BTUH = 500 x GPM x ▲ T To obtain any value in the center circle, perform the operation
Qsensible = 1.08 x CFM x ▲ T
in the adjacent segment of the outer circle.
▲ T = BTUH Qlatent = 0.68 x CFM x ▲ SH
500 x GPM Qtotal = 4.5 x CFM x ▲ H
Watts
Full Load Current = (1 Ø)
GALLON of WATER = 8.33 lbs. Voltage
Q = Heat Flow in BTUH
8.33 lbs/GAL x 60 = 500 lbs/hr Watts
SH = Specific Humidity Full Load Current = (3 Ø)
DENSITY = 62.4 lbs/cubic ft 1.732 x Voltage
(grains of moisture)
H = Enthalpy Volts = Amps x Resistance
Pump HP= GPM x Ft. Water Watts = Volts x Amps
Pump Eff. x 3960
800.497.6805 www.icorinternational.com
Pressure Temp Chart-'01 10/31/01 2:54 PM Page 2
EVAPORATOR CONDENSER
SUPERHEAT
CHECK SUCTION SUCTION LIQUID
PRESSURE
(always use dew SUBCOOLING
point for conversion) CHECK LIQUID
Check at evap. if DISCHARGE PRESSURE
possible, add for suction (always use bubble
line pressure drop if point for conversion)
COMPRESSOR
taken at compressor.
CHECK LIQUID
CHECK SUCTION TEMPERATURE
TEMPERATURE
SUCTION TEMPERATURE -- EVAPORATOR TEMPERATURE = SUPERHEAT
CONDENSING TEMPERATURE -- LIQUID TEMPERATURE = SUBCOOLING