Professional Documents
Culture Documents
Case Study Testing of Micom p220 Relay
Case Study Testing of Micom p220 Relay
Panels supplied for different types of HT motors by BHEL Bhopal generally consist
of MICOM P220 relay make AREVA. These relays are numerical relays and consist
of all types of motor protections.
Testing of these relays before commissioning of motors is required at site. In
these relays there is locked rotor protection which is checked during the relay
testing at site.
There are two types of protection are incorporated, these are LOCKED ROTOR,
EXCESS LONG START.
So this function simply depends on the current taken by motor. As during locked
rotor condition current of the motor goes on increasing as the current reaches
the setting value the protection act and trip the motor.
NOTE: Motor Stalled protection will act after the time delay obtained by
the addition of delay time provided in the setting of locked rotor during
start up and the time delay setting provided for rotor stalled during
normal run.
Testing Procedure:
The EXCES LONG START function protects the motor if the starting phase lasts
too long. To do this, it uses a starting current threshold Istart> and a starting
time delay tIstart. This threshold and this time delay can be adjusted to allow the
starting current to pass.
The MiCOM P220 relay uses following things for motor start-up detection:
Closure of the contactor/circuit breaker, or
Closure of the contactor/circuit breaker and overshoot of the starting current
threshold [Istart].
Here in GIPCL SLPP Mangrol we have done setting of both breaker contact and
over shoot of the starting current (52A+I).
It is deactivated on expiry of the starting current time delay tIstart.If, on expiry
of the time delay tIstart, the current consumed by the motor has not fallen below
the threshold Istart> again, a prolonged start signal .LONG START t Istart will be
generated and it will trip the breaker.
For testing Excess Long start protection on Micom P220 relay we have to feed
Threshold current setting value along with breaker contact to relay terminal for
start up detection. The detection of breaker closed state should be provided
within 90 milliseconds along with threshold value of current otherwise it will not
detect the start up condition of motor. For providing breaker closing status
within 90 millisecond we have to loop positive terminal of 220 volts
with binary input of omicron kit to terminal 22 of the relay and
negative of 220 volts is fed directly terminal 24 as shown below in
diagram 1.0.
Here in SLPP Mangrol breaker contact looping with relay terminal 22 and 24 was
not provided, this was done on site for taking this protection on line.
(-)110 volts
(52A)
22(+)
Breaker close/open status at
relay terminal
Aux 220
volts
24(-)
MICOM P220
RARE SIDE VIEW
DIAGRAM 1.0