You are on page 1of 34

BUS-BARS FORM A LINK BETWEEN THE INCOMING AND OUTGOING

CIRCUITS AT THE GENERATING STATIONS OR SUB STATIONS. IF A FAULT


DEVELOPS IN THIS PART OF THE POWER SYSTEM, CONSIDERABLE
DAMAGE AND DISRUPTION OF SUPPLY WILL OCCUR. TO REDUCE THE
EFFECT OF FAULT, VARIOUS BUS-BAR ARRANGEMENTS ARE EMPLOYED.
STILL PROPER PROTECTION SCHEME HAS TO BE ADOPTED TO
IMPROVE THE RELIABILITY OF SUPPLY. ALTHOUGH, THE VARIOUS
SCHEMES HAVE BEEN DEVELOPED FOR THE PROTECTION OF BUS-BARS
BUT THE MOST COMMON SCHEME IS DIFFERENTIAL PROTECTION
THE SCHEMATIC DIAGRAM OF CURRENT DIFFERENTIAL PROTECTION
SCHEME EMPLOYED FOR THE PROTECTION OF SUB- STATION BUS-BARS IS
SHOWN IN PREVIOUS SLIDE.
THE SECONDARY'S OF ALL THE CTS CONNECTED IN INCOMING &
OUTGOING FEEDERS ARE CONNECTED IN PARALLEL AS BEFORE. THE CTS
DESIGNED IN SUCH A WAY THAT UNDER NORMAL CONDITION , THE
EMFS INDUCED IN SECONDARYS OF THE CTS PLACED ON OUTGOING
FEEDER. THEN NO CURRENT FLOWS THROUGH THE OPERATING COIL OF
THE RELAY WHICH IS CONNECTED ACROSS THE CONNECTING WIRES.
OPEARTION
UNDER NORMAL CONDITIONAL OR EXTERNAL FAULT CONDITIONS, THE SUM
OF THE CURRENT ENTERING THE BUS BAR IS EQUAL TO THE SUM OF CURRENT
LEAVING IT. THEREFORE, NO CURRENT FLOWS THROUGH THE OPERATING COIL.
HOWEVER, WHEN FAULTS OCCURS WITHIN THE PROTECTED ZONE ( BUS- BAR),
THE CURRENT ENTERING THE BUS-BAR WILL NO LONGER BE EQUAL TO THOSE
LEAVING IT. THUS, A DIFFERENTIAL CURRENT FLOWS THROUGH THE OPERATING
COIL OF THE RELAY WHICH CLOSES THE TRIP CIRCUIT.

HIGH BUS FAULT CURRENTS DUE TO LARGE NUMBER OF CIRCUITS CONNECTED:
CT SATURATION OFTEN BECOMES A PROBLEM AS CTS MAY NOT BE
SUFFICIENTLY RATED FOR WORST FAULT CONDITION CASE
LARGE DYNAMIC FORCES ASSOCIATED WITH BUS FAULTS REQUIRE FAST
CLEARING TIMES IN ORDER TO REDUCE EQUIPMENT DAMAGE
FALSE TRIP BY BUS PROTECTION MAY CREATE SERIOUS PROBLEMS:
SERVICE INTERRUPTION TO A LARGE NUMBER OF CIRCUITS
SYSTEM-WIDE STABILITY PROBLEMS
WITH BOTH DEPENDABILITY AND SECURITY IMPORTANT, PREFERENCE IS ALWAYS
GIVEN TO SECURITY.

INTERLOCKING SCHEMES
OVER-CURRENT (UNRESTRAINED OR UNBIASED) DIFFERENTIAL
OVER-CURRENT PERCENT (RESTRAINED OR BIASED) DIFFERENTIAL
LINEAR COUPLERS
HIGH-IMPEDANCE BUS DIFFERENTIAL SCHEMES
LOW-IMPEDANCE BUS DIFFERENTIAL SCHEMES
BLOCKING SCHEME TYPICALLY USED.
SHORT COORDINATION TIME
REQUIRED .
CARE MUST BE TAKEN WITH
POSSIBLE SATURATION OF FEEDER
CTS.
BLOCKING SIGNAL COULD BE SENT
OVER COMMUNICATIONS PORTS.
TECHNIQUE IS LIMITED TO SIMPLE
ONE-INCOMER DISTRIBUTION BUSES.
50
50 50 50 50 50
B
L
O
C
K
DIFFERENTIAL SIGNAL FORMED BY
SUMMATION OF ALL CURRENTS
FEEDING BUS.
CT RATIO MATCHING MAY BE
REQUIRED.
ON EXTERNAL FAULTS, SATURATED
CTS YIELD SPURIOUS DIFFERENTIAL
CURRENT.
TIME DELAY USED TO COPE WITH CT
SATURATION.
51
Z
C
= 2 20 - typical coil impedance

(5V per 1000Amps => 0.005 @ 60Hz )
59
If = 8000 A
40 V 10 V 10 V 0 V 20 V
2000
A
2000 A 4000
A
0
A
0 V
External
Fault
ESEC= IPRIM*XM - SECONDARY VOLTAGE ON RELAY TERMINALS
IR= IPRIM*XM /(ZR+ZC) MINIMUM OPERATING CURRENT
WHERE,
IPRIM PRIMARY CURRENT IN EACH CIRCUIT
XMLINER COUPLER MUTUAL REACTANCE (5V PER 1000AMPS => 0.005
@ 60HZ ),
ZR RELAY TAP IMPEDANCE
ZC SUM OF ALL LINEAR COUPLER SELF IMPEDANCES
59
If = 8000 A
0 A
0 V 10 V 10 V 0 V 20 V
40 V
2000 A 2000 A 4000 A 0 A
Internal Bus
Fault
FAST, SECURE AND PROVEN.
REQUIRE DEDICATED AIR GAP CTS, WHICH MAY NOT BE USED FOR ANY
OTHER PROTECTION.
CANNOT BE EASILY APPLIED TO RECONFIGURABLE BUSES.
THE SCHEME USES A SIMPLE VOLTAGE DETECTOR IT DOES NOT PROVIDE
BENEFITS OF A MICROPROCESSOR-BASED RELAY .
(E.G. OSCILLOGRAPHY, BREAKER FAILURE PROTECTION, OTHER
FUNCTIONS)
OPERATING SIGNAL CREATED BY
CONNECTING ALL CT SECONDARY'S IN
PARALLEL.
CTS MUST ALL HAVE SAME RATIO.
MUST HAVE DEDICATED CTS
OVERVOLTAGE ELEMENT OPERATES ON
VOLTAGE DEVELOPED ACROSS RESISTOR
CONNECTED IN SECONDARY CIRCUIT.
REQUIRES VARISTORS OR AC SHORTING
RELAYS TO LIMIT ENERGY DURING
FAULTS.
ACCURACY DEPENDENT ON
SECONDARY CIRCUIT RESISTANCE.
USUALLY REQUIRES LARGER CT CABLES
TO REDUCE ERRORS HIGHER COST
CANNOT EASILY BE
APPLIED TO
RECONFIGURABLE
BUSES AND OFFERS NO
ADVANCED
FUNCTIONALITY
59
PERCENT CHARACTERISTIC USED
TO COPE WITH CT SATURATION AND
OTHER ERRORS.
RESTRAINING SIGNAL CAN BE
FORMED IN A NUMBER OF WAYS.
NO DEDICATED CTS NEEDED.
USED FOR PROTECTION OF RE-
CONFIGURABLE BUSES POSSIBLE.
51 87
n DIF
I I I I ...
2 1
n RES
I I I I ...
2 1

n RES
I I I I ..., , , max
2 1

INDIVIDUAL CURRENTS SAMPLED BY PROTECTION AND SUMMATED


DIGITALLY.
CT RATIO MATCHING DONE INTERNALLY (NO AUXILIARY CTS).
DEDICATED CTS NOT NECESSARY.
ADDITIONAL ALGORITHMS IMPROVE SECURITY OF PERCENT
DIFFERENTIAL CHARACTERISTIC DURING CT SATURATION.
DYNAMIC BUS REPLICA ALLOWS APPLICATION TO RECONFIGURABLE
BUSES.

DONE DIGITALLY WITH LOGIC TO ADD/REMOVE CURRENT INPUTS FROM
DIFFERENTIAL COMPUTATION.
SWITCHING OF CT SECONDARY CIRCUITS NOT REQUIRED.
LOW SECONDARY BURDENS.
ADDITIONAL FUNCTIONALITY AVAILABLE.
DIGITAL OSCILLOGRAPHY AND MONITORING OF EACH CIRCUIT
CONNECTED TO BUS ZONE.
TIME-STAMPED EVENT RECORDING.
BREAKER FAILURE PROTECTION.
IMPROVE THE MAIN DIFFERENTIAL ALGORITHM OPERATION.
A) BETTER FILTERING B) FASTER RESPONSE
C) BETTER RESTRAINT TECHNIQUES D)SWITCHING TRANSIENT BLOCKING
PROVIDE DYNAMIC BUS REPLICA FOR RECONFIGURABLE BUS BARS.
DEPENDABLY DETECT CT SATURATION IN A FAST AND RELIABLE MANNER,
ESPECIALLY FOR EXTERNAL FAULTS.
IMPLEMENT ADDITIONAL SECURITY TO THE MAIN DIFFERENTIAL
ALGORITHM TO PREVENT INCORRECT OPERATION.
EXTERNAL FAULTS WITH CT SATURATION.
CT SECONDARY CIRCUIT TROUBLE (E.G. SHORT CIRCUITS).
DATA ACQUISITION UNITS (DAUS)
INSTALLED IN BAYS.
CPU PROCESSES ALL DATA FROM
DAUS.
COMMUNICATIONS BETWEEN DAUS
AND CPU OVER FIBRE USING
PROPRIETARY PROTOCOL.
SAMPLING SYNCHRONISATION
BETWEEN DAUS IS REQUIRED.
PERCEIVED LESS RELIABLE.
DIFFICULT TO APPLY IN RETROFIT APP.
52
DAU
52
DAU
52
DAU
CU
copper
fi ber
ALL CURRENTS APPLIED TO A
SINGLE CENTRAL PROCESSOR
NO COMMUNICATIONS, EXTERNAL
SAMPLING SYNCHRONISATION
NECESSARY
PERCEIVED MORE RELIABLE (LESS
HARDWARE NEEDED)
WELL SUITED TO BOTH NEW AND
RETROFIT APPLICATIONS.
52 52 52
CU
copper
THE CHANCES OF FAULTS OCCURING ON THE FEEDER (TRANSMISSION
LINE) IS MUCH MORE DUE TO THEIR GREAT LENGTH AND EXPOSURE TO
THE ATMOSPHERIC CONDITIONS. THEREFORE, VARIOUS PROTECTION
SCHEMES HAVE BEEN DEVELOPED WHICH MAY BE CLASSIFIED AS:

A) TIME-GRADED OVER CURRENT PROTECTION
B) DIFFERENTIAL PROTECTION
C) DISTANCE PROTECTION
IN TIME GRADED OVER CURRENT PROTECTION SCHEME, THE TIME
SETTING OF RELAY IS SO GRADED THAT IN THE EVENT OF FAULT, THE
SMALLEST POSSIBLE SECTION OF THE SYSTEM POSSIBLE SECTION OF THE
SYSTEM IS ISOLATED. THIS SCHEME IS APPLIED FOR THE PROTECTION OF

(A) RADIAL FEEDERS
(B) PARALLEL FEEDERS
(C) RING MAINS
THE TIME-GRADED PROTECTION FEEDER IS OBTAINED BY EMPLOYING
INVERSE DEFINITE MINIMUM TIME LAG RELAYS. THE RELAYS ARE SO SET
THAT THE MINIMUM TIME OF OPERATION DECREASE FROM THE POWER
STATION TO THE REMOTE SUB-STATION AS SHOWN IN FIG. IN NEXT
SLIDE.

THE OPERATING TIME OF INVERSE DEFINITE MINIMUM TIME LAG
RELAYS IS INVERSELY PROPRTIONAL TO THE OPERATING CURRENT, BUT
IS NEVER LESS THAN THE MINIMUM DEFINITE FOR WHICH IT IS SET.






IF A FAULT OCCURS BETWEEN STATION E AND F, IT WILL BE CLEARED IN 0.1
SECOND BY THE RELAY AND CIRCUIT BREAKER OF SUBSTATION E BECAUSE
ALL OTHER RELAYS HAVE HIGHER OPERATING TIME. IF THE RELAY AT SUB
STATION E FAILS TO TRIP, THE RELAY AT D WILL OPERATE AFTER A TIME
DELAY OF 0.5 SECONDS I.E. AFTER 0.6 SECONDS FROM THE OCCURRENCE
OF FAULT.
WHERE CONTINUITY OF SUPPLY IS ABSOLUTELY NECESSARY, TWO
FEEDERS ARE RUN IN PARALLEL. IF A FAULT OCCURS ON ONE FEEDER, THE
SUPPLY CAN BE MAINTAINED FROM THE OTHER FEEDER, DISCONNECTING
THE FAULTY FEEDER. FOLLOWING FIG. SHOWS THE SYSTEM WHERE TWO
FEEDERS ARE CONNECTED IN PARALLEL BETWEEN GENERATING STATION &
SUB-STATION.
AT THE GENERATING STATION, NON-DIRECTIONAL OVER CURRENT
RELAYS ARE CONNECTED WHEREAS DIRECTIONAL OVER CURRENT
INSTANTANEOUS RELAYS ARE CONNECTED AT SUB-STATION END.
IF AN EARTH FAULT OCCURS ON FEEDERS AT POINT F AS SHOWN IN FIG. THE
FAULT IS FED;
(A) DIRECTLY FROM FEEDER 2 VIA RELAY B.
(B) FROM FEEDER I VIA A , P AND SUB-STATION Q AS SHOWN IN FIG. BY THE
DOTTED ARROWS.
THIS CLEARLY SHOWS THAT DIRECTIONAL RELAY P CARRIES THE CURRENT IN
NORMAL DIRECTION WHERE AS DIRECTIONAL RELAY Q CARRIES THE
CURRENT IN REVERSE DIRECTION MOMENTARILY. THIS OPEARATES THE
RELAY Q INTANTANEOUSLY. THE RELAY B HAVING INVERSE TIME
CHARACTERISTICS ALSO OPERATES BECAUSE OF HEAVY FLOW OF CURRENT .
THE SYSTEM IN WHICH VARIOUS POWER STATIONS OR SUB-STATIONS ARE
INTER-CONNECTED BY THE NUMBER OF FEEDERS FORMING A CLOSED
CIRCUIT IS CALLED A RING- MAIN SYSTEM.

IN THIS SYSTEM OF PROTECTION, NON-DIRECTIONAL OVER CURRENT
RELAYS HAVING INVERSE TIME CHARACTERISTIC ARE EMPLOYED. WHEREAS
DIRECTIONAL OR REVERSE POWER ARE EMPLOYED ON BOTH THE SIDES OF
EACH SUBSTATION. THE MINIMUM DEFINITE TIME OF ALL THE RELAY ARE
SET PROPERLY AS SHOWN IN FIG.
WHENEVER THE FAULT OCCURS ON ANY OF THE SECTION ONLY
CORRESPONDING RELAYS WILL OPERATE WITHOUT DISTURBING THE OTHER
RELAYS OF THE NETWORK, THUS, THE FAULTY SECTION IS ISOLATED AND
SUPPLY IS MAINTAIN.
THE TRANSLATION SCHEME IS BASICALLY A VOLTAGE BALANCE
DIFFERENTIAL PROTECTION SCHEME. BUT IN THIS SCHEME, VOLTAGES
INDUCED IN THE SECONDARY WINDINGS WOUND ON THE RELAY
MAGNETS IS COMPARED IN PLACE OF SECONDARY VOLTAGES OF THE
LINE CURRENT TRANSFORMERS.

THE SCHEMATIC DIAGRAM OF A TRANLEY SCHEME FOR THE
PROTECTION OF 3-PHASE FEEDER IS SHOWN IN FIG . ON NEXT SLIDE.
THE RELAYS USED IN THE SCHEME ARE ESSENTIALLY OVERCURRENT
INDUCTION TYPE RELAYS.
THE CENTRAL LIMB OF THE UPPER MAGNET (U.M.) CARRIES A WINDING (A
OR A) WHICH IS ENERGISED BY THE SUM OF SECONDARY CURRENTS OF
CTS PLACED ON FEEDER TO BE PROTECTED.
THE CENTRAL LIMBS OF UPPER MAGNET ALSO CARRIES A SECONDARY
WINDING (B OR B) WHICH IS CONNECTED IN SERIES WITH THE
OPERATING WINDING (C OR C) PLACED ON THE LOWER MAGNETS
(L.M). IN BETWEEN THE TWO MAGNETS, AN ALUMINIUM DISC D IS
PLACED WHICH IS FREE TO ROTATE. SPINDLE OF DISC CARRIES MOVING
CONTACT WHICH CLOSES TRIP CIRCUIT UNDER FAULT CONDITIONS.
UNDER NORMAL CONDITIONS, THE CURRENTS AT TWO ENDS OF THE
FEEDER ARE EQUAL SO THAT THE SECONDARY CURRENT IN BOTH SETS
OF CTS ARE EQUAL. CONSEQUENTLY, THE E.M.FS INDUCED IN THE
SECONDARY WINDINGS C AND C ARE EQUAL AND OPPOSITE AND NO
CURRENT FLOWS THROUGH THE CLOSED CIRCUITED SECONDARIES.
HOWEVER, WHEN FAULT OCCURS ON FEEDER SYSTEM SAY AT POINT F
THE VOLTAGE INDUCED IN C AND C WILL NO LONGER REMAIN EQUAL.
THEREFORE, CURRENT FLOWS THROUGH THIS WINDING AND TORQUE
IS DEVEOLPED IN THE DISC.

You might also like