Professional Documents
Culture Documents
Electrical Data
Electrical Data
Introduction:-
Data on the Electrical System are the most useful tool for the Electrical engineers to know
the limit of their working arena. According to the limitation of Data, proper planning, estimation and
confirmation regarding the equipments can be achieved. Basically the practice Engineer are very
cautious regarding the value of threshold on the Electrical Parameters, upon the field works on the
Equipments on which they work to obtain the efficiency of the assigned project. Many a times they
get confused to land upon a decisive conclusion; due to the non-availability of ready reckon electrical
data. This chapter has covered all the possible zones of electrical field topics with some reference data
in concise manner. The reference tips on the maintenance schedule, testing methods, installation
practice and commissioning patterns can help the Electrical Engineers to acquaint themselves and
develop a healthy environment by refining their practice towards the field works.
2.
PURPOSE
LETTERS
M
CT Secondary
PURPOSE
Motor Control
Circuit
Circuit special
B
Protection AC
Transformer Tap
Changer
Circuit (CT )
Control Circuit
Metering Circuit
Marking of Sec.
PT Secondary
CT Polarity
LT AC Supply
DC Main Circuit
wires
X
etc
L
Alarm, Indication,
Annunciation
Circuit
2.1
FUCTION /DEFINITION
Master Element
Time Delay Starting or Closing Relay
Checking or Inter locking Relay
Master Contactor
Reversing Device
Over Speed Device
Synchronous- Speed Device
Under Speed Device
Electric Operated Device
Distance Protection Relay
Equalizer Circuit Breaker
CODE
NO.
23
25
26
27
29
30
34
37
40
43
47
49
50/50N
51/51N
52
52a/52b
53
54
55
57
59
60
61
63
64
65
67/67N
68
69
72
74
76
78
79
80
81
83
85
86
87
88
89
90
91
92
94
95
96
FUCTION /DEFINITION
Temp. Control Device
Synchronism Check Device
Apparatus Thermal Device
Under voltage Relay
Isolator Contactors
Annunciation Relays
Motor Operated Sequence Switch.
Under Power Relay
Field Failure Relay
Manual Transfer Selector Switch
Phase Sequence Voltage Relay
Thermal Relays (Machine/ Transformer)
Instant O/C Relay/ Instant E/F Relay
AC Time Delay O/C Relay/ E/F Relay
AC Circuit Breaker
CB Aux. Switch N/O, CB Aux. Switch N/C
Exciter of DC Generator Relay
High Speed DC Circuit Breaker
Power Factor Relay
Short Circuiting Or Ground Device
Over Voltage Relay
Voltage Relay
Current balance Relay
Liquid- Gas pressure level Relay (Buch.)
REF Protective Relay
Governor
AC Directional O/C Relay / E/F Relay
Blocking Relay
Permissive Control Device
DC Circuit Breaker
Alarm Relay
Dc O/C Relay
Phase Angle Measure/ OUT of Step Protn.
AC Reclosing Relay
DC Fail Supervision Relay
Frequency Relay
Automatic Sel. Control / Transfer Relay
Carrier or Pilot wire Receive Relay
Master Relay (Locking out Relay)
Differential Protective Relay
Aux. Motor or Motor Generator
Line Switch (Isolator)
Regulating Device
Voltage Directional Relay
Power Dir. Relay
Tripping or Trip free Relay
Trip Circuit Supervision Relay
Tripping Relay
2.2
SYMBOLS USED
SL.
No
Symbols
1.
Meanings
Over Current
Over Voltage
Under Voltage
Distance Relay
Over Frequency
Under Frequency
T
Over Temp.
Balanced Phase
X
10
Pilot Wire
PW
11
Dirr. O/C
Z
12
Dir. Distance
CC
13
Carrier Pilot
O/c Ground with
Instant Element
14
I
15
16
B X
2.4.
Meanings
Protection
relay
Protection
relay with
enable input
*
EN
*
EN
Protection
relay with
blocking input
Symbols
3I>
Meanings
EN
Z<
Relay with mechanical
contracts (Auto reset
Meanings
Reverse current
Symbols
I
Meanings
Drop out delay
Id
Differential current
Inf
Step
I2 , In
Current of nth
Harmonic
Positive sequence
current
- Xe sequence current
I0 , Ip
Residual current
I1 , Ip
Irsd
LO
Lockout
TCS
Id
IN-N
Current to frame
IN
Iub
Thermal effect by
current
Voltage
X/Y
Translation of signal
>
<
>
<
Active power
Reactive power
Temperature
Thermal effect
Delay
P.T, V.T
Push button (Normally close )
Isolator
Fuse
Breaker
C.T.
CVT
Wave trap
Note: For study of drawing, the index, legends etc. are to be referred always
INTERNAL CIRCUIT
TB
PURPOSE
X11 CT Circuit
X12 PT Circuit
X13 DC Supply
X14 Control Circuit
X15 AC Supply
X17 Annunciation,
AlarmCircuit
17
25
37
1
2
3
101
325
137
3.
INITIATION OF RELAYS
32
G
INTERMEDIATE
AUX. RELAY
ACTION OF CIRCUIT
BREAKER
Trip Gen. CB
&
87G
87GT
87UAT
64G1
64G2
59G
99GT
64REF
51UAT
50UAT
64R II STAGE
Rotor Over Voltage
Excite Transf. O/C
Buch. PRDS
GT1,UAT1
Class A Trip
Relay 86G
Trip Field. CB
Trip Turbine
Trip UAT BkrA
Trip UAT BkrB
Initiate 6.6 KV CB
Initiate LBB
Arm- Reheater Protection
Block Closing of Gen. CB
Block Field CB
ACTION OF
CIRCUIT
BREAKER
46G
40G
21GB (II STAGE )
81
TRIP TURBINE
GCB (OPEN)
STATER CONDN. HIGH
WATER FLOW LOW
TRIP UAT CB
Initiate 6.6 KV CB
THYRISTOR COOLING
FAN SUPPLY FAIL
FCB CLOSE
ARM.REHEATER
PROTECTION
WINDING
INTERMEDIATE
AUX. RELAY
ACTION OF
CIRCUIT BREAKER
TRIP GEN. CB
H.P/L.P BYPASS FAST
OPN.
Class C Trip
Relay
86 GB
INITIATE LBB
3.2.4
Generator Size
Protection
I
04
MVA
II
4 15
MVA
III
15 50 MVA
IV
50 200
MVA
Rotor
Overload
X
X
X
X
Rotor E/F
4
X
4
X
4
X
Inter turn
Fault
X
X
X
Differential
Generator
X
X
X
Diff. Block
Transformer
3
X
3
X
3
X
Under
frequency
X
X
X
X
Over Voltage
X
X
X
X
Stator E/F
X
X
X
Loss of
Excitation
X
Pole- Slip (Out
of Step)
1
X
5
X
5
X
5
Reverse Power X
X
2
X
Under
Impendence
X
7
X
7
X
Unbalance
(I2 Current)
X
6
X
6
Over Current
(Definite Time)
Stator Over
Load
6
X
6
Over Current / X
Under Voltage
X
X
Dead Machine
X
X
Breaker
Failure
Note: - 1- Only necessary for Steam and Diesel Drives
2. Only necessary for Thyristor excitation from Generator terminals
3. Only necessary for Pump operation.
4. Only necessary for when several Bars of the same phase in the same slot
5. Not necessary for PELTON turbines
6. O/ C should not be used with self supported static excitation system
7. When unbalance load is expected
8. X- Required
V
Large Turbo
Alternator
X
X
X
X
X
4
X
X
X
X
X
X
X
X
X
3.2.4
TURBINE
PROTECTION
Protection System Power
Failure
Low Condenser vacuum
(2 Channels)
GENERATOR
PROTECTION
Generator Differential
Protection
Overall Differential
protection
8
9
10
11
12
13
Loss of 220 V DC
14
15
16
17
18
19
During starting
During running
7 Loss of load
8 Under voltage protection
3.4 TRANSFORMER PROTECTION
3.4.1 Requirement of relays
CAPACIT
BACK UP
GAS
Y OF
OPERA
TRANSFO
TED
RMER
RELAY
UP TO 5
MVA
5 to 12.5
MVA
ABOVE
12.5 MVA
AUTO
TRANS.
3
O/
C
2
O/
C
E/F
R
R
Dir.
R
Dir.
Inst.
TEM DIF
P
F
PRO REL
TEC AY
TION
O P O W
S R T TI
R V I
RE
F
RE
LA
Y
NEUT.
DISPL
RELA
Y
NEUT.
O/C
OVE
R
FLU
X
RELA
Y
B
U
C
H
R O - R
R O R
R
Dir.
R
Dir.
Inst.
R R R
R R R R
3.4.2
3.4.3
BUCHHOLTZ RELAY
3.4.3.1 Data:
1) Works on principal of BUOYANCY of liquid.
2) Position on pipe bent tank and conservator
3) Angle of inclination of pipe with horizontal 5 to 10
4) Length of straight run pipe section
(I) Transformer to relay = 5D (min)
(II) Relay to conservator = 3D ( min )
D : Dia of pipe
5) Vertical position of relay from tank = 8 cm ( min )
6) Gas volume for Alarm operation
Trans. Size
Upto 1 MVA
1 to 10 MVA
10MVA and
above
Pipe
dia
2.5 cm
5 cm
7.5 cm
Setting range
Normal setting
100 - 120cc
185 - 250cc
220 - 280cc
110cc
220cc
250cc
8)
Colour
Grey
White
/Milky
Black
Yellow
3.4.4
PRV
Gas of
decomposed
paper and cloth
insulation
Gas of
decomposed
wood insulation
Identification
Gas of overheated oil
due to burn of iron
Gas of decomposed
oil due to elect. Arc.
3.4.4.1 Data: 1 required / Universal for nitrogen cushioned transformer and optional for conservator
type transformer
3.4.4.2
3.4.4.3
3.4.5
3.4.5.1
3.4.5.2
OA, OW
OA / FA
OA / FA / FOA
FOA
FOW
3.4.6
Winding temp
rise on F.L.
condition
55C
55C
50C
3.4.6 .1
DATA: 1 Bellow (Bourdon tube) and shunt network, being connected to WCT (Winding
Ct), simulates the temp. Gradient, (proportionate with load current) and provides
reading on the scale.
3.4.6.2
3.4.6.3
2 Amps
= (2.5 0.1)
at 30C
RESISTANCE
0
10
20
30
40
50
60
70
80
90
100
110
120
130
140
150
100.00
103.90
107.79
111.67
115.54
119.40
123.24
127.07
130.89
134.70
138.50
142.29
146.06
149.82
153.58
157.31
Breaker Close
Operation
Pole
Discrepancy
PDR Operation
Time
Tripping
Contact
Margin
( 2)
(3)
Margin
(4)
(5)
Margin
Breaker
Fail Relay Starts
Total Clearing time of LBB Relay
Maxim. Fault clearing time before system Instability
(1)
(2)
(3)
(4)
(5)
3.6.
BUS PROTECTION
1
2
3.7.
LINE PROTECTION
1
2
2nd. Method
For available of the following data zone selection standard should be as follows
a3 = 0.85 ( a + k b2)
a2 = 0.85 ( a + k b1)
a1 = 0.85 a
b1
b2
A
NOTE
3. 7.1.2
220 kV
132 kV
100 ms
150 ms
Zone
Zone 1
Zone 2
Zone 3
Reverse
Zone
Time
Instant Relay
operation time ( 30
to 40 mS )
0.2 to 0.5 S
0.4 to 1 S
1 to 2 S
66
110
132
Minimum
DeEnergisation
Time in Sec.
0.1
0.15
0.17
Line KV
Minimum DeEnergisation
Time in Sec.
220
275
400
0.28
0.3
0.5
Line
Voltage
in KV
33
132
220
400
Length
Ra (Arc
In Mtr Resistance)
Ohm
1.22
3.66
6.7
8.3
2.5
8.6
12.8
18
3. 7.1.7
3. 7.1.8
3.7.1.8.1
Line Voltage
132kv Panther
220kv Zebra
400kv Twin
Moose
R
ohm/
ph/km
0.151
0.078
0.031
X
ohm/
ph/km
0.401
0.402
0.327
Yc
mho/ph/km
1.43
1.44
1.73
3.7.1.8.2
1
#R1 = l /a ohm/ph/km
# R1 -+ve Sequence Resistance
(Usually given in conductor data)
X1 = 2 f x 2 x 10 4 ln (Dm / Ds) ohm /ph/km
X1 = +ve seq. reactance
Dm = Mutual Geometric Mean Distance
= (Dmab x Dmbc x Dmca) 1/ 3
Dmab = Mutual GMD between 'A' and 'B' conductor of the Line
Dmbc = conductor between 'B' and 'C'
Dmca = Between 'C' and 'A' conductors
Ds = Self GMD
Note: - For Double circuit loop reactance = 2 X 1
Ro = Zero sequence resistance
= ( R1+ 0.00477f /1.609) ohm/ph/km
Z L =(U / MVA)
Where U = Line to Line voltage,
MVA = Maximum permitted load
= (Umin. / 3 I max.)
3.7.1.8.4 Conversion to secondary value
Z Sec = Z pri x C.T.R
P.T.R
Base
=
P.U x KV
impedance value 100
3.7.1.8.5 Zero seq. compensation factor (KN)
i. KN = (Zo Z1) / 3Z1, When mutual zero seq. impedance is not considered.
= (Xo X1 ) / 3X1 ,
ii. K 0 angle = Tan- (Xo - X1) / (Ro - R1) --Tan- (X1) / R1
iii. KNP = (Xo +Xom - X1 ) / 3X1 ,
iv. KNG = (Xo - Xom - XoX1 ) / 3XoX1 For parallel system is out of service and
grounded at both ends.
3.7.1.10
Possible length in
KM
Length
Line
Minimum
Max.
40
120
50
140
50
160
80
180
100
300
3.7.1.10.1 1st Method: Minimum voltage at relay: S.I.R: - System Impedance Ratio
= Source Impedance
Relay setting impedance
C.I.R: -Characteristics Impedance Ratio
= Maximum value of system impedance ratio
=E-V
V
E - P.T. Secondary voltage
V - Minimum voltage at relay
Zs =(KV ) / (MVA) Fault/source = Source impedance
IF = KV
for 3 fault current
3 (Zs +ZL)
ZL = Line Impedance
Vrelay = E/ (1+Zs / ZL)
3.7.1.10.2
2nd Method: -
ii. Ph - Ph fault
Vrelay = ( 3 ZL x I F) / PTR OR VT Ratio
ii.
Ph - Earth fault
Vrelay = (IF x Zre) / VT ratio
Zre - Earth loop impedance = ZL1 (1 + (K-1)/3)
Where K = ZLo / ZL1,
ZLo = Zero sequence impedance,
ZL1 = +re sequence impedance
3.7.1.11
2 During PS
3.7.2
( Z/
t)
Slow
3.7.2.1
TYPE
K
0.14
13.5
80
120
C
0.02
1.0
2.0
1.0
Operating
current
(Multiple of
plug
setting)
2
5
10
20
24.15
15.98
15.08
15.00
2.42
16.65
1.67
0.69
8.48
0.36
0.45
7.58
0.23
0.33
7.5
0.17
3. 7.2.5
Relay
connecti
on angle
30
60 Type
1
60 Type
2
90
90
MTA
Connection
Bph
Cph
Current
Voltage Current Voltage
coil
coil
coil
coil
Ib
Vba
Ic
Vcb
Ibc
Vba
Ica
Vcb
Aph
Current Voltage
coil
coil
Ia
Vac
Iab
Vac
0
0
0
Ia
- Vc
Ib
- Va
Ic
- Vb
30 Lead
45 Lead
Ia
Ia
Vbc
Vbc
Ib
Ib
Vca
Vca
Ic
Ic
Vab
Vab
Relay
characteristic
angle
12.5 (lag)
14 (lag)
45 (lag)
60 (lag)
Connection
Current coil
Voltage coil
Residual
Current
I0 = IA + IB
+ IC
Residual Voltage
= Open Delta Secondary
Voltage
Sl
No
Model
Standard
MVAA23
Two
unit/Case
MCAG34
THREE/Case
MCAG14
Single
unit/Case
CONTACTS
Alar Trip
m
2315-17
25
1-3
9-11
2-4
1-3
2-4
1-3
Current
Terminal
23-24,
25-26,2728 #
27-28
Voltage
Termin
al
13-14
27-28
Aux.
DC
220-250V
# 24-26-28
SHOTRTE
D
MCGG22
MCGG62
MBCH12
MVAP22
MCVG62
25-23-21
MWTU11
27-28
10
MCND04
11
12
13
MYTU04
MVTU12
MCSU
Single
unit/Case
THREE/Case
Single
Unit/Case
6-7
8-10
3637
3335
9-11
1-2
15-16
29-30
41-42
1-3
2-4
7-9
1820
7-9
4-16
4-6
27-28
13-14
21-22
23-24, 2526 #
13- 14
# 22-24-26
SHORTED
23-25-27
23-2527
Short
37&42,
41&46,
38&45
25-2321
13-14
6-8
13-14
27-28
1-3
27-28
13-14
Type
ER
IDMT NONDIR
TJM10,
2TJM10,
TJM20, TJM11,
2TJM10,
TJM21
ER
IDMT DIR.
TJM12,
2TJM12,
TJM22
Standard
Single
unit/Case
Multi
unit/Case
3O/C
Multi
unit/Case
2O/C, E/F
Single
unit/Case
O/C
Single
unit/Case
E/F
Alar
Trip
Current
m
Terminal
Nor Inst
mal ant
1,2
3,4 11,1
9,10
2
1,2
3,4 11,1 (5,6-R), (7,82
Y),
(9,10-B)
1,2
3,4 11,1 (5,6-R), (7,82
E/F), (9,10-B)
Volt
age
Aux.
DC
5,6
1,2
3,4
11,1
2
9,10
5,6
1,2
3,4
11,1
2
9,10
5,6
3,4
9,10
Single
unit/Case
E/F
1,2
ER
ER
IDMTL
PROGRAMME Multi
DCD, MIT
unit/Case
1,2
3,4
3,4
IDMT NONDIR
CDG11,
12,13,14
IDMT NONDIR
CDG31,
32,33,34
CDG61, 62
Single
unit/Case
1,2
3,4
3,6
(5,6-R),
( 7,8-Y),(9,10B),
(11,12-E/F)
9,10
Multi
unit/Case
3O/C
Multi
unit/Case
2O/C, E/F
Single
unit/Case
1,2
3,4
3,12
OR20
1,2
3,4
(5,6-R),( 7,8Y),
(9,10-B)
(5,6-R), (7,8E/F), (9,10-B)
1,2
3,4
9,10
7,8
3,
12
OR20
3,6
OR 20
1,2
3,4
3,17
19,20
30V DC
1,2
3,4
9,10
11,1
2
13,1
4
20,19
9,10
1,2
5,6
11,1
2
7,8
1,2
3,4
9,10
1,2
7,8
1,4
EE
ALSTOM
EE
ALSTOM
EE
ALSTOM
EE
ALSTOM
EE
ALSTOM
JVS
JYOTI
ABB
UE
IDMT DIR
CDD 21, 23,
24,26
CDD
31,33,34,36
DEF. TIME
Multi
DELAY
element/C
CTU32
ase
INSTANT
Single
CAG11,
unit/Case
12,13,14, 17, 19
IDMT NONMulti
DIR
element/C
JRC053
ase
IDMT NONDIR
IDMT NONDIR ICM21P
IDMT NONDIR
R-1156
Single
unit/Case
Single
unit/Case
Single
unit/Case
3,8
ER
4C21
B
10
r
9
13
13
17,18
3,4
6
1
4
7
18
8
10
3 4
11 15
5
7
1+1
4+4
11+11
During Test both HT & LT
Terminals to be shorted (Ex.
1+1)
12
13
14
12
16
8
1,2
3,4
17
27
10 20
30
8 or 9
Short
(8 +9)
Single unit /
Case
Multi unit /
Case
Single unit /
Case
1,2
3,4
10
10
1,2
3,4
1
0
5
18
13
10 20
9, 11
1,3
2
5
25
25
-do-
9,11
1,3
2
5
25
25
RADSB
DTH31
-do-do-
15, 16
1,2
DTH32
-do-
DDT
3,4
Module 2 (RL1,
RL2) General
Command
DDT
MBCH 12 (2
Winding
MBCH 13 (3
Winding
R0
Y0
Aux. Volt
DC
Trip
Alarm
Y
10
1,2
EE
ALS
TOM
EE
ALS
TOM
CURRENT TERMINALS
LT Side
Operating Point
(BIAS)
HT Side
(COMMON)
R
1
0
3
Single unit /
Case
Multi unit /
Case
DUO-BIAS M
ABB
Standard
Type
Make
B0
7
28 or 29
Short
(28 +29)
18 or 19
Short
(18 +
19)
7
11
16
14
23 23
23
27
27
Short (24 +26 +28)
27
23 23
or or
21 21
23
or
21
27
27
27
220 V
DC
1,2
5- 110 V
6- 220 V
19- 30V
20 - --ve
11- 30 V
13- 110 V
15220 V
12 - - ve
3- + ve
8 --- ve
3- + ve
8 --- ve
13- + ve
14 -- ve
220 V
13- + ve
14 --- ve
220 V
Particulars
TECHNICAL PARTICULARS
33KV
132KV
220KV
Vacuum,
Oil
Operating medium
Spring
4
5
36
50
145
50
Oil,
Air blast
SF6
Spring
Hydraulic
Air pressure
400KV
245
50
420
50
SF6 (Puffer)
Air blast
Spring
Hydraulic
Air pressure
Air
Pressure
Insulation standard
170
650
1050
1425
70
275
460
520
28
1250
105
1250/1600
176
2000
320
2000/3150
25
40
40
40
70
25
100
40
100
40
100
40
6.5
10
10
10
50
50
125
400
3.0
3.0
3.0
3.0
O-10s-CO-3min-CO
O-0.3s-CO-3min-CO
1.5
1.5
1.3
1.3
60
100
50
150
50
150
40
120
80
80
60
3.3
3.3
3.3
Rating /
Value
Make
Rated Lightening 650 KVp
impulse with
Stand voltage
Type
Rated short
31.5 KA
Circuit Breaking
Current
Rated Voltage
145 KV
Rated Operating 15.5
pressure
KG/cm2 g
Rated Frequency 50 HZ
First pole to
1.5
Clear factor
Rated Normal
3150 A
Rated Duration
31.5 KA
Current
of short Circuit
3 Sec
current
Rated Closing
220 V DC
Rated Line
50 A
Voltage
Charging
Breaking Current
Rated SF6 Gas
pressure
Rated Opening
220V DC
Rated Voltage
415 VAC
Voltage
and frequency
50 HZ
for Aux. Circuit
GAS
6.0 bar at 20 Rated operating
0-0.3SPRESSURE SF6 0 c
Sequence
CO3Min-CO
Total weight
2000 KG
Gas weight
9 KG
with Gas
Sl. No.
11583C
STD. IEC
56
Month / Year of MARCH./
Manufacturing
99
4..2.2
Rating /
Value
Crompton
Greaves Ltd.
Nasik
120-SFM-32
A
Particulars
Rating /
Value
1050
KVp
40 KA
21..5
pressure
4. 2.3
Rated Frequency
50 HZ
First pole to
Clear factor
Rated Duration
of short Circuit
current
Rated Line
Charging
Breaking Current
Rated SF6
pressure
Rated Voltage
and frequency
for Aux. Circuit
Rated Normal
Current
2000 A
Rated Closing
Voltage
220 V DC
Rated Opening
Voltage
220V DC
GAS
PRESSURE SF6
7.0 bar at
20 0 c
Rated operating
Sequence
Total weight
with Gas
Month / Year of
Mang
3800 KG
Sl. No.
KG/cm2 g
1.3
40 KA
3 Sec
125 A
1-PH
(230V &
3 PH
415 VAC
50 HZ
0-0.3SCO3Min-CO
307786
MARCH./
99
Rating /
Value
BHEL
Type
PVN 36
Rated Voltage
36 KV
Rated Frequency 50 HZ
Rated Normal
Current
1250 A
220 V DC
Spring REL.
Coil
Rated operating
Sequence
Sl. No.
220 V DC
0.3 Min. CO
9087652
Particulars
impulse with
Stand voltage
Short Time
Current
Rated Air
pressure
Making
Capacity
Sym. Breaking
Capacity with
Dur.
P.F With stand
V
Spec.
Month / Year of
Manufacturing
TOTAL
WEIGHT
Rating /
Value
170 KVp
25 KA
62.5 KAp
25 KA for
3 Sec
70 KV
IS 2156/
IEC 56
April/1991
1000 KG
4.2.
CURRENT TRANSFORMER
4.2.1. SPECIFICATIONS
RATIO OF THE CT
NUMBER OF
CORES
CLASS OF
ACCURACY
Items
CT
Rating
No Of
Cores
Core
Burden
( VA)
Factors
Core
Acc.
Class
33
KV
3 Cores
(Metering,
Protection
, Diff.)
5 Cores
Metering
Protection
,
Differenti
al
Bus Prot.,
Dist. Prot.
Meterin
g
2.5,5,
7.5,10,
15,30
ISF
(5, 10, 20)
METE
RING
0.1, 0.2
0.5,
1, 3, 5
PROTE
C
TION
(5P, 10P
15P) *
Ratio
Primary
Current
Secondary
Current
33
KV
In
door
Single
Ratio
33
KV
Out
Door
Multi
Ratio
Suitably
(10,15,20,30
50,75) Multiple
or Fraction
1A or 5 A
66
KV
Protecti
on
ALF
(5,10,15,20,
30)
Voltage
2.5,5,
Across CT
7.5,10,
=
15,30
(Burden X
ALF)/
Rated
Current
Rated Short time
Current
Ist = 150 Ip for 1 Sec.
SELE
TIVE
PROTE
CTION
PS * *
4.2.2
Nominal Highest
Lightning Nominal Highest
Power
Lightning
Power
System System Frequency Impulse
System System Frequency Impulse
Voltage Voltage Withstand Withstand Voltage Voltage Withstand Withstand
Voltage
Voltage
KV
Voltage
Voltage
KV
KV
KV
(RMS
RMS
RMS
KV RMS
KV
(RMS)
KV RMS
KV
PEAK
PEAK
List List
220
245
360
850
1
2
Upto 0.6
0.66
3
395
950
3.3
3.6
10
20
40
460
1050
6.6
7.2
20
40
60
400
420
950 *
1175
11
12
28
60
75
1050 *
1300
33
36
70
145 170
1050*
1425
66
72.5
140
325 325
525
524
1050*
1425
110
123
185
450
1175*
1550
230
550
* Switching Impulse Withstand Voltage in
KV (PEAK)
132
145
230
550
275
650
4.2.3
ERRORS IN CT
4.2.3.1
METERING CORE
Acc.
Class
0.1
0.2
0.5
1.0
0.2s
0.5s
5P
10P
15P
Current Error
at Rated
Primary
Current (%)
1
3
5
Phase displacement at
Rated Primary Current
(Minutes)
60
-
Composite Error
at Rated Acc.
Primary
Current (%)
5
10
15
ALSTOM MAKE
Relay type:DTH 31/32
Application
Transformers, Generators,
Generator transformers, Motors,
Shunt reactors, Series reactors also
Overall generator- transformer
units,
Transformers connected to a mesh
corner, having two sets of CTs
each Supplying separate relay
inputs.
4. 2.4.1.2
1.
Knee point
voltage V K
24In [R CT
+2RI ]
Through fault
stability X/R
40
If
48In [R CT
+2RI
48In [R CT
+2RI
120
15In
40
120
40In
15 In
ABB MAKE
Relay type :RADSB (Static)(Medium impedance)
15In
3.
EASUN REROLLE
Relay type:4C21 (Static)(Low impedance)
ALSTOM
Relay type:CAG34 (High Impedance Scheme)
V K >2I f (R CT +2R L )
Example :V K >2x10(3+4) >140V
Where ,I f =sec. equivalent of Fault Current
Ie =Is-Ir =(0.15-0.10) /2 =25 m A at V K /2
2.
For voltage dependent, over current , field failure and negative phase, sequence protection
V K >20In (R CT +2R L )
l For stator earth fault protection
V K >Is (R CT +2R L +RR)
2.For generator differential protection:
Low impedance diff. V K >50In (R CT +2R L )
High impedance diff V K >2 Vs
where Vs =1.5I f (R CT +2R L ), Rs =Vs/Is
ABB
Relay type: RADHA /RADHD (High impedance )
EASUN REYROLLE
Relay type:4B3 (EM)/DAD 3 (Static)/Argus-1
(Numeric)(High Impedance Scheme)
ABB
Relay type: RADHA/RADHD (High impedance scheme)
ALSTOM
Relay type:CAG34 (High Impedance scheme)
EASUN REROLLE
Relay type:B3 (EM)/DAD3 (Static)
CT Class: PS , V K >2I f (R CT +R L )
Example: V K >2X10(3+4) >140V
I f -Max. thro fault current
R CT -Main CT resistance
R L -Lead resistance between CT to relay
4. 2.4.4
DISTANCE PROTECTION
4. 2.4.4.1.
EASUN REYROLLE
1.
ALSTOM
1.
Relay type: Micromho, Quadrmaho
V K >I f (X/R)(M+R CT +nR L )
Example: V K >10(4)(10.2+3+4) >40(17.2) >688V
Ie <3%In at V K /2 <30 mA at V K /2
Where M=Relay resistance (Phase fault)
2.
Relay type: MiCOM 430/441/442,EPAC,LFZR,LFZP,
PD521,PD932 (Numerical)
V K >I f x(1+X/R)x(R CT +R L +R B )
Where: X/R=The primary system ratio. R B =Relay Burden
R L =Rest of cable connecting CT to relay (lead and return for ground faults, lead only for phase
faults)
4. 2.4.4.3.
ABB
4. 2.4.5.1.
1.
EASUN REYROLLE
Relay type :Solkor-M and Microphase-FM (Numerical) (Current
Differential)
2.
Class:5P10, Burden:5VA
4.2.4.6.2.
1.
ABB
Relay type: SPAJ 140 (Numerical)
CT class: PS V K =50/ In + (I f / N) (R CT +R L)
In -Rated Current
I f -Maximum primary steady state through fault current
N -CT ratio, R CT -CT resistance, R L -Lead Resistance
Rating / Value
HIVOLTRANS ELECT. PVT.
LTD
IS 2705-1992
600-300-150 A
Insulation Level (
Kv )
Frequency
3625 mm
50 HZ
Particulars
Type
Rating / Value
CB-14
Normal Sys.
Voltage
Highest Sys.
Voltage
S.Ty.Current
Ka/Sec
Wt. Of Oil /Ct
Kg
Drg. No
132KV
145KV
18.2/3
120/550
0-325/CB14/B/2031
Suitable For Hotline Washing
Sl. No
0-325/B/1
CAUTION
1. Sec. Terminals Must Be Shorted Before Burdon Is Disconnected
2. P.F. Testing Terminal to Be Earthed During Operation.
1s1
1s2
1s3 2s1
2s2
RATED ACC.
Vk
VA
CLASS (V)
Min
PS
1200
PS
600
PS
600
15
0.5
Fs<5
15
0.5
Fs<5
15
0.5
Fs<5
PS
1200
PS
600
PS
600
2s3 3s1
3s2
3s3
I exc@Vk
(mA)
MAX
10
20
20
-
Rct at
75 0 C
Max
5.0
2.5
2.5
-
10
20
20
5.0
2.5
2.5
Rating / Value
W.S INDUSTRIES
IS 2705-1992
1050/460 KV
50 HZ
100 KAp
5643/1997
RATIO
PRI/SEC
CURRENT
(A)
PRI. CONN.
Particulars
Type
HSV/NSV
S.T.Current
Wt. Of Oil
TOTAL WEIGHT
Rating / Value
IT-245
245/ 220 KV
40/ 1 KA/Sec
350 KG
1200 KG
400-200-100/1-1-1-1-1
200/1
100/1
400/1
P1C1
P2C2
C1-C2
C1-C2
SEC.
CONN.
CORE 1
CORE2
CORE3
1S1-1S3
2S1-2S3
3S1-3S3,S
CORE4
CORE5
4S1-4S3
5S1-5S3
1S1-1S3
2S1-2S3
3S13S3,S
4S1-4S3
5S1-5S3
1S1-1S2
2S1-2S2
3S13S2,S
4S1-4S2
5S1-5S2
1
2
3
4
CORE
40
OUT PUT*
PS
PS
0.5
PS
ACC.
CLASS*
5
ISF/ALF*
1200
1200
1200
Vk (V) Min*
25
25
25
I exc@Vk
*(mA) Max
*
5
5
5
Rct at 75 0 C
Max*
* AT 400/1 AND 200/1 RATIO ONLY
P1
C1
C2
P2
S1
S2
S3
5
PS
1200
25
Rating /
Value
GYRO
LAB
PVT.
IS 27051992
400-200100/1-11A
70/170
KV
3452
Make
Ref.
Standard
Ratio
Insulation
Level
Sl. No
Particulars
Type
Rating /
Value
GWT-0/33
Frequency
50 HZ
Highest Sys.
Voltage
36 KV
S.T.CurrentKA/Sec
25 KA / 1
I
II
III
30
30
-
5P
0.5
PS
10
-
ISF Rct
I
exc@Vk
at
(mA)
75 0
mAX
C
Max
<5 1000- 25/ 15
<3
1200
/<6
CONNECTION DIAGRAM
RATIO
100/1
200/1
400/1
P1
C2
C1
P2
S1
PRIMARY CONN.
C1+C2
P1+C1 & P2 +C2
P1+C1 & P2 +C2
S2
SEC. CONN.
S1-S2
S1-S2
S1-S3
S3
R=Y=B= x Amp
N= 0 Amp
R=Y=B= x Amp
2
& N= 2x Amp
i. If (R+Y ) = ( Y + B ) = 3x
& ( B + R )= x
ii. If (R+Y ) = ( B + R ) = 3x
&( Y + B ) = x
iii. If (Y+B ) = ( B + R ) = 3x
&( R +Y ) = x
I. If R = 0 Amp
3
& Y = B= N = x Amp
Then Check for all other R phase CT secondary
cores, if values obtained as
If R = 0 Amp
& Y = B= N = x Amp
II. Similarly for Y phase and B Phase also.
III. If R = 0 Amp
& Y = B= N = x Amp
For only in One core, Then
7
8
Expected Faults
No Fault in the circuits
ANY ONE OF THE PHASE CT
POLARITY REVERSED
Y PHASE REVERSED
R PHASE REVERSED
B PHASE REVERSED
R PHASE PRIMARY SIDE OPEN
4.3.
VOLTAGE TRANSFORMER
4.3.1
SPECIFICATIONS
RATIO OF PT
ITEM
22 KV
UNIT
Multi
phase in
single
unit
Y/Y, V/V
Winding
Connection
Primary
Voltage
Secondary
Voltage
33 KV
3 Single phase
PT in star
connection
separate
Y/Y, Y/Y
Open delta
Rated Voltage / 3
110V /
ERRORS IN PT
METERING CORE
ACC. Class
%
Phase Angle
Voltage
displacement
Ratio Error
Error in
Minutes
0.1
0.1
5
0.2
0.2
10
0.5
0.5
20
1.0
1.0
40
3.0
3.0
Note. Errors at any Voltage between 80 to
120 % of rated voltage, with Burdens
between 25 to 100 % of rated burden at p.f 0.
8 (lag)
RATED
CLASS OF ACC.
BURDEN
1. The Rated
Winding
Acc.
Burden at a
Class
P.F = 0.8
Metering 0.1,
(lag) shall be
0.2,
chosen as
0.5,
(10, 25, 50,
1.0, 3.
100, 200,
400, 500) VA
/ Phase for 3 Protection 3P, 6P
Phase
Transformer
2. Two
independent
Secondary
Windings are
to be
Provided for
Metering &
Protection
Core
4.3.2
PROTECTION CORE
ACC.
%
Phase Angle
Class
Voltage
displacement
Ratio
Error in
Error
Minutes
3P
3
120
6P
6
240
Note 1. Errors at 5 % rated Voltage
and Voltage multiplied by voltage
factor (1.2, 1.5 or with burdens
Between 25 to 100 % of rated burden at
p.f 0. 8 (lag)
Note 2: - Errors at 2 % rated Voltage
shall be twice as high as given in the
table with similar burdens to Note 1.
Rating / Value
Make
Type
Highest
System
Voltage
Total
WEIGHT
CAP. OIL
EMU OIL
CGL
Sl. No.
VCE :145/275/50 Rated Voltage
145 KV
Rated Insulation
Level
Int. V ( Sec )
Capacitance
Nom.
Interme.Volt.
Total
Thermal
Burden
Voltage
Factor
Particulars
Rating /
Value
02314
132 KV/ 3 KV
275/650 KV
420 10 % KG
Rated Frequency
50HZ
25 10 % KG
85 10 % KG
Standard
HV ( Pri)
Capacitance
Equ. Cap
( Cn ) for PLCC
TOTAL SIM.
BURDEN/CLASS
Month / Year of
Manufacturing
IS 3156
6511+ 10%
- 5 % pF
5575+ 10%
- 5 % pF
150 VA / 0.5
35418 + 10%
- 5 % pF
13 KV
300 VA
1.2 Continuous /
1.5 for 30 Sec
MARCH./ 98
Rating / Value
Rating /
Value
Make
GYRO LAB PVT.
Type
GWT-0/33
Ref. Standard IS 3156 ( PT I,II,III ) SL. NO
4536
Ratio
33/ 3 KV/ 110/ 3 V Insulation Level
70/170 KV
Voltage Factor 1.2 Continuous /
Highest Sys. Voltage 36 KV
1.5 for 30 Sec
RATED
CORE VA
W1
100
W2
100
Particulars
ACC.
CLASS
0.5
0.5
TERMINAL
MARKING
1a-1n
2a-2n
4.3.3.3
Particulars
Make
Type
Highest System Voltage
Rating / Value
ABB Limited
WP 245N2
245 KV
Total Creepage
Wt of Oil
Total Weight
750 KG
48400 pF
Terminal Marking
1a-1n
2a-2n
3a-3n
Particulars
Sl. No.
Rated Voltage
Rated Insulation
Level
Rated Frequency
Standard
Rating / Value
2204147
220/ 3 KV
245/460/1050 KV
50 HZ
IEC : 60186/ IS :
3156
4840 pF
HV ( Pri)
Capacitance
Equip. Cap
4400 + 10 %
( Cn ) for PLCC
- 5 % pF
Temp. category
- 5 to 55 0 C
Class of Insulation A
Suitable for hot Line Washing
Voltage Divider
220/ 3 KV/20/ 3
ratio
KV
G.A Drg. No.
1HYT900158-013
Rated burden VA
150
150
50
Acc. Class
0.5
3P
3P
3)
Highest System
Voltage
KV, RMS
Typical Switching
Surge pu
Highest System
Voltage
KV, RMS
Typical Switching
Surge pu
12 KV 36 KV
123 145 KV
245 KV
420 KV
<4
<3
3
2.5
525 KV
765 KV
1500 KV
2.25
2.0
1.5 (Projected)
4.4.2
Sl.
No
11
System Voltages in KV
11
11
22
22
Rating KV (RMS)
2
3
4
MCOV (RMS)
Discharge Current
Line Discha. Class
7.2
7.2
9.6
Rated frequency
a) IR at MCOV
b) IG at MCOV
a) Reference Current, mA
b) Reference Volt at
Reference Current
Max. RDA
(KV p) at
a) 5KA
b) 10KA
c) 20 KA
Max. Switch IMP R V
(KVp
500A
1000A
Max. Steep Current
Impulse RDV (KVp)
High Current Impulse
Withstand
TOV (KVp)
i) 0.1 Sec
ii)1.0 Sec
iii) 10.0 Sec
iv) 100.0 Sec
9
10
11
33
33
18
18
30
30
9.6
15
10 KA
2
1
15
25
25
50HZ
Less than 400 micro Amps.
About 1200 micro Amps.
1 to 5 mA
Greater than Rated Voltage
27
30
34
26
28
30
36
38
42
33
36
40
51
60
68
52
56
60
90
95
105
86
90
100
24
36
22.4
34
30.4
42
28.8
40
48
60
44.8
56
76
105
72
100
32
30
29
28
53
51
49
47
53
51
49
47
100KAp
15
15
14
13
16
15
14
13
21
20
19
18
21
20
19
18
32
30
29
28
12
Insulation Withstand
a) Lightning IMP
b) Power frequency
c) Switching IMP
13
14
15
Partial Discharge
PR Relief Class
PR Relief Class KA (RMS)
16
17
4.4.3
Sl.
No
1
2
3
4
5
9
10
11
12
75
28
-
75
28
-
75
28
-
75
28
-
125
50
-
125
50
-
170
70
-
170
70
-
Less than 50 pC
Class A
40 KA
270
270
300
300
600
600
900
900
325
325
325
325
325
325
325
325
Rating KV (RMS)
MCOV (RMS)
Discharge Current
Line Discha. class
Frequency
a) IR at MCOV
b) IG at MCOV
a) Reference Current, mA
b) Reference Volt at
Reference Current
Max. RDA (KV p) at
a) 5KA
b) 10KA
c) 20 KA
Max. Switch IMP R V
(KVp
500A
1000A
Max. Steep Current
Impulse RDV ( KVp)
High Current Impulse
withstand
TOV (KVp)
i) 0.1 Sec
ii)1.0 Sec
iii) 10.0 Sec
iv) 100.0 Sec
Insulation Withstand
a) Lightning IMP
b) Power frequency
c) Switching IMP
System Voltages in KV
66
66
110
132
220
220
400
400
60
60
96
120
198
216
360
390
51
51
81
102
168
175
292
303
10 KA
2
3
3
3
3
3
3
3/4
50HZ
Less than 400 Amps.
Less than 500 micro Amps.
About 1200 Amps.
About 1500 micro Amps.
1 to 5 mA
Greater than Rated Voltage
170
180
200
160
170
119
251
272
307
320
340
380
518
550
610
567
600
668
820
880
925
860
950
1000
144
200
136
190
217
298
272
372
455
600
496
654
830
1000
850
1050
100KAp
106
102
98
94
106
102
98
94
170
163
156
149
212
204
195
187
350
336
322
308
382
366
351
336
636
610
585
560
689
661
634
607
325
140
-
325
140
-
550
230
-
650
275
-
1050
460
-
1050
460
700
1425
630
1050
1425
630
1050
13
14
15
16
17
4.4.5
Sl.No
1
2
3
4
5
6
7
8
10
Partial Discharge
PR Relief Class
PR Relief Class KA RMS)
Total creepage Distance in
mm
Max. Cant. Strength in
KGM
1800
1800
500
500
Less than 50 pC
Class A
40 KA
3075
362 6125 6125
5
500
100 1000 1000
0
1050
0
1000
10500
1000
Unit
KVp
36 KV
170
72.5
KV
325
145
KV
650
245 KV
1050
KV
30
60
120
198
KV
KAp
KAp
25
10
100
52
10
100
102
10
100
168
10
100
94
185
380
600
80
84
94
70
156
165
185
136
330
350
390
290
510
550
610
450
60
55
52
51
120
111
105
102
254
234
222
215
404
372
353
31
KV
KVp
mm
70
170
900
140
325
1800
275
650
3625
460
1050
6125
mm
mtr
Kgs
280
0.68
45
280
0.940
60
280
1.540
150
280
2.785
250
mm
368
4
15
368
4
15
368
4
15
368
4
19
Single
zebra
Single
Panther
(66 &
132kv)
(KVp)
@ 1 KAp
(KVp)
mm
ACSR
Single
rabbit
Temporary
Over Voltage
Switching
Over Voltage
Magnitude
1 to 2 pu
1.5 to 5 pu
Duration
mS to Tens of
Sec.
P.D. causes
retardation of
life of
insulation
Tens of S to
Tens of mS
Partial Discharge
on Insulation
--
250 100 S
2500 100 S
Effect
Testing
Evaluation
4.4.6
SURGE IMPENDANCE
( L/ C)
Lightning
Objects
Surge
Over Voltage
Impedance
( L/ C)
Hundreds of KV to
Z T = 100 to
Tower
150 Ohm
Several Tens of MV
Few Tens to Hundred OH Ground
Z G = 400 Ohm
of S.
Wire
Z T = 325 to
Influences
OH Phase
Transformer
400 Ohm
Conductor
Insulation and Break
down of Weaker
Section
1.2 S 30%
Source Surge Z T = 1500 to
3000 Ohm
50 S 20%
Impendance
Range of Voltage
Low Voltage or
Secondary Arrestor
(175 to 660 V)
Distribution Class
(3 KV to 18 KV)
Intermediate Class
(3 KV to 110 KV)
Station Class
(light Duty)
(11 KV to 198 KV)
Station Class
(Heavy Duty)
(198 KV and
above)
Impulse Current
KA
8x20 Micro Sec.
2.5
High
Current
5.0
50
75
1000
5.0
50
75
1000
10.0
65
150
2000
10
15
20
65
300
3000
25
Particulars
Type
Continuous Current Rating at 50 0 C
ambient
Continuous Current Rating at 65 0 C
ambient
Max. Symmetrical Short Circuit Current
For 1 Sec
Asymmetrical peak value of first half of
rated short time Current
Rated Inductance
Blocking Range
Min. Resistive Component in Blocking
frequency range
Radio Interference voltage
Mounting
Basic Insulation Level
Standard Nominal Discharge Current for
8/20 micro Sec. Wave impulse
Rated Voltage of Arrestor
Max. 1.2/50 micro sec. Impulse Spark over
voltage
Min. value of power frequency Spark over
voltage
Virtual steepness and max. Front of wave
Impulse Spark over voltage
Tuning
Visual Corona Extinction Voltage
Max. Residual Discharge Voltage for 8/20
micro Sec. Impulse Discharge current
1. 5000 A
2. 10000 A
No of Turns in Main coil
Value
Out door, Air Cored,
Air Cooled
1250 Amp
1125Amp
31.5 KA
80.5 KA
0.5 H
150-500 KHz
570 Ohm
< 500 V
Suspension
32.37 KVp
10 KA
6 KV
21.6 KVP
9 KV rms
49.8 KV / micro S
24.9 KVp
Broad Band
156 KV
21.6 KVp
21.6 KVp
28 (2 in Parallel
4.6 ISOLATORS
TECHNICAL PARTICULARS FOR 245 KV ISOLATOR
Particulars
Type
Standards used
Highest System Voltage
Nominal System Voltage
Max. Continuous Current Rating
Rated Short time Current for 3 Sec
Max. Magnetizing current
Rated Peak Short time Current
1.2/50 Sec. Impulse Withstand
Voltage
Radio Interference voltage
Earthing SWITCH Rated Current
Capacity
Minimum Clearance in
1. Between Live parts and ground
2. Fixed Contact and blade in Open
condition
Operating Time
1. Opening
2. Closing
Continuous Rating of Aux. Contact
Temp. Rise
Insulation Level
Value
Air break, Off load
1SS 9921/85
245 KV
220 KV
2000 Amp
40 KA
0.7 A at 0.15 p F
100KAp
1200 KV
1000 V
50 % of Main switch
2400mm
1600mm
10-12 Sec
10-12 Sec
10 A
55 above Ambient
530 KV
4.7 TRANSFORMER
4.7.1. CURRENT RATING OF TRANSFORMER (3~
)
Thumb rule Current = (600 x MVA)/ KV
Actual rule Current = (575 x MVA) / KV
Where MVA = Rating of Transformer
KV = Rated voltage of transformer
Supply voltage,
Rated voltage
(KV)
ACTUAL
Current / MVA
11
33
66
132
220
400
52.3
17.43
8.72
4.36
2.615
1.44
THUMB
RULE
Current /
MVA
54.55
18.2
9.1
4.55
2.73
1.5
THUMB RULE
Current / MWatt
(for cos =0.9 )
60
20
10
5
3
1.66
4.7.2.
4.7.4
(U/f) / (UN/fN)
Time in Seconds
100
109
118
127
136
82
19
9.9
6.0
2.5
KV
3.7%
3.3%
-
230
KV
4.0%*
3.5%*
2.2%*
* Reduced insulation
NOTES FOR TESTING ENGINEER
1.
No load current should be maximum 3 to 4% of rated current.
2.
The exciting current varies directly with voltage rating and inversely to KVA rating.
4.7.5
Grain oriented
Non-grain oriented
Decay to the
laminations
laminations
value in Cycle
Switching on of
Switching on of
Outer
Inner
Outer
Inner
Winding
Winding
Winding
Winding
(A mp)
(A mp)
(A mp)
(A mp)
8 to 10
500
11.0
16
6.0
9.4
8 to 10
1000
8.4
14
4.8
7.0
10 to 60
6.0
10
3.9
5.7
5000
10 to 60
10000
5.0
10
3.2
3.2
60 - 3600
50000
4.5
9
2.5
2.5
1.In actual practice the value may vary 8 to 10 times the maximum value. It
depends upon the cycle of energisation of supply wave.
2. (Maximum value of inrush current)/(Peak value of rated current) = Ratio.
Water
Air
Transformer Oil
Thermal resistivity
(0C/Watts/inch3
70
1710
245
Copper (Pure)
0.0896
Copper
(Commercial)
Wrought iron
0.1125
Caste iron.
Steel (laminated
with grain)
0.984
2.4
0.50
Material
Aluminum
Mica
Press board (Un
treated)
Press board (Oil
treated)
Varnished cambric
(Sheet form)
Varnished cambric
(tap lap wraps)
Porcelain & Cement
Steel (laminated
across grain)
Thermal resistivity
(0C/Watts/inch3
0.30
110
400 500
250 300
200 250
250 300
40
25.0
OA, OW
OA / FA
OA / FA / FOA
FOA
FOW
7.9
115
138
161
196
230
Low. Voltage
Insulation Class
15
15
25
25
34.5
34.5
46
34.5
69
34.5
69
92
34.5
69
115
46
92
138
46
92
161
46
92
138
161
%
Min.
5.5
6
6.5
6.5
7
7
8
7.5
8.5
8
9
10
8.5
9.5
10.5
9.5
10.5
11.5
10
11.5
12.5
11
12.5
14
14
Max.
8
8
9
9
10
10
11
10.5
12.5
12
14
15
13
15
17
15
16
18
15
17
19
16
18
20
20
4th letter
3rd letter
Kind of
Kind of
Circulation
Medium
Indicating the cooling medium
that is in contact with the
external cooling system
(i)
(ii)
(iii)
(iv)
Type
Oil immersed,
natural air
cooled
Dry type natural
air cooled
Oil-immersed,
forced air cooled
Dry type, forced
air cooled
Reduced by %
2%
2.5%
3%
5%
Winding
Note (1)
Note (2)
Cooling
Method
(All cases)
Oil
Circulation
(All cases)
- do -
- do -
(Natural air),
(Forced Air),
(Water
(Internal)
Forced air
Water
(external
cooler)
Natural
Forced
Temp. Rise
600C when transformer is sealed or
equipped with conservator.
550C when transformer is neither so
sealed nor equipped.
The temperature in no case to reach a
value that will injure the core or its
adjacent material
650C
650C
4.7.13 LOSSES (NO LOAD LOSS AND FULL LOAD LOSS) FOR TWO WINDING
TRANSFORMER
Rated Power
(KVA)
500
1000
2000
3150
5000
6300
10000
12500
20000
31500
40000
Above 40,000
#
*
INSULATION RESISTANCE
4. 7.16.1
Insulation
Condition
Dangerous
Poor
Questionable
4. 7.16.3
Insulation Resistance and P.I Value
(a) Minimum insulation resistance is obtained by following formula: R=CE/
KVA
Where R = I.R of winding with ground when other windings are grounded in M.
C = Constant = 0.8 for ONAN at 200C.
= 16 for dry, compound filled or un tanked oil filled,
KVA = Rated capacity of winding under test.
E = 1 voltage (Y) and line voltage for () in volt.
4. 7.16.4
0
0
0
winding
600C
30 C
40 C 50 C
66 KV and above
600
300
150
75
22 KV and 33 KV
500
250
125
65
6.6 KV and 11 KV
400
200
100
50
Below 6.6 KV
200
100
50
25
The I.R. value should be taken with all windings earthed
except the tested winding.
4. 7.16.5
4. 7.17.
PI2=R60/R15
1.5 to 2
PI3 = R600/R60
1.2 To 1.5
1800
0
Group (3)
-30 ; 330
Group (4)
+ 300
4. 7.19.2
CONDITIONS FOR PARALLEL OPERATION
i. Same inherent phase angle difference between primary and secondary terminals.
(ii) Same voltage ratio
(iii) Same frequency
(iv) Same polarity
(v) Same phase rotation
4. 7.20 LOAD SHARING BY TRANSFORMERS IN PARALLEL
4. 7.20(A)
P = Total Load,
For 3 Transformers
PA = P (QA.ZB ZC) /
PB = P (QB.ZC ZA) / ,
Pc = P (QC.ZA.ZB) /
Where = (QA.ZB ZC + QB.ZC ZA + QC.ZA.ZB)
Note: - Currents are also shared by same proportionate as loads.
4. 7.21.
CIRCULATING CURRENTS
4. 7.21.(A)
Two Transformers in Parallel
(i) For impedance having same ratio (R /X)
ICr = (VA-VB) / (ZA+ZB)
(ii) For impedance having different ratio (R/X)
ICr = (VA-VB)/Z,
Where Z = ( R A + R B ) 2 + ( X A + X B ) 2
VA = Secondary terminal voltage of transformer (A) (Lower ratio)
4. 7.21 (B)
(i)
ICrA
ICrC
(VC-M) / ZC
TRANSFORMER TAPPINGS
Note: - (1) For 2 winding transformer, tap changer is generally provided on the H.T. side i.e.
L.T. side
voltage remains constant.
(2) For Autotransformer, tap changer is generally provided on the L.T. side i.e. H.T. side
voltage remains constant.
Transformer
20%
20%
3. 132 / 33 KV
132 / 11KV
20%
20%
4. 220 / 132KV
220 / 33KV
20%
20%
1. Distribution
Transformer
(11/0.4 or
11/6.6 KV)
2. 33/11KV
8.
9
10
11
12
13
14
15
16
17
18
19
20
CHARACTERISTICS
APPEARANCE
DENSITY gm/cc Max@
29.5 0 c
Kin. Visco. CSt Max
Inter facial Tension( N/m
Min.
Flash Point 0 C Min.
Pour Point 0 C Min.
BDV KV/cm Min.
New Unfiltered
After Filter
Tan Delta @ 90 0 C Max.
Resistivity Ohm-cm .
@ 90 0 C Min
@ 270 C Min.
Oxi. Stability 164 Hrs
1. Neutralization Value
(mg KOH/ gm Max)
2. Sludge Cont. (% / wt
Max)
Neutralization Value
1. Total Acidity(mg KOH/
gm )
2. Inorganic Acidity
Corrosive Sulphur
Oxi. Inhibitor
Water Content (ppm) Max
Bulk / Drum Delivery
S.K. Value
Accl. Ageing Test (Open
Beaker Method with Copper
Catalyst)
1. Tan Delta @ 90 0 C Max.
2. Resistivity Ohm-cm. @
90 0 C
3. Resistivity Ohm-cm. @
27 0 C
4. Total Acidity
5. Sludge Cont. (% / wt
Max)
Gassing Tendency at 50 Hz
after 120 min., mm3/min.
Max
Total PCB Con. mg/Kg
Total Furan mg/Kg Max
Poly cyclic Aromatic Wt%,
Max
IS:335
IEC-296
IEC-296
BS-148
1993
CLASS-1
CLASS-II
CLASS-I
Oil should be clear, transparent, free from suspended mater and sediments
0.89
0.895
0.895
0.895
27 @270 c
BS-148
CLASS-II
0.89
0.04
16.5 @ 40 0 c
800 @ - 15 0 c
N. R
11.0@ 40 0 c
1800 @ - 15 0 c
N. R
16.5 @ 40 0 c
800 @ - 15 0 c
N. R
11.0@ 40 0 c
1800 @ - 15 0 c
N. R
140
-6
140
-30
130
-45
140
-30
130
-45
30
60
0.002
30
50
0.005
30
50
0.005
30
As Delivered
0.005
30
As Delivered
0.005
35 1012
1500 1012
N. R
N. R
N. R
N. R
0.4
0.4
0.4
1.2
1.2
0.1
0.1
0.1
0.8
0.8
0.03 Max
Nil
0.03 Max
-
0.03 Max
-
0.03 Max
-
0.03 Max
-
NonCorrosive
0.05% Max
50
Non- corrosive
Non- Corrosive
Non- corrosive
Non- Corrosive
Not-Detectable
40
Not-Detectable
40
Not-Detectable
20/30
Not-Detectable
20/30
N. R
N. R
N. R
N. R
+5
+5
Not-Detectable
1.0
3.0
Not-Detectable
1.0
3.0
Under
Consideration
0.2
0.2 1012 Min
2.5 1012 Min
0.05
0.05
4.7.23.2
Sl
No
1
2
3
4
5
6
7
8.
9
11
12
10
13
14
15
16
17
18
19
CHARACTERISTICS
APPEARANCE
DENSITY gm/cc Max@ 29.5
0
c
Kin. Visco. CSt Max
Interfacial Tension
( N/m Min.
Flash Point 0 C Min.
Pour Point 0 C Min.
BDV KV/cm Min.
New Unfiltered
After Filter
Tan Delta @ 90 0 C Max.
Resistivity Ohm-cm .
@ 90 0 C Min
@ 270 C Min.
Neutralization Value
1. Total Acidity
(mg KOH/ gm Max)
2. Inorganic Acidity
Corrosive Sulphur
Oxi. Stability 164 Hrs
1. Neutralization Value
( mg KOH/ gm Max)
2. Sludge Cont.
(% / wt Max)
3. Volatile Acidity Max
Oxi. Stability 500 Hrs
1. Neutralization Value
(mg KOH/ gm Max)
2. Sludge Cont. (% / wt Max)
Oxi. Inhibitor
Water Content (ppm) Max
Bulk / Drum Delivery
Accl. Ageing Test (Open
Beaker Method with Copper
Catalyst)
1. Tan Delta @ 90 0 C Max.
2. Resistivity Ohm-cm. @ 90 0
C
3. Resistivity Ohm-cm. @ 27 0
C
4. Total Acidity
5. Sludge Cont. (% / wt Max)
Gassing Tendency at 50 Hz
after 120 min., mm3/min. Max
Total PCB Con. mg/Kg
Total Furan mg/Kg Max
Poly cyclic Aromatic Wt%,
Max
IS:
IEC-296
IEC-296
BS-148
BS-148
12463/1988
CLASS-1A
CLASS-IIA
CLASS-IA
CLASS-IIA
Oil should be clear, transparent, free from suspended mater and sediments
0.89
0.895
0.895
0.895
0.89
27 @270 c
16.5 @ 40 0 c
800 @ - 15 0 c
11.0@ 40 0 c
1800 @ - 15 0 c
16.5 @ 40 0 c
800 @ - 15 0 c
0.04
0.04 @ 250 c
0.04 @ 250 c
11.0@ 40 0 c
1800 @ - 15 0
c
-
140
-6
140
-30
130
-45
140
-30
130
-45
30
60
0.002
30
50
0.005
30
50
0.005
30
As Delivered
0.005
30
As Delivered
0.005
35 1012
1500 1012
0.03
0.03
0.03
0.08
0.08
Nil
NonCorrosive
NonCorrosive
Non- Corrosive
NonCorrosive
NonCorrosive
0.4
0.4
0.4
0.25
0.25
0.1
0.1
0.1
0.01
0.01
0.28
0.28
1.5
1.5
0.3
50
0.15-0.4
30/40
0.15-0.4
30/40
1.0
0.3
20/30
1.0
0.3
20/30
N. R
N. R
N. R
N. R
+8
+8
Not Detectable
1.0
3.0
Not-Detectable
1.0
3.0
0.2
0.2 1012
Min
2.5 1012
Min
0.05
0.05
4.7.23.3
Sl
No
CHARACTERISTICS
1
2
3
APPEARANCE
DENSITY gm/cc Max
Kin. Visco. CS t (SUS) Max
@ 100 0 c
@ 40 0 c
@00c
@ -15 0 c
@ -30 0 c
IFT @ 25 0 c N/m Min
Flash Point 0 C Min. (PMCC)
Pour Point 0 C Max.
4
5
6
1
2
3
4
1
3
4
5
6
7
8
9.
10
BDV KV Min.
Before / After Filtration
BDV Impulse, @ 25 0 c, KV
Min. Needle Neg. to Sphere
grounded (25.4mm gap)
Gassing Tendency at 50 Hz
after 120 min., mm3/min. Max
Tan delta @60 Hz
Oxi. Stability Max.
1. 72 Hrs Sludge % Mass
TAN mg KOH/ mg
2. 164 Hrs Sludge % Mass
TAN mg KOH/ mg
Ageing Resistance as per
Badder (140 Hrs / 110 0 c)
Saponification No. mg KOH
/mg
Sludge Cont. wt%, Max
Tan delta @ 90 0 c Max
Oxi. Stability Max. (Rotating
Bomb Test ) Minutes Min.
Oxi. Inhibitor % Mass/Max
Corrosive Sulphur
Water Content (ppm) Max
1. Total Acidity
(mg KOH/ gm Max)
PCB Content ppm
Total Aromatic Content %
Max
Total Sulphur Content % Max
ASTM D 3487
TYPE-1
HVDC
SPEC.
DIN 57370
VDE 0370
PHYSICAL PROPERTIES
CLEAR &BRIGHT
0
0.91 @ 15 c
0.885 @ 20 0 c
0.895 @ 200 c
3 (36)
12 (66)
11
76 (350)
1800
0.04
0.04
145
140
-40
-30
ELECTRICAL PROPERTIES
AUSTRALIAN
AS 1767.1
CLASSI/II
0.895 @ 200 c
25 @ 20 0 c
1800
130
16.5/11
800/-/1800
0.04
140/130
-30/45
30/50
30/50
30/50
30/50
145
150
0.005 @ 90 0 c
0.005 @ 90 0 c
+15/+30
0.05 @ 25 0 c
0.005 @ 90 0 c
CHEMICAL PROPERTIES
0.15
0.5
0.3
0.6
0.03
0.15
0.6
0.3
0.1
0.4
0.6
0.05
0.18
195
0.08-0.3
Non- Corrosive
35
Non- Corrosive
10
Non- Corrosive
-
0.03
0.03
0.03
0.15-0.4
Non- Corrosive
30(Bulk)/40
(Drum)
0.03
Nil
-
Nil
12
Nil
-
Nil
-
0.15
4.7.23.4
Sl.
No
1
CHARACTERISTICS
Voltages
Test Method
PERIODICITY
BDV
145 KV &
ABOVE
72.5 TO <
145 KV
< 72.5 KV
145 KV &
ABOVE
BELOW 145
KV
IS 6792/1992
(Ave. of 6
Values
with 2.5 mm
gap
IS 335/1993
After filling or
refilling prior to
energizing then after 3
Months and after one
year
After filling or
refilling prior to
energizing then after 3
months and after one
year
After filling or
Refilling prior to
Energizing then after 3
Months and after 2
years
After filling or
Refilling prior to
Energizing then after 2
years
WATER CONTENT
PERMISSBLE
LIMIT
50 KV (Min.)
40 KV ( Min. )
30 KV ( Min. )
25ppm
35ppm
0.1 1012
Min.
SP. RESISTANCE @
90 0 c IN Ohm -cm
ALL
VOLTAGES
IS 6103
/1971
TAN DELTA @
90 0 c MAX
145 KV &
ABOVE
BELOW 145
KV
IS 6262/1971
IS 1448
PART-2
1967
APPENDIXA
IS 1866/1983
IS 1448
PART-21,
1992
-DO-
0.5 mg KOH/gm
-DO-
NO SLUDGE
-DO-
IS 6104
/1971
1S
9434/1992
-DO-
DECREASE OF 15
0
c FROM
INITIAL VALUE,
MIN. 125 0 c
0.018 N/m
5.
Neutralization Value
1. Total Acidity MAX
ALL
VOLTAGES
SEDIMENT OR
PRECIPITATE SLUDGE
ALL
VOLTAGES
FLASH POINT
-DO-
IFT @ 27 0 c MIN.
-DO-
DGA
145 KV &
ABOVE
After filling or
refilling prior to
Energizing then after 3
Months and after one
year
0.2
1.0
REFER IS
10593/1993/DGA
CHART
CH4/H2
> 1.0
<0.1
>0.1
<1.0
C2H2/C2H4
C2H2/CH4
< 0.75
>0.75
<0.3
<0.3
>0.3
C2H6/C2H2
>0.4
> 0.4
<0.4
C2H2/C2H4
0.1to 1.0
<0.1
0.1 to 3.0
<0.1
<0.1
<0.1
CH4/H2
< 0.1
<0.1
0.1 to 1.0
0.1 to 1.0
>1.0
>1.0
C2H4/C2H6
<1.0
<1.0
>3.0
1.0 to 3.0
1.0 to 3.0
>3.0
4.7.24.2
Sl
No
1.
2.
1.Internal Corona
2. Partial Discharge
5.
6.
4.7.24.3
C2 H6 (10-20%)
C H4 (10-20%)
H2 (60-70%),
>100ppm
C2H4 (30-40 %), >
30 ppm
H2 (80 90 %)
> 100 ppm
CH4 (50 60 %)
> 50 ppm
CO (90 95 %)
> 350 ppm
(0 720)
(721 1920)
(1921 4630)
>4630
INTERPRETATIONS
4. 7.24.4
PERMISSIBLE LIMIT (IN ppm) OF GASSES FOR SERVICE
TRANSFORMERS
GASSES
C02
CO
C2H4
C2H2
H2
CH4
TRANSFORMER
WITHIN 4 YEARS
2000-3000
150-300
100-150
20-30
100-150
50-70
TRANSFORMER
4-10 YEARS
3000-4000
300-450
150-200
30-50
150-250
70-150
TRANSFORMER
AFTER 10 YEARS
4000-6000
400-550
200-300
30-60
200-300
70-150
4.7.24.5OTHER INFORMATIONS
DISINTIGRATION OF
TRANSFORMER OIL
AT ORD. TEMP
GAS
%
C02
1.17
Heavy
4.86
Hydro
Carbon
O2
1.36
CO
19.21
H2
N2
CH4
59.10
10.10
4.2
Total
100
GAS
METHANE (CH4)
ETHANE (C2H6)
COUNTRY
USA
FRANCE
SPECIFICATIONS
ASTM D 1040 73
N.F Cir. C 1.03
>150
ETHYLENE
(C2H4)
ACETYLENE
(C2H2)
GERMANY
VDE 0370
INDIA
IS 335
SWEDEN
ITALY
SWITZERL
AND
UK
USSR
IEC
SEN-14
A.E.1.7
S.E.V.124
>700
220/132 KV
132/33 KV
132/11 KV
66/11 KV
33/11 KV
NATIONAL SPECIFICATIONS
BS 148
GOST-981
IEC: 296
OF TRANSFORMERS
- 0.005
- 0.009
- 0.008
- 0.006
- 0.010
- 0.010
- 0.006
- 0.010
- 0.010
- 0.006
- 0.010
- 0.010
- 0.006
- 0.008
- 0.008
- 0.018
- 0.020
- 0.020
Duration of Overload in
Oil Temp. At the
beginning of the Overload minutes
in deg. Cent. For cooling
method
ONAN
OFAN OFAF 10
20
30
40
50%
ONAF
OFW
%
%
%
%
50
55
49
160 80
60
30
15
75
68
60
120 60
30
15
8
90
78
68
60
30
15
8
4
Note _: - Type of Insulation: - A Class for above Table
Previous
Continuous
Loading as
% Rated
Load
All day
LONG PERIOD
MEDIUM PERIOD
SHORT PERIOOD
Heavy Load 16 Hrs
Remaining
Remaining
8 Hrs Remaining 3 Hrs
Continuous
Heavy
8 Hrs Light Heavy
16 Hrs
Heavy
Hrs Light
Load)
Load
Load
Load Light Load Load
Load
0
120
125
105
130
105
150
105
5
115
120
100
125
100
145
100
10
110
115
94
120
94
140
94
15
105
110
88
115
88
135
88
20
100
105
82
110
82
130
82
25
94
100
76
105
76
125
76
30
88
94
70
100
70
120
70
35
82
88
64
94
64
115
64
40
76
82
57
88
57
110
57
45
70
76
49
82
49
105
49
50
64
70
40
76
40
100
40
Note: - Type of Cooling: - ON (Oil Natural) Type of insulation A Class.
Max. Oil Temp. : - 80 Deg. Cents. Max. Winding Temp. : - 95 Deg. Cents.
4. 7.28 Daily Peak Loads per unit of Name plate rating to give Normal Life Expectancy
(COOLING SELF COOLED OR WATER COOLED ( OA OR OW ) $
Peak
Load
Time
In
Hrs
1/2
1
2
4
8
24
10
2.00
1.88
1.64
1.43
1.30
1.22
20
2.00
1.73
1.51
1.33
1.19
1.11
30
1.89
1.58
1.37
1.19
1.08
1.00
40
1.70
1.41
1.22
1.06
0.96
0.89
50
1.52
1.23
1.00
0.94
0.84
0.78
0
2.00
1.95
1.72
1.52
1.40
1.33
10
2.00
1.80
1.59
1.41
1.30
1.22
20
1.95
1.65
1.46
1.29
1.19
1.11
30
1.78
1.49
1.32
1.17
1.07
1.00
40
1.60
1.32
1.16
1.04
0.95
0.89
50
1.41
1.14
0.99
0.89
0.83
0.78
90 percent
Ambient in degree C
0
2.00
1.86
1.66
1.50
1.39
1.33
10
1.99
1.70
1.53
1.39
1.29
1.22
20
1.81
1.55
1.39
1.26
1.18
1.11
30
1.64
1.39
1.24
1.13
1.06
1.00
40
1.46
1.20
1.08
1.00
0.94
0.89
50
1.24
0.99
0.90
0.84
0.82
0.78
$ Subtract 5 0 C from each of the ambient column heading for water cooled transformer.
Minimum water temp. must be above 0 0 C
Example :- Assume a load cycle which resolves to a constant value of 50 % followed by a
100 % peak load for 2 Hrs. using the above table if the ambient Temp. is 30 0 C , a self cooled
(OA ) , a water cooled
( OW ) transformer will carry 1.32 times name plate rating for 2 Hrs following an equivalent
continuous load up to 70 % of name plate rating , if the equivalent 2 Hrs peak load from the
load cycle is 10 MVA . The constant equivalent load before the peak is 5 MVA which is 66.6
% of the name plate rating of the transformer . Therefore a 7.5 MVA transformer is suitable
for this daily load cycle.
4. 7.29 Daily Peak Loads per unit of Max . Name plate rating to give Normal Life
Expectancy (COOLING FORCED AIR COOLED RATED 133 % OR LESS OF SELF
COOLED RATING OR WATER COOLED ( OA / FA )
Peak
Load
Time
In
Hrs
1/2
1
2
4
8
24
Cooling Forced Air cooled Rated 133 % or less of Self Cooled Rating or Water cooled ( OA / FA )
Continuous equivalent Load in %tage of rated KVA preceding the peak Load
50 percent
70 percent
90 percent
Ambient in degree C
Ambient in degree C
Ambient in degree C
0
2.00
1.90
1.64
1.46
1.37
1.31
10
2.00
1.77
1.53
1.36
1.27
1.21
20
1.97
1.64
1.42
1.26
1.17
1.11
30
1.82
1.50
1.29
1.15
1.07
1.00
40
1.66
1.35
1.16
1.03
0.96
0.89
50
1.49
1.19
1.02
0.90
0.84
0.78
0
2.00
1.84
1.61
1.45
1.37
1.31
10
2.00
1.71
1.50
1.35
1.27
1.21
20
1.89
1.57
1.38
1.24
1.17
1.11
30
1.74
1.43
1.26
1.13
1.07
1.00
40
1.58
1.28
1.12
1.01
0.96
0.89
50
1.40
1.11
0.97
0.88
0.83
0.78
0
2.00
1.77
1.58
1.44
1.36
1.31
10
1.92
1.63
1.46
1.34
1.27
1.21
20
1.77
1.49
1.34
1.23
1.17
1.11
30
1.61
1.35
1.21
1.11
1.06
1.00
40
1.43
1.19
1.08
1.00
0.95
0.89
50
1.25
1.00
0.91
0.85
0.83
0.78
Note:- The peak load in this table are calculated on the basis of all cooling in use during the
period preceding the peak load. When operating with out fans, use this table for OA
transformer
4. 7.30 Daily Peak Loads per unit of Max . Name plate rating to give Normal Life
Expectancy (COOLING FORCED AIR COOLED RATED 133 % OR LESS OF SELF
COOLED RATING OR WATER COOLED ( OA / FA )
Peak
Load
Time
In
Hrs
1/2
1
12
4
8
24
Cooling Forced Air cooled Rated 133 % or less of Self Cooled Rating or Water cooled ( OA / FA )
Continuous equivalent Load in %tage of rated KVA preceding the peak Load
50 percent
70 percent
90 percent
Ambient in degree C
Ambient in degree C
Ambient in degree C
0
2.00
1.73
1.53
1.40
1.34
1.30
10
1.91
1.62
1.43
1.31
1.35
1.20
20
1.78
1.51
1.33
1.21
1.16
1.10
30
1.65
1.38
1.22
1.11
1.06
1.00
40
1.52
1.25
1.11
1.00
0.96
0.90
50
1.37
1.12
0.98
0.89
0.84
0.79
0
1.96
1.68
1.51
1.40
1.34
1.30
10
1.84
1.58
1.41
1.31
1.25
1.20
20
1.71
1.46
1.30
1.21
1.16
1.10
30
1.58
1.33
1.19
1.10
1.06
1.00
40
1.43
1.20
1.07
1.00
0.96
0.90
50
1.28
1.06
0.95
0.88
0.84
0.79
0
1.89
1.64
1.49
1.39
1.34
1.30
10
1.77
1.53
1.39
1.30
1.25
1.20
20
1.64
1.41
1.28
1.20
1.15
1.10
30
1.50
1.28
1.17
1.09
1.05
1.00
$ Subtract 5 0 C from each of the ambient column heading for water cooled transformer.
Minimum water temp. must be above 0 0 C
40
1.35
1.15
1.06
0.99
0.95
0.90
50
1.19
1.01
0.93
0.87
0.84
0.79
Air above 30 0 C
average OR Water
above 25 0 C
- 1.5 % per degree
- 1.5 % per degree
- 1 % per degree
Air above 30 0 C
average OR Water
above 25 0 C
1 % per degree
1 % per degree
0.75 % per degree
- 1 % per degree
4. 7.34
4. 7.35
Capacitance ( nF)
420 - 480
280 - 400
180 - 300
180 - 300
260 - 280
OF BUSHINGS
Tan
0.002 - 0.005
0.002 - 0.005
0.002 - 0.005
0.002 - 0.004
0.002 - 0.004
4.8
2 2.5 3
30
Approx 35% of
10
motor rating
8.4.1
750 RPM
1
2
3
4
6
8
9
10
14
16
20
24
30
39
45
1000 RPM
1
2
3
4
5
7
8
9
12
16
20
23
30
38
45
1500 RPM
1
2
3
4
5
6
7
8
11
13
16
19
24
31
36
3000 RPM
1
2
3
4
4
5
6
7
10
11
14
16
20
26
30
4.9.
BATTERY
4.9.1DATA
Sl.No.
1
2
3
4
5.
6
7
8
DATA/PARTICULARS
RECOMMENDED END
VOLTAGE
SP. GRAVITY (FULLY
CHARGED)
SP. GRAVITY (FULLY
DISCHARGED)
ALLOWABLE DIFF. IN
MAX & MIN SP. GRAVITY
NORMAL OPERATING
VOLTAGE
FULLY CHARGED
VOLTAGE
Equivalent SP. GRAVITY AT
27 0 C
RATE OF CHARGING
1. FINISHING RATE
AT 10 HRS
2. NORMAL RATE
3. EQUALISING
CHARGE AT 10
HRS
FLOAT CHARGE
1. FLOAT CHARGE
CURRENT
2. TICKLE CHARGE
CURRENT
VALUES
1.85/CELL
1200 AT 27 0 C
1190 AT 27 0 C
30 POINTS /CELL
2.15/CELL
2.4 2.5 /CELL
HYDROMETER READING
AT t 0 C + 0.0007 ( t 27 )
(% AH Rating of Battery) in Amp
4
10
2
(AH
3. SET Voltage
4.9.2
IMPORTANT NOTE
4.9.3
PERIODICITY
DAILY
WEEKLY
ITEMS TO BE
CHECKED
1. Measure
and
record the pilot
cell Voltage, Sp.
Gravity
&
Electrolyte
Temperature
2. Battery Voltage
by Switching off
Charger
3. Hourly reading
DC
Voltage,
Charger out put
current
and
Trickle Charge
Current
1. Cleaning
of
terminals,
topping
up
distilled water if
required
2. Check pilot cell
reading
and
adjust the trickle
charge current if
required
PERIODICITY
MONTHLY
YEARLY
ITEMS TO BE
CHECKED
1. Sp.
Gravity,
Voltage of each cell
and
electrolyte
Temp.
2. Give
Equalizing
Charge
3. Switch off Charger
and test tripping/
closing of any one
feeder from Battery
Source
4. Check
all
connection
of
battery and Charger
1. Allow Condition
Charging
4. 10
ENERGY METERS
1.0
0.5 Lg
CLASS
0.2
0.5
0.4
0.2
0.5
0.5
0.3
0.3
0.5
0.5
1.0
0.5
1.0
1.0
0.6
0.6
1.0
1.0
0.3
0.4
0.6
1.0
BALANCE LOAD
CBIP 88: 1996
P.F
CLASS
(Cos / sin
0.2
0.5
1.0
)
1.0
0.4 1.0
1.0
2.0
1.0
0.2 0.5 1.0
0.5 Lg
0.5 1.0 2.0
0.8 Ld
0.5 1.0 2.0
0.5 Lg
0.3 0.6 1.2
0.8 Ld
0.3 0.6 1.2
0.25Lg
0.5 1.0 2.5
0.5 Ld
0.5 1.0 2.5
UNBALANCE LAODS
0.3 0.6
1.0
0.5 Lg
0.4 1.0
1.5
2.0
1.5
IS 14697: 1999
P.F
CLASS
(Cos ) 0.2S 0.5S
3.0
1.5
3.0
3.0
1.8
1.8
3.5
3.5
1.0
1.0
0.5 Lg
0.8 Ld
0.5 Lg
0.8 Ld
0.25Lg
0.5 Ld
0.4
0.2
0.5
0.5
0.3
0.3
0.5
0.5
1.0
0.5
1.0
1.0
0.6
0.6
1.0
1.0
2.5
3.0
1.0
0.5 Lg
0.3
0.4
0.6
1.0
Class
1.0
2.0
5 - < 10
10- < Imax
1.0
1.0
1.5
1.0
2.5
2.0
10- < 20
* Spl. Request
20- < 100
0.5 Lg
0.8 Ld
0.5 Lg
0.8 Ld
0.25Lg
0.5 Ld
1.5
1.5
1.0
1.2
3.5
2.5
2.5
2.0
-
1.0
0.5 Lg
2.0
2.0
3.0
3.0
IEC 1036:1996
P.F
(Cos )
% Load
(Ib)
Direct
Connected
5 - < 10
10- < Imax
T/F
Operated
2 - <5
5- <Imax
10- < 20
5- <10
* Spl.
Request
20- < 100
* Spl.
Request
10- <100
UNBALANCE LOAD
10- < Imax
5- < Imax
(20- < Imax
10- < Imax
Class
1
1.0
1.0
1.5
1.0
2.5
2.0
0.5 Lg
0.8 Ld
0.5 Lg
0.8 Ld
0.25Lg
0.5 Ld
1.5
1.5
1.0
1.0
3.5
2.5
2.5
2.0
-
1.0
0.5 Lg
2.0
2.0
3.0
3.0
Cos
Nominal Ratio
K=
Nominal Ratio
ARPT =
1 (p/100 )
ARCT =
Cos (
1 (e/100 )
Where
METERS
AMMETERS
VOLTMETERS
MF FOR METER
READINGS
(LINE CTR / METER
CTR ) X METER MF
METERS
ENERGY
METERS
POWER
METERS
EXAMPLE FOR CALCULATION OF M.F : - Energy meters :1. WH Meter has DATA in Name Plate (Meter CTR = - /1 , Meter PTR = 11 KV / 110 V ,
Meter MF ( Not given )
Suppose this meter is connected to a 33 KV System of Line CTR = 400/1, Line PTR = 33
KV / 110 V
Then MF for METER Reading = (LINE CTR / METER CTR ) X (LINE PTR / METER PTR
) X METER MF
400/1 x 300
-/1
100
= 1200 for WH Reading ( Because meter is WH Meter )
1
2
Type of Meters
Terminals
CT
PT
R ,B
R,Y,B
REMARK
W1= VL I L COS ( 30 0 - )
W2 = VL I L COS ( 30 0 + )
3 , 4 Wire meters R , Y, B R , Y , B , N
W1= VPH I PH COS
W2 = VPH I PH COS
W3 = VPH I PH COS
1 , 2 Wire meters
PH
PH. , N
W = VPH I PH COS
3 , 3 Wire meters
5.2.
1
2
3
4
5
5.3.
WIND ZONE
WIND
ZONE
1
2
3
BASIC WIND
SPEED (m/Sec)
33
39
44
WIND
ZONE
4
5
6
BASIC WIND
SPEED (m/Sec)
47
50
55
Plain
Hilly
Suspension
Small/
Medium
Angle
Large Angle
Suspension
Small/
Medium
/Large Angle
spans)
400 KV
Normal
Broken
Max/
Wire
Min
Max
/Min
600/200
360/100
600/0
360/-200
220KV
Normal
Broken
Max
Wire
/Min
Max
Min
525/200
315/100
525/0
315/-200
132KV
Normal
Broken
Max
Wire
/Min
Max
/Min
488/195
195/104
488/0
195/-200
66KV
Normal
Broken
Max
Wire
/Min
Max
/Min
375/163
150/75
375/0
150/-150
600/0
600/200
1000/
-1000
525/0
525/200
1000/
-1000
488/0
488/208
960/
-960
NA
375/163
750/750
360/-300
360/100
-600/-600
315/-300
315/100
-600/-600
195/-300
192/104
576/-576
NA
150/75
450/-450
VOLTAGE
66KV
132KV
220KV
400KV
SUSPENSION
NO. OF DISCS
UTS IN KN
5
45
9
70
14
90
23
115
TENSION
NO. OF DISCS
UTS IN KN
6
50
10
120
15
120
2X23
165
PARTICULARS
DISC INSULATOR
( STANDARD TYPE)
70 KN 90
120
160KN
KN
KN
16
16
20
20
255/
280
11/13
255/
280
11/13
280
280
DISC INSULATOR
( ANTI-FOG TYPE )
70KN 90
120K 160KN
KN N
16
16
20
20
280/
305
13/15
255
/280
11/13
280
280
72/66
KV
145/132
KV
245/220
KV
420/400
KV
800 KV
Zone-I
& II
800KV
Zone-III
& IV
800KV
Zone-V
& VI
500KV
DC
Single Suspension
Insulator
Swing from Minimum
Vertical
Clearance
(mm )
( Degree )
Nil
15
30
45
Nil
15
30
45
60
Nil
15
30
45
Nil
22
44
Nil
22
45
Nil
27
55
Nil
30
60
Nil @
( V String
)
915
915
760
610
1530
1530
1370
1220
1070
2130
1980
1830
1675
3050
3050
1860
5600/5100
4400
1300
5600/5100
4400
1300
5600/5100
4400
1300
3750
Jumper
Swing
from
Vertical
( Degree )
Nil
10
20
30
Nil
10
20
30
Nil
10
20
Nil
20
40
Nil
15
30
Nil
20
40
Nil
22
45
40
Minimum
Clearance
(mm )
915
915
610
610
1530
1530
1070
1070
2130
2130
1675
3050
3050
1860
5100
4400
1300
5100
4400
1300
5100
4400
1300
1600
d75 + ls + ( V/150 )
d75 + ls + ( V/150 )
= 134522 KG/4 =
SIL (MW )
2250
614
515
614
560
155
132
50
TRANSMISSION TOWERS
A
20
Suspension
TOWER TYPE
B/SEC
C/SEC
150/ 00
300/ 00
D/DE
600/ 150
Tension
Tension
Tension
3a GROUND WIRE
525 ( 100 )
525 ( 100 ) 600 (100)
315 (100 )
315 (100 )
360 (100 )
3b CONDUCTOR
Effect of both span
525 ( 100 )
525 ( 100 ) 600 (100 )
Effect of one span
315 (100 )
315 (100 )
360 (100 )
4 WEIGHT
OF
WIRES
4a GROUND WIRE
Effect of both span
227(43 )
227(43 )
258 ( 43 )
Effect of one span
136 ( 43 )
136 ( 43 )
155 ( 43 )
4b CONDUCTOR
Effect of both span
706 ( 135 )
706 ( 135 ) 807 (135 )
Effect of one span
424 (135 )
424 (135 )
484 (135 )
5
Permissible sum of adjacent of one span
700
for deviation
20
150 700
300 700
0
0
angles
810
809
1
14
290 806
910
00
130 918
280 913
0
1027 270 1020
12
110 1137 260 1127
100 1247 250 1234
an
an
d
d
bel
bel
ow
ow
6
Design LOAD Tension in KG
6a GROUND WIRE
320 C ( Full Wind )
1640
1626/1640
1584/1640
0
0 C ( 2/3 Full Wind ) 1712
1697/1712
1653/1712
6b CONDUCTOR
320 C ( Full Wind )
2122
4287/4843
4098/4243
0
0 C ( 2/3 Full Wind ) 2406
4771/4812
4648/4812
600 (100 )
360 (100 )
600 (100 )
360 (100 )
258 ( 43 )
155 ( 43 )
807 (135 )
484 (135 )
600
590
580
570
560
550
and
belo
w
700
795
891
988
1085
1182
1428/1640
1483/1712
3675/4243
4167/4812
Up to 220
KV
400 KV
and above
Suspension
Angle
40- 90
70- 110
Dead end
Suspension
Angle
80- 130
80- 120
100- 170
Dead end
110- 150
Shield
Angle
300
200
UNIT WT Kg/
Mtr
44.1
35.8
33.8
27.3
23.5
19.7
18.2
13.4
13.4
16.6
12.1
10.7
9.2
9.6
8.2
8.2
7.3
7.3
6.8
6.8
5.3
5.3
4.9
4.9
4.0
4.0
4.5
3.7
3.3
3.3
3.0
3.0
2.7
2.7
REMARK
(USE)
Leg
Leg
Leg
Cleat
Cleat
Cleat
Leg
Leg
X A Rm
Leg
Leg
Leg
Leg
Bracing
Cleat
Leg
Cleat
Bracing
CLEAT
Bracing
Bracing
Bracing
Redundant
Bracing
Redundant
Bracing
Redundant
Redundant
Redundant
Bracing
Redundant
Redundant
Redundant
Redundant
200
200
150
450
Size/Dia
( No / mm )
Al.
Steel
6/3.0
1/3.0
6/3.66
1/3.66
6/3.99
1/3.99
6/4.22
1/ 4.22
30/3.18
7/3.18
30/4.27
1/ 4.27
54/3.35
7/3.35
30/2.924 7/2.924
30/3.353 7/3.353
42/3.595
7/1.96
54/3.280 7/13.28
26/3.72
7/2.89
30/3.92
19/2.35
42/4.57
7/2.34
54/3.51
7/3.51
54/2.69
7/2.69
6/2.36
.36
OD
(mm )
Wt.
( Kg/Km )
Brkd
( kg )
Rdc20
(ohm/km )
Amp
9
11
12
12.6
22.3
29.9
30.2
20.47
23.5
26.88
29.51
23.55
27.46
35.1
31.62
24.18
7.09
171
255
303
339
1097
1977
1804
923
1219
1218
1721
1137
1648
2185
1976
1158
106
1503
2207
2613
2923
10210
16230
14750
9080
11300
9050
14650
10180
15690
15734
16850
10210
952
0.6795
0.4565
0.3841
0.3434
0.1223
0.06756
0.06125
1.098
115
165
176
185
405
590
610
85
Size/Dia
( No / mm)
Voltage
(KV )
OD
(mm )
Area
(mm2 )
Wt.
Kg/Km
Brkd
( kg )
Rdc20
ohm/km
Amp
Al
Steel
66
14.15
118.5
394
3290
0.281
218
Dog
6/4.72 7/1.57
30/3
7/3 110, 132
21
261.5
974
9242
0.14
350.7
Panther
220
28.62
484.5
1621
13466 0.06915 510.8
Zebra 54/3.18 7/3.18
54/3.53 7/3.53
400
31.77
597
2004
16594 0.05552 571.6
Tw.
Moose
COMMONLY USED EARTH CONDUCTORS (GALVANISED )
9.54
54.55
428
5913
3.375
STEEL 7/3.15 STEEL 66 - 220
TWO
400
10.98
73.65
583
7848
2.5
STEEL 7/3..66 STEEL
Max.
Allow
Temp.0C
75
75
75
75
53
53
SIZE
10 7/1.49
20 7/2.09
30 7/2.56
50 7/3 .31
80 19/2.46
100 19/2.79
150 37/2.49
200 37/2.88
400 37/3.92
420 61/3.19
520 61/3.55
560 61/3.68
7/2.00
7/2.50
7/3.15
7 /3.81
7/4.26
19/2.89
19/3.15
19/3.40
19/3.66
19/3.94
37/3.15
37/3.45
37/3.71
37/4.00
61/3.31
61/345
31/3.55
61/3.66
61/3.81
61/4.00
Size/Dia
( No / mm )
7/1.96
7/2.21
7/2.78
7/3.1
7/3.4
7/3.66
7/4017
7/4.39
19/3.78
19/3.55
19/4.65
19/5.00
OD
(mm )
5.88
6.63
8.34
9.3
10.2
10.95
12.61
13.17
18.9
19.95
23.25
25
Wt.
( Kg/Km )
58
74
116
145
174
201
261
290
586
654
888
1025
Brkd
( KN )
2.6
4.52
7.55
8.25
11.64
12.6
14.05
15.96
34.05
35.74
48.74
52.5
Rdc20
(ohm/km )
2.156
1.093
0.6756
0.5561
0.4244
0.3915
0.3369
0.277
0.1393
0.1244
0.0917
0.0837
Standing
No./dia
(mm)
Weigh
t per
mtr
(kg)
Overal
l dia
(mm)
Total
area
sectional
(mm2)
UTS
UTS
UTS
700 kg.
N/(mm2)
1100 Kg
2
1570 Kg
N/(mm )
N/(mm2)
Mod. of
elasticity
kg/cm2
Co-efficient
of linear
expansion
per0C
1.933x106
11.50 x 10-6
7/3.15
0.429
9.45
54.552
3899
5913
8297
7/3.50
0.523
10.50
67.348
4587
7177
10243
- do -
- do -
7/3.66
0.583
10.98
73.648
4994
7848
11201
- do -
- do -
7/4.00
0.690
12.00
87.965
5985
9374
13379
- do -
- do -
19/3.15
1.163
15.75
148.069
10041
15778
- do -
- do -
19/3.50
1.436
17.50
182.801
12396
19479
- do -
- do -
19/3.66
1.570
18.30
199.897
13555
- do -
- do -
19/4.00
1.875
20.00
238.761
16191
- do -
- do -
1/5+8/3.2
0.458
11.40
71.41
8000
1.520x106
013.40x106
4
5
Profile
CATEGORY OF CLEARANCES
Unit
LV
MV
Mtr
5.8
Mtr
Mtr
Mtr
2
3
4
5
6
7
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
33
KV
6.1
66
KV
6.4
REMARK
5.8
11
KV
6.1
5.5
4.6
-
5.5
4.6
-
5.8
5.2
2.6
6.1
5.5
2.8
6.4
5.8
3.4
Rule 77 IE 1956
Do
IS 5613
Mtr
1.2
1.2
2.44
2.44
3.05
Rule 78 IE 1956
Mtr
2.44
IS 5613 ( Part
II/ Sec-I ) 1985
Mtr
13.28
11.28
13.28
11.59
13.59
12.20
IS 5613 ( Part
II/ Sec-I ) 1985
Mtr
15.28
13.28
15.28
13.28
15.59
13.59
IS 5613 ( Part
II/ Sec-I ) 1985
Mtr
2.5
2.5
3.7
3.7
4.0
Mtr
1.2
1.2
1.2
2.0
2.0
Mtr
2.75
3.7
4.0
Mtr
2.6
2.8
3.0
Rule 77 &79 IE
1956
Rule 79 & 80
IE 1956
Rule 64-2 (a)
(ii) IE 1956
do
Mtr
0.33
0.915
Mtr
0.12
0.32
0.63
Mtr
0.4
0.4
Mtr
0.4
0.4
0.75 to
1.6
0.75
Mtr
0.12
0.32
0.63
do
Mtr
15
18
Mtr
2.44
2.44
2.44
Is 5613 (Pt-2/
Sec-1 ) 1985
do
Mtr
1.5
3.0
Mtr
5.5
Mtr
3.65
Do- (Pt-2/Sec-2
)
Rule 77-4 IE
1956
IE 1956
--
30
IE 1956
Mm
50.8
50.8
50.8
127
Mm
50.8
50.8
50.8
101.6
Rule 77 IE 1956
Is 4513 (Pt-2/
Sec-1 ) 1985
IS 10118 (Pt-III
1982
IS -5613
do
7.2. DIFFERENT CLEARANCES FROM 132 KV TO 400 KV (AC) AND 500 KV (DC)
Sl.
1
2
3
4
5
6
7
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
CATEGORY OF
CLEARANCES
Clearances of Overhead Electrical
Lines across the street
Along the street
Else Where
Minimum clearance between
Conductor & Tree
Clearance to Ground at Crossing
with Tram- way / Trolley
Clearance to Ground at Crossing
with Telecom lines
Clearance to Ground at railway
crossing
1. Inside Station
2.Out Side Station
Clearance to Ground at
Electrified railway crossing
1.Inside Station
2. Out Side Station
Vertical Clearance of Overhead
Lines from any building roof
Horizo. Clearance of Overhead
Lines from any building roof
Ground Clearance in Out Door
Sub Station
Sectional Clearance in Out Door
Sub Station
Clearance from power conductor
to Earthed Metal parts
Clearance live conductor to
Earthed Metal parts of Switchgear
Phase to Phase Clearance of
Overhead lines
Unit
220
KV
7.83
400
KV
9.5
800
KV
-
500
KV
-
REMARK
Mtr
132
KV
7.01
Mtr
Mtr
Mtr
7.01
6.41
4.0
7.83
7.23
4.6
9.5
8.9
5.5
Rule 77 IE 1956
Do
IS 5613
Mtr
3.57
3.85
Rule 78 IE 1956
Mtr
3.05
4.58
5.49
7.94
Mtr
14.2
13.11
15.11
-
Mtr
16.2
14.2
18.6615.11
Mtr
4.6
5.4
7.04
Mtr
2.3
2.9
3.7
5.34
Mtr
4.6
5.5
8.8
Mtr
3.6
4.3
5.57
Mtr
1.53
2.13
Mtr
0.9
1.3
Mtr
1.35
2.3
to 5.2
Mtr
to2.7
1.35
2.3
3.4
to
6.1
3.4
do
Mtr
1.3
1.5
2.4
do
Mtr
27
35
52
Mtr
3.05
4.58
5.49
7.94
Mtr
6.1
8.5
9.0
12.4
8.5
Do- (Pt-2/Sec-2 )
Mtr
6.1
7.0
8.8
12.4
12.5
Mtr
4.3
5.1
6.4
9.4
6.75
IE 1956
30
30
20
20
10
IE 1956
Mm
Mm
Rule 77 IE 1956
Rule 77 &79 IE
1956
Rule 79 & 80 IE
1956
Rule 64-2 (a) (ii) IE
1956
do
Value
0.01-1.0
1000
10 8
Rod
Pipe
Strip
Plate
Round
Conductor
-
16 mm
12.5mm
2.5 mm
Ideal 3 to
3.5 mm
38 mm Steel
100 mm GI
2.5mm
0.5m
15m
1.5m
25x 1.6
mm Cu
25 x 4
mm
Steel
3 mm2 Cu
60x60 cm
6 mm2 Steel
Thickness
6.3 mm
Steel
3.15 mm
Cu
Value
3000 Ohm- mtr
Terms
Ambient Temp.
Value
50 0 C
Density of
Material
Max. Temp. of
Bolted joint
Soil Resistivity
Type of
Electrode
Allowable
Corrosion
7.86 gms/cc
500 0 C
100 Ohm- mtr
MS Flat ( 50 60 mm )
1 % per annum for the 1st 12 yrs and 0.5 %
for the next 12 yrs as per ISS 3043/ 1987
Earth Resistance
5 Ohm and below
Less Than 1 Ohm
Voltage Class
66 KV
Generating station
Earth Resistance
2 Ohm and below
0.5 and Below
40
39
38
37
36
35
34
33
32
31
30
29
28
27
26
25
24
23
22
21
20
19
18
17
9.2 SAG AND TENSION TABLE for WEASEL & RABBIT CONDUCTOR
SPA
ACSR 7/2.59mm WEASEL
N
SAG ( Mtr) TENSION (Kg )
60
0.401
143
80
0.681
150
100
0.997
160
120
1.35
170
140
1.75
178
160
2.189
187
0.4
Code name of
Conductor
Gnat- AAC
( 7/2.21 )
Ant AAC
450
35
34.6
0.4
( 7/3.10 )
Weasel - ACSR
1070
0.0897 0.0868
11
Rabbit ACSR
1070
0.0590 0.0589
11
Raccoon ACSR
1070
0.0450 0.0435
11
Weasel - ACSR
1368
0.0100 0.0098
33
Rabbit ACSR
1368
0.0068 0.0067
33
Raccoon ACSR
1368
0.0053 0.0050
33
Dog - ACSR
1368
0.0044 0.0041
33
Coyote - ACSR
1368
0.0038 0.0037
33
Weasel - ACSR
1520
0.00986 0.0101
33
Rabbit ACSR
1520
0.0069 0.00675
33
Raccoon ACSR
1520
0.00531 0.00504
33
Dog - ACSR
1520
0.0045 0.00412
33
Coyote - ACSR
1520
0.0037 0.0034
33
1. Regulation is taken at Temp. 0f 45 0 C
2. % Regulation for 100 KVA/ Km
= ( Voltage drop in line x 100 ) / Per phase Voltage
De = Equivalent Spacing = ( D1 x D2 x D3 ) 1/3
33
0.0840
0.0502
0.0337
0.0097
0.0055
0.0037
0.0028
0.0022
0.0092
0.0055
0.0037
0.0028
0.0022
9.4 SAG AND TENSION TABLE for RACCOON & DOG CONDUCTOR
SPAN
60
80
100
120
140
160
ACSR 7/4.09mm
RACCOON
SAG ( Mtr)
TENSION (Kg )
0.433
331
0.708
360
1.03
386
1.395
411
1.80
433
3.25
453
400 V
11KV
33KV
AAC 16 mm2
AAC 30 mm2
ACSR 7/2.59mm
ACSR 7/3.35mm
ACSR 7/4.09mm
ACSR 7/2.59mm
ACSR 7/3.35mm
ACSR 7/4.09mm
ACSR 6/4.72mm +
7/1.57
ACSR 26/2.54mm +
7/1.91
Equ. Spacing in
mm De
450
450
1216
1216
1216
1216
1520
1520
1520
1520
21622
26470
45455
Type
Twin Core
Wires
Phase
( 1/1.4 mm) / 1.5 mm2
Neutral
( 1/1.4 mm) / 1.5 mm2
Twin Core
Twin Core
( 1/3.55 m) /
10 mm2
Single Core ( 1/1.8 mm) / 2.5 mm2
( 1/3.55 mm)
( 1/1.24 mm)
( 1/1.8 mm)
7/3mm
7/3mm
3.
Rating of
Transformer
25 KVA
63 KVA
100 KVA
IRON
LOSS
0.0365
0.085
0.130
0.195
0.28
0.31
0.50
0.615
0.720
0.850
1.28
COPPER
LOSS AT F.L
0.35
0.40
0.65
0.92
1.23
1.7
2.1
2.6
3.4
3.9
5.8
COPPER LOSS AT
75 % F.L
0.197
0.213
0.366
0.52
0.68
0.965
1.18
1.46
1.90
2.19
3.25
No. &
Size
(mm )
14/0.3
22/0.3
36/0.3
Current
Capacity
11
14
19
Nominal
Area in
mm2
4
6
56/0.3
85/0.3
26
33
No. &
Size
( mm )
1/1.4
1/1.8
Current
Capacity
15
20
Nominal
Area in
mm2
4
6
No. &
Size
( mm )
1/ 2.24
1/ 2.80
Current
Capacity
27
34
9.12 RELAY COORDINATION CHART/ PROCEDURE FOR O/C AND E/F RELAY
SETTING.
1. DATA REQUIRED
3Ph. Fault MVA for O/C Relay setting
Single Line to Ground Fault MVA for E/F relay
CTR used
Relay Characteristics
2. STANDARD DATA TO BE USED
Operating Time$ can be selected as follows
System Voltage in KV Operating Time in Second
11
0.25
33
0.5
132
1.0
220
1.25
$ The selection and choice of the operating time of the relays depend upon the type of
protection scheme used in the system and type of radial system and type of relay used
in the system.
PSM of O/C relay
It is to be selected according to the load required by the system and thermal
characteristics of the line conductor
Standard allowable OVER LOADING FACTOR is ( 1.25 to 1.5 )
PSM of E/F relay
It is to be selected according to the residual current and allowable unbalance current in
the a system
EXAMPLE OF AN
EXAMPLE 1
Suppose 3 Phase fault MVA = 1000 MVA
Single line to Ground fault MVA = 750 MVA
CTR used = 500/1
3 Secs of IDMT characteristics is in use
OT =
3 TDS
log10 CM
3 TDS
log10 CM
0 .5 =
3 TDS
log10 46.65
TDS = 0.278
0.3
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
STANDARD COPPER
CONDUCTOR
AREA
( SQ.
mm )
STRAND
( mm )
SWG
CODE
2 SC CABLE
IN CONDUIT
THROUGH OR
CASING
1.00
1.25
2.00
3.00
4.5
6.75
10.00
14.00
18.00
25.00
-
1/1.12
3/0.737
3/0.914
7/0.737
7/0.914
7/1.12
7/1.35
7/1.65
19/1.15
19/1.32
-
1/18
3/22
3/20
7/22
5
10
15
20
20
27
28
34
36
43
53
59
62
69
74
91
7/20
7/18
7/17
7/16
19/18
19/17
Bunched In Free
Air Or Open
Trench
2 SC
3 or 4 SC
cable
cable
5
5
10
10/9
15
13/12
20
15
20
17
27
24
28
25
34
31
36
32
43
39/38
53
48
59
54
62
46
69
62
74
67
91
82
ONE
TWIN
CORE
ONE
CORE
FOR 3
PHASE
5
10
15
20
20
27
28
34
36
43
53
59
62
69
74
91
5
8/7
11/10
15
14
19
20
24
25
30
37
42
43
48
52
62
STANDARD
ALUMINIUM
CONDUCTOR
AREA STRAN
( SQ.
D
mm )
( mm )
1.5
2.5
4.0
5.0
6.00
16
25
35
50
1/1.40
1/1.80
1 /2.24
1 /2.80
1/3.55
7/1.70
7/2.24
7/2.50
7/3.00,
19/1.80
SL.
NO
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
STANDARD COPPER
CONDUCTOR
AREA
( SQ.
mm )
STRAND
( mm )
SWG
CODE
2 SC CABLE
IN CONDUIT
THROUGH OR
CASING
40.00
50.00
65.00
70.00
95.00
130.00
160.00
200.00
260.00
325.00
500.00
670.00
19/1.65
19/1.83
19/2.11
37/1.65
37/1.85
37/2.15
37/2.36
37/2.62
61/2.36
61/2.62
91/2.62
127/2.62
19/16
19/15
19/14
37/16
37/15
37/14
37/13
37/12
61/13
61/12
91/12
127/12
Bunched In Free
Air Or Open
Trench
2 SC
3 or 4
cable
SC
cable
97
88
125
107
134
118
143
138
160
140
177
158
184
170
205
185
210
185
246
216
250
220
290
248
293
260
335
295
364
302
425
360
435
372
480
410
480
411
565
484
610
620
704
630
ONE
TWIN
CORE
ONE
CORE
FOR 3
PHASE
97
115
118
135
140
158
162
180
181
209
218
240
252
284
281
342
-
68
78
82
94
98
109
114
126
127
146
153
169
178
199
202
240
-
STANDARD
ALUMINIUM
CONDUCTOR
AREA STRAN
( SQ.
D
mm )
( mm )
70
95
120
150
185
225
300
400
500
625
-
19/2.24
19/2.50
37/2.06
37/2.23
37/2.50
37/2.80
61/2.50
61/3.33
91/2.65
61/3.00
-
10 DATA ON SUB-STATION
10.1 BREAKING CURRENT AND FAULT MVA CAPACITY.
Voltage
132
220
400
765
10.2 NORMAL BUS BAR SIZE, BAY LENGTH & BAY WIDTH
Voltage
33 KV
132KV
220KV
Rigid Bus
40 mm
Al. Pipe
80 mm
Al. Pipe
80 mm
Al. Pipe
Duplex
Bay width in
mm
Bay length in mm
5550
28350
10400
44300
17000
63400
10.4
Voltage
KV
72.5
145
245
420
STRAIN BUS
Bus conductor
Lynx ACSR
Kundah ACSR
19/3.53 AAC
Panther ACSR
Kundah ACSR
19/4.22 AAC
Moose ACSR
Kundah ACSR
19/5.36 AAC
37/5.23 AAC
Moose ACSR
I = K A 1 / t 10 4
I = Symmetrical RMS Current in Amp.
A= Cross sectional area in inches
t= Time in Secs , K= Co-efficient of alloys at Max. Temperatures
Max. Temp in degree centigrade Value of K for different aluminium alloys
200
5.50 to 5.71
250
6.28 to 6.52
300
6.94 to 7.18
Note ;- For general practice the temperature of rigid aluminium bus to 1000 C and for
emergency rating 2500 C for short circuit duty.
Vibration in Bus
f= ( K2/ 24L2 ) x ( Eim/ M )1/2
f= Natural frequency of span in HZ
L= span length in feet
E= Modulus of Elasticity PSI
m=Moment of Inertia ( in 4 )
M= Mass per unit length
Short circuit Force in BUS
For line to line fault
Fsc =
37.4 I 2 sc
107 D
43.2 I 2 sc
107 D
Description of
Unit
System Voltages
Technical Particulars
33
132
220
400
Normal System
KV rms
Voltages
36
145
245
420
Max. System
KV rms
Voltages
70
275
460
520
Power frequency
KV rms
630
Withstand
Switching Surge withstand Voltage ( for 250/2500ms )
Not
Not Appl.
Not
1050
1.Line to Earth
KVp
Appl.
Appl.
900 + 345 KV
2. Across isolating
rms
gap
5
1.Line to Earth
2.Across isolating gap
6
7
8
9
10
11
12
13
14
15
DRY
WET
Frequency
Vibration frequency
Corona Extinction
Voltage
Radiation Interface
Voltage
System Neutral
Rating
Continuous Current
rating
Sym. Short Circuit
Current
Duration of Short
Circuit Current
Dynamic Short
Circuit current
16
17
18
19
20
21
22
23
Phase to Ground
Phase to Phase
Design Temp
Pollution Level as per
IEC 815 & 71
Creepage distance
Max. fault clearing
Time
Bay Width
Height of bus equip .
connection from
ground
Height of strung bus
bar
1000 V at 1000 V at
93 KV
167 KV
Solidly earthed
1425
1425+240rms
520
610
320
1000 V at 266
KV
Amp
600
800
1600
1600-2000
KA
25
31.5
40
40
Sec
62.5
79
100
100
KAp
6.5
7.0
Mm
msec
900
150
3625
100
6125
100
10500
100
Mtr
Mtr
5.5
4
10.4- 12
5
16.4-18
5.5
27
8
Mtr
5.5
10
> 15
PLACES
Switch Yard
Control Room,
Carrier Room, LT Panels, Charger Room, Offices, Conference
Room, Rest Room, Work Shop, Repair Bay etc
Battery Room, Corridor, PLCC Room, Toilets, Store Room, Cloak
Room, stairs etc..
ILLUMINATION LEVEL
(LUX )
25
300-500
300
100
VOLTAGE
132 KV
220 KV
400 KV
AS PER IEGC
MAX
145 KV
( + 10 % )
245 KV
( + 10 % )
420 KV
(+5%)
MIN
120 KV
( - 10 % )
200 KV
( -10 % )
360 KV
( - 10 % )
Indian
Standards
1.
IS 2261975
2.
IS 2691976
Title
International
Standards
Sl N
Indian
Standard
Title
Technical
supply
conditions for
threaded
fasteners.
Method of
tensile testing
of steel wires
Internatio
nal
Standards
ISO 68921984
3.
Is 3831970
CSA
A23.1/A23.2
17.
IS 30431972
4.
Specification for
aluminum conductors
for overhead
transmission Purposes
ICE 1089-1991
BS 215-1970
18.
IS 31881965
b) IS 3981982 PartII
Aluminum conductor
galvanized steel
reinforced
BS 215-1970
ICE 1089-1991
19.
IS 40911967
Aluminum alloy
standard conductor
BS 3242-1970
ICE 1089-1991
ASTMB399M
86
20.
IS 5613
(PartII/Sec-1)1985
(Part-III
/Sec1)1989
Aluminum conductor
galvanized steel
reinforced for extra
high voltage (400 KV
and above
BS 215-1970
IEC 1089-1991
21.
IS 5613
5.
IS 2781978
Specification for
barbed wire
ASTM A 121
6.
IS 4561978
ISO 3893-977
7.
IS 7311971
BS 137-1982
22.
(Part-I&II) IEC
383-1993 (Part
I & II)
8.
a. IS 8021995
(PartI/Sec.I)
(Part
I/Sec.II)-
IEC 826
ANSI/ASCE
10-90 (1991)
BS 8100
23.
(PartII/Sec-2)1985
1985(Part
III/Sec.2)
-1989
Is 66391972
Is 67451972
Code of
practice for
earthing (with
amendment no.
1 and 2)
Dimensions for
disc insulators
IEC 3051978
ANSI/AS
CE 10-90
(1991)
Code of
practice for
design and
construction of
foundation for
transmission
line towers and
poles.
Code of
practice for
design, install.
And maintain
of overhead
power lines
(Section 1 :
Design)
Code of
practice for
design,
installation and
maintenance of
overhead
power lines
(Section 2
Installation and
maintenance)
Hexagonal
bolts for steel
structure
Methods for
determination
of wt. Of Zn.
Coating of zinc
coated iron and
steel articles.
ISO/R
272-1968
ASTM A
394 CSA
B 33.4
ASTM
A90 ISO
1460
1992
b. IS 8021978 (PartII)
c. IS 8021978(PartIII)
Is 1363
ANSI/ASCE
10-90 (1991)
24.
IS 26331972
ANSI/ASCE
10-90 (1991)
IEC 652
25.
IS 1367
BS 1559-1949
26.
Part III
IEEE 693
27
Part VI
9.
IS 17781980
10
.
IS 18931965
Criteria of earthquake
resistant design of
structures.
11
.
IS 20161967
Plain washers
12
.
IS 2121
Specification for
conductor and earth
wire accessories for
overhead power lines.
Armour rods, binding
wires and tapes for
conductors.
Mid span joints and
repair sleeve for
conductors.
Part-I 1981
13
a)
13
b)
Part-II
1981
13
c)
Part-III
1992
13
d)
Part-IV
1991
28.
29
30.
31
Hexagonal
head bolts,
screws and
nuts of product
Grade C
Testing
uniformity of
coating of zinc
coated .
Tech. Spec.
Condns. for
threaded steel
fasteners
Mechanical
properties and
test methods
for bolts,
screws and
stud studs with
fully load
Mechanical
properties and
test methods
for nuts with
full load ability
Indian
Electricity
Rules 1956
Indian
Electricity Act
1910
IS 18881982
Method of load
test on soils
IS 29111979
(Part-I)
Code of
practice for
design and
construction of
pile
foundations.
Recommended
practice for hot
dip galvanizing
of iron and
steel.
Quality
management
and quality
assurance
standards
IS 26291966
IS 140001994
ASTM A
123
CAN/CSA
ISO 898-1
ISO/DIS
898/II
ASTM A
123
CAN/CSA
G164
BS729
ISO 90001994
14
.
IS 2486
Part-I
Part-II
Part-III
Sl
N
o.
1.
2
3
Sl
N
o.
Indian
Standards
Specification for
insulator fittings for
overhead power lines
with nominal volt age
greater than 1000V
General requirements
and tests
Dimensional
requirements
Locking devices
33.
BS 3288 IEC
1284
34
Method of
standard
penetration test
for soils
ASTM D 1883
GRIDCO
safety manual
(draft) 1997
B) POWER TRANSFORMERS
Title
Sl
Indian
No.
Standards
IS 1885 (Pt
38)1977
IS 2026
(Pt 1)1977
IS 2026
( Pt 2
)1977
IS 2026
( Pt 3
)1981
IS 2026
( Pt 4
)1977
IS 2026
( Pt 5
)1994
Indian
Standards
IS 2131
1967
IS 6600
/1972
IS
10561/1983
IS
11171/1985
10
IS 10028
( Pt 1 ) 1985
11
IS 10028
( Pt 2 ) 1985
12
IS 10028
( Pt 3 ) 1985
Title
Title
Sl
No.
Indian
Standards
Maintenance
Title
C) INSTRUMENT TRANSFORMER
1
IS 1885(
Pt-28 )
1993
IS 2705
( Pt 1
)1992
IS 2705
( Pt 2
)1992
IS 2705
( Pt 3
)1992
IS 3156
( Pt 2 )1992
Voltage Transformer
Measuring VT
IS 3156
( Pt 3 ) 1992
Voltage Transformer
Protection VT
IS 3156
( Pt 4 ) 1992
Voltage Transformer
Capacitive VT
10
IS 4146
1983
IS 2705
( Pt 4
)1992
IS 3156
( Pt 1 )
1992
11
Is 4201/1983
12
IS 5547
/1983
D ) CIRCUIT BREAKERS
High Voltage AC Circuit Breaker
7
IS 2516 ( Pt1 / Sec1 ) Pt
1 & 2 / Sec 1
) :1985
IEC 56
:1987/IS
13118:199
1
IEC376:1971/
IS 13072
:1992
IEC 427 :
1973/ IS
13516
:1993
IEC- 694
:1980
IS 12729
/1988
IS 7567 :
1982
10
IS 9135:
1979
IS 1885 (
Pt 17 ) /
1979
11
IS 10118 (
Pt 1 to 4
:1982
IS 12032 (
Pt 7 )
/1987
IS 335 :
993
10
IS 6104 /
1971
IS 1448 (
PT 10 )
1970
11
IS 6262
:1971
IS 1448 (
PT 16 )
1970
12
IS
6792:1992
IS 1448 (
PT 21 )
1970
IS 1448 (
PT 25 )
1970
13
IS 6855
:1973
14
IS 9434
:1992
IS 1886
:1983
15
IS 10593
:1992
IS
6103:1971
16
IS 13567
:1992
IS 12463
:1988
17
IS 13631
:1992
IS 2362 :
1973
18
IS 12177:
1987
IEC 129
F) ISOLATORS
AC Current Isolators ( Disconnectors and 4
Earth Switches
2.
IS : 3921
Pt 1 /1981
IS : 3921
Pt 2 /1982
IEC: 99-4
1
2
IEC: 99-1
IS : 3921
Pt 3 /1982
IS : 3921
Pt 4 /1985
AC Current Isolators
( Disconnectors and
Earth Switches FOR
voltages above 1KV
(General &Definitions)
Construction
-do- (Type Test &
Routine Test
IS : 3921
Pt 5 /1985
G) SURGE ARRESTERS
Specification for Surge Arresters without 3
IEC 270
gap for AC System
Non Linear Resistor type gapped arresters 4
IS : 3070
for AC Systems
(Pt-3 ) /
1993
Partial Discharge
Measurement
LA for AC Systems
Specification for Metal
Oxide LA without gap. )
RULES
TITLE
2 (av ) Definition of Voltage
50
54
55
56
57
58
74
75
RULES
TITLE
Max. Stresses and Factor of
76
Safety in Overhead lines
Supply and Use of Energy
Clearance above ground of the
77
lowest Conductor
Declared Voltage of Supply to
Clearances from buildings of
79
Consumer
low and medium Voltage lines
and Service Line
Declared Frequency of Supply to
Clearances from buildings for
80
Consumer
HT, EHT lines
Sealing of Meters and Cut-outs
General Clearances
83
Meters, Maximum Demand Indicators
Routes, Proximity to Aerodrome
84
and other apparatus on Consumers
premises
Point of Commencement of Supply
Max. Interval between supports
85
Materials and Strength in Over head
Line Crossing or Approaching
87
lines
each other
Joints in Overhead lines
Sl.No. DATA
1
DC Supply required for Carrier Set
2
AC Current required for single
Carrier
3
Characteristic Impendance of Coaxial cable
4
Capacitance of CC/CVT
VALUE
48 V
1A
75/125 ohm
4400pF (220 KV)
5575/6000 Pf
( 132 KV )
0.5 mH (132 KV)
1 mH ( 220 KV )
630/800/1200 A
Carrier Type
ETI
ETL
BPL
PUNCOM
Frequency ( Hz )
3600
3780
3570
3923
Interface 1
Protection
Relay
Interface 2
Teleprotection
equipment
Interface 2
Interface 1
Teleprotection
equipment
physical
link
Protection
Relay
Telecommunication system
Teleprotection system
AF Signal
Signal levels
Absolute Voltage
levels at the test
sockets TXAF
(-10dBr)
dBmO Weighti
dBu
ng
0
1.0
-10
+3
1.41
-7
-14
-11
-8
-3
0
-3
0
+10.8
0.2
0.28
0.4
0.71
1.0
0.71
1.0
3.48
-24
-21
-18
-13
-10
-13
-10
+0.8
-6
0.5
-16
FORMULA
10 log (Px)/1mW
20 log (Ux)/775mV
UNIT REFERENCE
dBm P0 =1mW
dBu
U0 =775mV
Magnitude of diff.
dBr
Reference=0dBr
w.r.t.vertual
reference
point(0dBr)
Absolute signal
Magnitude of diff.
dBmo Reference=0dBr
Level(L0)
w.r.t.vertual
reference
point(0dBr)
Conversion to another
$ Lu= L ( dBm ) system impedance Lu
10 log
( 600 ohm / Z
ohm )
$ Example = The power level at 75ohm RF O/P of a PLC equipment is
given 40 dBm. Then the voltage level Lu would be = Lu= 40 ( dBm ) - 10
log ( 600 ohm / 75 ohm ) =31dBu
5
6
7
8
10
Data
Value
Channel ( Bd )
Maximum Baudrate (Bits/s)
Nominal Baudrate(Bits/s)
ITU-T Channel
Channel bandwidth / spacing Hz
Lowest center frequency Hz
Highest center frequency Hz
Frequency shift Hz
Maximum isochronous distortion:
at nominal baudrate %
at maximum baudrate %
with receive level margin of dB
Regenerator On
Receive distortion % < 25 %
< 50 %
Channel delay times:
Propagation delay ms
Max RTS On to DCD On delay
ms
Max RTS Off to DCD Off delay
ms
RTS On to CTS On channel
dependent delay a) ms
TX channel turn-off time ms
(for half-duplex operation)
Maximum 2-wire attenuation:
No frequency gap
120 Hz frequency gap
with own channel & <15% dist.
Maximum 4-wire attenuation: dB
Signal to noise ratio:
for bit error rate of dB 10-3
10-4
10-6
measured with ITU-T V.52
Noise bandwidth Hz
50
75
50
R.35
120
420
3900
30
100
150
100
R.37
240
480
3840
60
200
225
200
R.38B
360
540
3780
90
200
200
200
R.38A
480
600
3840
120
300
300
300
5
8
5
5
8
5
7
8
5
5
5
5
8
8
5
3
5
3
5
3
5
3
5
3
5
30.5
67.0
18.3
36.0
13.5
24.0
11.4
19.0
10.5
16.0
54.0
45.0
31.0
24.0
22.0
60.0
30.0
15.0
15.0
10.0
20.0
12.5
7.5
5.6
4.4
20
35
30
38
25
35
30
38
25
38
40
40
40
40
40
12.5
12.5
11.5
12.5
11.0
14.5
14.5
13.0
14.5
13.0
16.5
16.5
15.5
16.5
15.5
50
100
200
200
300
480
600
3840
120
RELAY
MEANINGS
MEANINGS
INDICATIONS
ENGLISH ELECTRIC MR3V &RR3V
Phase A B Shorted
Zone 1 Fault
30 (A-B )
30 G
Phase B C Shorted
Zone 2 Fault
30 (B-C )
30H
Phase C A Shorted
Zone 3 Fault
30 (C-A )
30J
Phase A with Earth Fault
Distance Relay Operated
30 A
86Y
Phase B with Earth Fault
CB Lockout
30 B
186A,186B
Phase C with Earth Fault
Auto Reclose operated
30 C
VARM
ENGLISH ELECTRIC SSM3V
Phase (R- Y ) Shorted
Zone 2 Fault
R
Zone II
Phase (Y- B) Shorted
Zone 3 Fault
B
Zone III
Zone 1 Fault
Aux. Relay Trip
Zone I
86 X
ENGLISH ELECTRIC MM3V
SAME AS MR3V & RR3V RELAY WITH FOLLOWING INDICATIONS
Aux. Relay for MHO
Aux. Relay for MHO
Y3AXX
Y3CXX
Start
Start
Aux. Relay for MHO
Carrier Receive
Y3BXX
85X2
Start
ENGLISH ELECTRIC PYTS (Static )
LED
LED
Phase Faults
Zone 3 Fault
Zone III
A, B, C
Zone 1 Fault
Switch on to Fault
Zone I
SOTF
Zone 2 Fault
Power swing Block
Zone II
PSB
LED
A, B, C
Zone 2
Zone 3
30 A
30 B
30 C
30D
30 G
ABC
AB
BC
CA
Zone I
SOTF
V ~ fail
86 BX
Zone 1 Fault
ENGLISH ELECTRIC SSR3V
Phase Fault
Zone II
Phase A B Shorted
Zone III
Phase B C Shorted
186A,186B
Phase C A Shorted
86 X1
Zone 1 Fault
85X1
Zone 2 Fault
Zone 3 Fault
Distance Relay Operated
Relay operated in
Remote Scheme
Zone 2 Fault
Zone 3 Fault
CB Lockout
Aux. Relay with Zone
1(Carr. Receive)
Switch on to Fault
ZM1
ZM2
ZM3
ZM3R
PSR
PSS
PST
CRZ
Trip zone 1
Trip zone 2
Trip zone 3
Trip zone 3Reverse
Carrier aided Trip
Trip Weak end Infeed
Trip Switch on to Fault
Trip Stub Protection
Carrier Send
TROC
Trip on O/C
TRULOW
PSB
SUP
VTS
START
TRVTF
TRIP3PH
TRBL
TRIPZ
VTF
CSZ
ECHO
PAR
PAS
PAT
PD
PE
PtaE
PTA
PS II
PS III
PtaW
PSW
Trip RST
ZA
CM
RLv
PSA
3 Ph. Fault
Zone 2 Fault
V
Zone 3 Fault
W
Breaker Trip with
Wa
Recloser
Switch over to Lockout
ABB REL 316
General Trip of Phase
Delay 2
Trip CB 1P
Trip CB 3P
Trip CB R
Delay 3
Delay 4
Start R + S + T
Trip CB S
Trip CB T
Trip CB
S Phase fault
T Phase fault
Gen Trip of Phase R.S.T
Start R
Start S
Start T
Carrier Started
Tripping initiated from
internal Relay
Impedance Start Relay
Rotating Field Relay
O/C Relay for E/F
Distance Step contactor
for Overlap
Aux. Current
Transformer
Balancing Transformer
Auto Reclose Switch
Manual switch for
Overlap
SOTF
Delay 1
LED CON.
ADDRESS
5701
5703
5705
5707
5709
Signal received
Signal Transmitted by
PLCC
Start OC
3 Ph. Trip
VT Sup
Tr Switch on to Fault
Zone 1 Time Delay
ALSTOM PD 521
LED CON.
ADDRES
LED Func Assgn. H1
5713
LED Func.Assgn. H2
5715
LED Func Assgn. H3
5717
LED Func.Assgn. H4
5719
LED Func Assgn. H5
5721
LED Func Assgn. H6
5723
5711
Fault Signals
Fault Signals
3600
3601
3602
3603
3604
3605
3609
3613
3614
P.O
R,Y,B
E
Ic
PO
Pt
R,S,T
E
T
LED
EN
INSTANT
TIME
COMM
General Start
Starting A
Starting B
Starting C
Starting Ground Fault
General Trip Signal
Dist. Trip Signal
Back Up O/C Start
Back Up O/C Trip
3618
3619
3635
3626
3627
3628
3629
3670
3671
Zone 2 Fault
Zone 3 Fault
Non- Dirrectional
Zone 4 or Level 4
A Phase involved
B Phase involved
C Phase involved
Zone 2 Fault
Zone 3 Fault
Lock Out Relay
Zone 1,2,3
Phase Faults
Earth Faults
SOTF
1
G
Q
Zone 2 or Level 2
Zone 3 or Level 3
51
50
DISPLAY
AG,BG,CG
DISPLAY
Phase to Ground Fault
AB
BC
AB Phase Fault
BC Phase Fault
CA
CA Phase Fault
TWO PHASE TO
GROUND
SAME
SAME
3 Phase Fault
Zone Mho or Quadr.
Zone Phase Dist. Inst
Zone Dist. Time Delay
ABG
BCG
CAG
ABCT
Z1G,Z2G,Z3G
M1P,M2P,M3P
Z1GT,Z2GT,Z3GT
21L (R-Y )
21L (Y-B)
21L (B-R )
21GR
21GY
Dec A
Dec B
Dec C
Dec M
Dec f
Sel A
Sel B
Sel C
Aval
Amo
Ground involved
Negative Sequence
Current
Time O /C
O/C High Set
M1PT,M2PT,M3
PT
LOP
67Q1,
67Q2,67Q
67N1,67N2,67N3
67Q2T,67Q3T,67
Q4
3P27
50H
50Q1
50N1
3PT
3P59
85GX
Phase Y Fault
21 LX
ALSTOM, EPAC 3100/3500
Phase A tripping
\Z1
Phase B tripping
Z2
Phase C tripping
Z3
Phase B Fault
Timer for 21G Relay
Carrier Tripping For
Phase Fault
Carrier Tripping For
Ground Fault
Timer for 21L Relay
Zone 1
Zone 2
Mro
Poly
Mono
Tele
Ffus
Zone 3
Start up
Multi Phase fault
One Phase Fault
Carrier Send
Fuse Failure
Forward Direction
Reverse Direction
Varc
Dpom
Hourly/Continuous
2. Electrical Testing
1.Temp. Monitoring
2.Electrical
Parameters
3.Oil Flow ( OFAF )
Daily
1.Oil Levels in
Transformer
2. Cooling System
3. Breather Reagent
Quarterly
Half Yearly
Yearly
1.Bushings, OTI,
WTI, other
Equipments
2. Oil condition in
Transformer
1. DGA of Oil
1. Electrical Testing
2. PI , Tan value
3. DGA
4. Detail Checking of
Clamps, joints etc.
5. OLTC
Notes on Checking
1. All Components
( OLTC, PRV,
Bushing others )
2. Routine Test
1.Reading of OTI,
WTI
2.Voltage, Current,
Loads
3.Ensure about the
flow
1. Check up to
Level
2. check contacts,
bearings etc
3. Check Colour of
Reagent
1. Clean the Tank,
Bushing
and Trial operation
of components
2. Dielectric
Strength of Oil
1. Check Sample of
Main Tank Oil and
OLTC
1. Routine Test
2. Record Values
3. DGA Analysis
4. Check
5. OLTC Checking
Actions to be taken
1.Compare with
factory value.
1. Top up Oil if
required
2. change or replace
the faulty parts
3. Change Reagents
1. Suitable Action
Periodicity Checking/Testing
Daily
1.Oil Leakage
2. Abnormal Noise
3. Other visual check
Actions to be taken
Follow up action
Monthly
Yearly
1.Oil level
2. Terminal checking of Marshal
box.
3. Current reading of Secondary
circuits
1. IR Value
2. All Connections
3. Earth Resistance
4. Tan Value
5. Cleaning of insulators
14.3CVTs and PT
Periodicity Checking/Testing
Daily
1.Oil Leakage
2. Abnormal Noise
3. Other visual check
Actions to be taken
Follow up action
Monthly
Yearly
1.Oil level
2. Terminal checking of Marshal
box.
3. Voltage reading of Secondary
circuits
4. Earthing of PLCC Link
5. HF Bushing
1. Capacitance Measurement
2. All Connections
3. Earth Resistance
4. Cleaning of insulator
DAILY
WEEKLY
ITEMS TO BE
CHECKED
1. Measure
and
record the pilot
cell Voltage, Sp.
Gravity
&
Electrolyte
Temperature
2. Battery Voltage
by Switching off
Charger
3. Hourly reading
DC
Voltage,
Charger out put
current
and
Trickle Charge
Current
1. Cleaning
of
terminals,
topping
up
distilled water if
required
2. Check pilot cell
reading
and
adjust the trickle
charge current if
required
PERIODICITY
MONTHLY
YEARLY
ITEMS TO BE
CHECKED
1. Sp.
Gravity,
Voltage of each
cell
and
electrolyte
Temp.
2. Give Equalizing
Charge
3. Switch
off
Charger
and
test tripping/
closing of any
one
feeder
from Battery
Source
4. Check
all
connection of
battery
and
Charger
1. Allow Condition
Charging
2 Sulphation
Under Charging
Over Discharge
Too strong /Weak Acid
Too Rapid Discharge
Short Circuit
Plate Exposed to Air
REMEDIES
1. Remove Electrolyte
2. Pour Distill Water
3. Refill with New Electrolyte
1. Initial stage, repeat the low rate Charging and
Discharging.
2. Latter stage, Special treatment should be provided
Actions to be taken
1. Record purpose
2. within the Green zone
3. Like Crack, damage
1. within the Limit
2. Compare Results
Compare with Initial Results and Follow up action