You are on page 1of 2

QF-DGN-01

TITLE: DOCUMENT/DRAWING APPROVAL/COMMENT TRANSMITAL

PROJECT : DESIGN, SUPPLY, ERECTION, TESTING & COMMISSIONING OF 230/132KV AIR


INSULATED SWITCHGEAR (AIS) SUBSTATION AT BARISAL ON TURNKEY BASIS.
CONTRACT NUMBER : PGCB/SS/2011/02, Dated 01.08.2012
DOCUMENT SUBMITTAL REF: LECLDR14/08/24-093, Dated: 24.08.2014.
SUBJECT : COMMENTS ON ASSEMBLE DRAWING OF 132KV GANTRY TOWER MARKED "T1A & T1C"
FOR BARISAL 230/132KV AIS SUBSTATION.

To Copy to,
Project Director
Managing Director, PGCB
Barisal – Bhola Project
Power Grid Company of Bangladesh Limited √ Executive Director (P & D), PGCB
NLDC Complex Aftabnagar South Badda,
Dhaka-1212 √ Chief Engineer (P & D/Project), PGCB
Kind Attn: Mr.
√ Shandong Taikai Power Engineering Co.,Ltd

√ Executive Engr. (Civil Design), PGCB

√ Master File
Dear Sir,

We are pleased to enclose the following documents for the purpose indicated below:

Issued by:
(1)
In case of any modification other than those desired are carried out, the same shall be
highlighted clearly in the Drawing/Document with full justification thereof and resubmitted SUKANTO LAL NAG
for approval. Superintending Engr.
(2)
Approval/Comments/Information conveyed herein neither relieves the contractor of his
(Civil Design & Q/C),
contractual obligation and his responsibilities for correctness of dimensions, material of PGCB, Dhaka
constructions, weight, quantities, design details, assemble fits, performance particulars
and conformity of the supplies with the Statutory Laws of Bangladesh as may be Our Ref: 04-PGCB/SE(Civil)/Design & QC/2014/15
applicable, nor does it limit the Employer’s right under the contract.”
Date: 01/09/14

Item No Description of Document Drawing Number Revision Status Enclosed


Drawing/ Documents Number
Approved (A)
Yes √
Approved with
Please refer to Annexure -1 Correction (C)

Request for re-


Submission (RR)
√ No

For information
(FI)

Please acknowledge receipt of documents:

Received by Date

Note:
(1)The above paragraph shall be added if the status of the document is C/RR/FI.
(2)The above paragraph shall be added if the status of the document is A or C.
04-PGCB/SE(Civil)/Design & QC/2014/15 Date: 01 September, 2014

Annexure-1

Sl. no Description Drawing / Document no. Comments

1. Provide all general notes in assemble drawing


Assemble Drawing of 132KV Gantry TKPE-230-B0004-A-C0403-07; as per structural design drawing.
01. 2. Specify all material grade in assemble drawing.
Tower marked "T1A" for Barisal Rev. 0, Sheet 1 of 2
230/132KV AIS Sub-station. 3. Provide sectional details of joints.
TKPE-230-B0004-A-C0403-07;
Rev. 0, Sheet 2 of 2
4. "SLD" of Gantry to be match with structural
drawing.
5. Distance of gauge line shall have to be shown
specially for main leg.
6. Dimension of gantry in position of beam to be
match with structural drawing.
7. Setional details marked 6-6 to be match with
structural drawing.
8. Packing plate to be provided at the joint where
two main leg of different thickness jointed
together.
9. Member section (e.g.412,413,414) to be match
with structural drawing)
10. Base palte at intersection point of diagonal
bracing to be of thickness as per requirement.
11. Please Submit "Sheet 1 of 2" in A1 plot.

1. Provide all general notes in assemble drawing


Assemble Drawing of 132KV Gantry TKPE-230-B0004-A-C0403-09; as per structural design drawing.
02. 2. Specify all material grade in assemble drawing.
Tower marked "T1C" for Barisal Rev. 0, Sheet 1 of 1
230/132KV AIS Sub-station. 3. Provide sectional details of joints.
4. "SLD" of Gantry to be match with structural
drawing.
5. Distance of gauge line shall have to be shown
specially for main leg.
6. Dimension of gantry in position of beam to be
match with structural drawing.
7. Setional details marked "6-6" to be match with
structural drawing.
8. Packing plate to be provided at the joint where
two main leg of different thickness jointed
together.
9. Member section (e.g.412,413,414) to be match
with structural drawing)
10. Base palte at intersection point of diagonal
bracing to be of thickness as per requirement.
11. No of bolts provided with member (201, 202)
to be match with structural drawing.