Professional Documents
Culture Documents
Lampiran 1 Perhitungan
Lampiran 1 Perhitungan
PERHITUNGAN
Tabel 4.1 Data Hasil Pengamatan Cooling Tower
Q(kW) Mv(g/s) X Temperatur
H2O T1 T2 T3 T4 T5 T6
(mm )
20 20 30,0 28,2 36,2 34,5 41,0 31,0
0,5 30 20 31,2 28,2 36,9 35,3 41,0 31,5
40 20 30,2 28,7 37,3 36,2 41,0 30,5
20 20 30,2 29,4 38,7 35,7 50,0 35,5
1,0 30 20 31,9 28,3 38,9 36,3 50,0 34,2
40 20 30,7 28,4 39,2 36,5 50,0 34,3
Keterangan
T 1 = Temperatur dry bulb masuk
Diketahui :
1. Orifice Constant
Rumus :
ma
= 0,137 x
Vb
Keterangan :
ma = Dry air mass flowrate (kg/s)
H2O
x = Orifice differential (mm )
Vb = Specific volume of steam and air mixture leaving top of column ( m /kg )
3
Number of decks =8
Number of plates per deck = 18
2
Total surface area of packing m = 2,16
T3
Temperatur dry bulb udara keluar ( ) dan temperature wet bulb keluar (
T4 Vb 3
) pada physcometric chart, maka diperoleh = 0,92 ( m /kg )
= 0,137 20
0,92
= 0,204 kg/s
Vb
Air Volume flowrate (V) = m.
3
kg m
= 0,204 s x 0,92 kg
m3
= 0,018 s
= 0,0225 m2
V
Kecepatan udara = A
m3
0,018
= s
0,0225m 2
= 0,8 m/s
2) Perhitungan Laju Pendinginan dan Cooling Range
Q
Laju Pendinginan = T 5T 6
0,5
= 41,031,0
= 0,05 kW/
T 5 T 6
Cooling Range =
= 41,0 31,0
= 10
T 6 T 2
Dry Bulb =( )
= 31,0 28,2
= 7,5
T3
Temperatur dry bulb udara keluar ( ) dan temperature wet bulb keluar (
T4 Vb 3
) pada physcometric chart, maka diperoleh = 0,923 ( m /kg )
= 0,137 20
0,923
= 0,6377 kg/s
Vb
Air Volume flowrate (V) = m.
kg m3
= 0,6377 s x 0,923 kg
3
m
= 0,0184 s
V
Kecepatan udara = A
m3
0,0184
= s
2
0,0225 m
= 0,8177 m/s
4) Perhitungan Laju Pendinginan dan Cooling Range
Q
Laju Pendinginan = T 5T 6
0,5
= 41,031,5
= 0,052 kW/
T 5 T 6
Cooling Range =
= 41,0 31,5
= 9,5
T 6 T 2
Dry Bulb =( )
= 31,5 28,2
= 3,3
Untuk Cooling Load Q = 0,5 kW, laju Alir 40 gr/s
H2O
Untuk Orifice Diffrential (x) = 20mm
T
Temperatur wet bulb udara masuk ) = 28,7
T6
Temperatur air keluar ( ) = 30,5
T3
Temperatur dry bulb udara keluar ( ) dan temperature wet bulb keluar (
T4 Vb 3
) pada physcometric chart, maka diperoleh = 0,93 ( m /kg )
= 0,137 20
0,93
= 0,635 kg/s
Vb
Air Volume flowrate (V) = m.
kg m3
= 0,635 s x 0,93 kg
m3
= 0,590 s
V
Kecepatan udara = A
m3
0,590
= s
0,0225m 2
= 26,24 m/s
6) Perhitungan Laju Pendinginan dan Cooling Range
Q
Laju Pendinginan = T 5T 6
0,5
= 41,030,5
= 0,0476 kW/
T 5 T 6
Cooling Range =
= 41,0 30,5
= 10,5
T 6 T 2
Dry Bulb =( )
= 30,5 28,7
= 1,8
T3
Temperatur dry bulb udara keluar ( ) dan temperature wet bulb keluar (
T4 Vb 3
) pada physcometric chart, maka diperoleh = 0,928 ( m /kg )
= 0,137 20
0,928
= 0,6353 kg/s
Vb
Air Volume flowrate (V) = m.
3
kg m
= 0,6353 s x 0,928 kg
m3
= 0,5895 s
= 0,0225 m2
V
Kecepatan udara = A
m3
0,5895
= s
0,0225 m 2
= 26,20 m/s
8) Perhitungan Laju Pendinginan dan Cooling Range
Q
Laju Pendinginan = T 5T 6
1,0
= 50,035,5
= 0,06 kW/
T 5 T 6
Cooling Range =
= 50,0 35,5
=14,5
T 6 T 2
Dry Bulb =( )
= 35,5 29,4
= 6,1
T3
Temperatur dry bulb udara keluar ( ) dan temperature wet bulb keluar (
T4 Vb 3
) pada physcometric chart, maka diperoleh = 0,93 ( m /kg )
= 0,137 20
0,93
= 0,6353 kg/s
Vb
Air Volume flowrate (V) = m.
kg m3
= 0,6353 s x 0,93 kg
3
m
= 0,5908 s
V
Kecepatan udara = A
m3
0,5908
= s
2
0,0225 m
= 26,25 m/s
10) Perhitungan Laju Pendinginan dan Cooling Range
Q
Laju Pendinginan = T 5T 6
1,0
= 50,034,2
= 0,063 kW/
T 5 T 6
Cooling Range =
= 50,0 34,2
= 15,8
T 6 T 2
Dry Bulb =( )
= 34,2 28,3
= 5,9
T3
Temperatur dry bulb udara keluar ( ) dan temperature wet bulb keluar (
T4 Vb 3
) pada physcometric chart, maka diperoleh = 0,94 ( m /kg )
= 0,137 20
0,94
= 0,6319 kg/s
Vb
Air Volume flowrate (V) = m.
kg m3
= 0,6319 s x 0,94 kg
m3
= 0,5940 s
= 0,0225 m2
V
Kecepatan udara = A
3
m
0,5940
= s
0,0225 m2
= 26,40 m/s
1,0
= 50,034,3
= 0,06 kW/
T 5 T 6
Cooling Range =
= 50,0 34,3
=15,7
T 6 T 2
Dry Bulb =( )
= 34,3 28,4
= 5,9