You are on page 1of 5

Calculate Size of Transformer and Voltage drop due to St

:Transformer Detail:
Transformer Size
Transformer Secondary Voltage:(v2)
% Impedance: (z)
Allowable Voltage Drop in System:
:Motor Detail ( Only One No of Motor):
Motor Size:
Volt (vm): (L-L)
Power Factor:
Motor KVA
Motor Code: (Kva/Hp)
InRush Current at Starting:(Enter If you know otherwise leave it blank)
Enter Motor Full Load Current(Enter If you know otherwise leave it blank )
Motor Full Load Current: (ILM)
Locaked Rotor Current Multiplier: (Min)
Locaked Rotor Current Multiplier: (Max)
Locaked Rotor Current (L1): (Min)
Locaked Rotor Current (L2): (Max)
Motor InRush KVA At Starting: (IrsM)
How many times Motor Starts per Hours
:Calculations:
Full Load Current of Transformer : (ILX)
Short Circuit Current at Transformer Secondary: (Isc)
Max KVA of Transformer at Isc: Q1
Motor InRush KVA At Starting:(IrsM)
Voltage Drop at Transformer Secondary Due to Motor inRush: (Vd)
Transformer Secondary Voltage
:Result:
(1) Motor Full Load Current <= 65% Transformer Full Load Current
(2) Voltage Drop at Transformer Secondary Due to Motor inRush
(3) Transformer Size:(20% Added due to motor starts more than once/Hour)

1000
480
5.75%
10%
300
460
0.8
240

471
4.10
4.50
1930
2118
1688
2
1203
20919
17391
1688
10%
433
Yes
Low
1200

Size of Transformer is Adequate


Calculation Formulas:
ILX=KVA/(1.732xv2)
ILM=(Kwx1000)/(1.732xVmxP.F)
Isc=ILx/z
Q1=(v2xISCxILMx1.732)/1000
IrsM=(VmxL2x1.732)/1000
Vd=IrsM/Q1

1
2
3

Code Letter (KVA per HP) -Locked Rotor Current


Motor Code
A
B
C

Min
3.15
3.16
3.56

4
5
6
7
8
9
#
#
#
#
#
#
#
#
#
#

4.1
4.6
5.1
5.7
6.4
7.2
8.1
9.1
10.1
11.3
12.6
14.1
16.1
18.1
20.1
22.5

D
E
F
G
H
J
K
L
M
N
P
R
S
T
U
V

4
4.1
4.5

age drop due to Starting of Large size Motor


KVA
Volt

Kw
Volt
KVA

Amp

:Transformer Detail:
Transformer Size
Transformer Secondary Voltage:(v2)
% Impedance: (z)
Allowable Voltage Drop in System:
:Motors Detail ( More Than One No of Motor):
Total KW of Three Phase Motors:
Total KW of Single Phase Motors:
Volt: (L-L)
Volt: (L-N)
Power Factor:
Locaked Rotor Current: (Max)
Total Three Phase Motors Full Load Current
Total Single Phase Motors Full Load Current
Total Motors Full Load Current
Motor InRush KVA At Starting

Jignesh.Parmar
www.electricalnotes.wordpress.com

1000
480
5.75%
10%
300
5
460
266
0.8
450%
471
24
494
1772

Amp
Amp
KVA

Amp
Amp
KVA
KVA
90%
Volt

Kva

:Calculations:
Full Load Current of Transformer : (IL)
Short Circuit Current at Transformer Secondary: (Isc)
Max KVA of Transformer at Isc
Motor InRush KVA At Starting
Voltage Drop at Transformer Secondary Due to Motor inRush
Transformer Secondary Voltage
:Result:
(1) Motor Full Load Current <= 65% Transformer Full Load Current
(2) Voltage Drop at Transformer Secondary Due to Motor inRush
(3) Transformer Size:

Increase Size of Transformer

Max
3.55
4

1203
20919
17391
1772
10.2%
431
Yes
High
1000

4.5
5
5.6
6.3
7.1
8
9
10
11.2
12.5
14
16
18
20
22.4

Jignesh.Parmar
w.electricalnotes.wordpress.com

KVA
Volt

Kw
Kw
Volt
Volt

Amp
Amp
Amp
KVA

Amp
Amp
KVA
KVA
90%
Volt

KVA