCUIT DESIRED EFF. PRIMARY CURRENT SETTING TO 24 OPERATE THE PROTECTION 25 Ieff. SETTING/CT RATIO 26 EXCITATION CURRENT AT 1/2 KPV VALUE MAXIMUM VOLTAGE APPEARING ACROSS RELAY 27 CIRCUIT 28 RELAY IMPEDANCE @ RELAY SETTING CURRENT 29 TOTAL RELAY CIRCUIT IMPEDANCE FINAL CT PARAMETERS: CT RATIO (Ip/Is) KNEE POINT VOLTAGE CT SECONDARY RESISTANCE EXCITATION CURRENT AT 1/2 KPV VALUE STABILISING RESISTOR
KPV RCT Ie Rs
04.07.07