HT CABLE SELECTION CALCULATION

1. RMG Panel - 1

DATA
Equipment : RMG-1 (Incomer from HT 6 Panel Board
from MRS Room)
Rating : 263A
Ambient Temperature : 45C
Maximum Allowable Drop : 3%
Type of Cable : XLPE
Method of Laying : in Ground
Length of Cable : 550 Mtrs
Short Circuit Rating for 1Sec. : 25KA

CALCULATION
Cable Selected (Based on Short Circuit Rating) : 1R of 3C x 300Sq.mm Aluminum
Current Rating of Cable at 30C : 360A (From Catalogue)
Rating factor for Ground Temperature : 0.82
Final rating of Cable : 295A
Short Circuit Rating / One sec. : 28.2A (From Catalogue)

FAULT LEVEL CALCULATION


Short Circuit Rating / One Sec. : 28.2KA > 25KA

HENCE ADEQUATE
VOLTAGE DROP
Impedance (Z) : ((0.130)2 + (0.095)2)
: 0.161 / Km
Voltage : 11KV
Voltage Drop : 3 x 263 x 0.161 x 550 / (1000 x11x1000)
: 0.00367V
% Voltage Drop : 0.36% < 3%
Current Carrying Capacity : 295A > 263A

HENCE ADEQUATE
2. RMG Panel 2

DATA
Equipment : RMG-2 (Incomer from HT 6 Panel Board
from MRS Room)
Rating : 263A
Ambient Temperature : 45C
Maximum Allowable Drop : 3%
Type of Cable : XLPE
Method of Laying : in Ground
Length of Cable : 630 Mtrs
Short Circuit Rating for 1Sec. : 25KA

CALCULATION
Cable Selected (Based on Short Circuit Rating) : 1R of 3C x 300Sq.mm Aluminum
Current Rating of Cable at 30C : 360A (From Catalogue)
Rating factor for Ground Temperature : 0.82
Final rating of Cable : 295A
Short Circuit Rating / One sec. : 28.2A (From Catalogue)

FAULT LEVEL CALCULATION


Short Circuit Rating / One Sec. : 28.2KA > 25KA

HENCE ADEQUATE
VOLTAGE DROP
Impedance (Z) : ((0.130)2 + (0.095)2)
: 0.161 / Km
Voltage : 11KV
Voltage Drop : 3 x 263 x 0.161 x 630 / (1000 x11x1000)
: 0.00427V
% Voltage Drop : 0.42% < 3%
Current Carrying Capacity : 295A > 263A

HENCE ADEQUATE