Professional Documents
Culture Documents
Proracun Struja Kratkih Spojeva Metodom Simetricnih Komponenti PDF
Proracun Struja Kratkih Spojeva Metodom Simetricnih Komponenti PDF
STRUKOVNIH STUDIJA‐VIŠER, BEOGRAD
STUDIJSKI PROGRAM: NOVE ENERGETSKE TEHNOLOGIJE
SPECIJALISTIČKE STUDIJE
PREDMET: SPECIJALNE ELEKTRIČNE INSTALACIJE
PRORAČUN STRUJA KRATKIH SPOJEVA
METODOM SIMETRIČNIH KOMPONENTI
+ + =
geometrijska konstrukcija I1
geometrijska konstrukcija I2
ELEMENAT NULTA IMPEDANSA
Z(0)
TRANSFORMATOR (sa strane sekundara)
Bez neutralne tačke ∞
Yyn ili Zyn (slobodni fluks) ∞
Yyn ili Zyn (forsirani fluks) 10‐15X(1)
Dyn ili YNyn X(1)
Primar D ili Y+zn 0.1‐0.2X(1)
ELEKTRIČNE MAŠINE
SINHRONE ≈ 0.5Z(1)
ASINHRONE ≈0
MREŽA ≈ 3Z(1)
EKVIVALENTNE ŠEME POJEDINIH
ELEMENATA ZA SVE REDOSLEDE
• GENERATORI
• TRANSFORMATORI
UTICAJ NULTIH STRUJA NA IMPEDANSU‐
PRIMER: sprega Y‐y sa uzemljenim zvezdištem
na primaru
• Ako na primarnoj strani
transformatora, kod koga je
samo zvezdište primara
uzemljeno, dovedemo u sve tri
faze naizmenične napone koji
su u fazi (međusobni fazni
pomeraj jednak nuli), u primaru
će se javiti u sve tri faze struje
koje su takođe u fazi.
• Veličina ovih struja zavisi od
konstrukcije magnetnog kola
(jezgra) transformatora, tako da
će od nje zavisiti i vrednost
nulte impedanse (reaktanse)
transformatora.
I‐SLUČAJ: MAGNETNO KOLO SA TRI STUBA
Prilike ne odgovaraju onima koje se imaju u
praznom hodu transformatora, jer se ovde radi
o strujama koje su u fazi u sva tri namotaja
odnosno o fluksevima koji su u fazi te se oni moraju
zatvarati kroz okolni vazduh, a za to je potrebna
puno veća struja magnetizacije, odnosno reaktansa
Xo = 4-5 Xd.
Ono što je zajedničko sa situacijom u praznom
hodu je to, da nema struja u u sekundarnom
namotu (u oba slučaja samo kroz primarni namot
teku struje magnetizacije).
*NAPOMENA: u praznom hodu su struje međusobno pomerene
za 120° te se stoga fluksevi mogu zatvarati kroz magnetno kolo
tj.gvožđe;u ovom slučaju je Xm = 100Xd
•Budući da su magnetni fluksevi nultog sistema prouzrokovani strujama koje su u fazi, oni se moraju zatvarati
kroz vazduh ili transformatorski sud. Vazduh ima veliki magnetni otpor pa bi se u namotaju indukovala
odgovarajuća kontra-elektromotorna sila suprostavljena dovedenom naponu Vo. Stoga će biti potrebna
značajna struja (zbog velikog Rm) da bi se ostvario potreban magnetni fluks. To onda znači da je Xo
relativno mala (Xo = 4-5 Xd).
•Ako se magnetni fluks zatvara kroz obližnji magnetski provodan metalni sud (bez obzira što je sad magnetni
otpor kojeg vide silnice fluksa manji) promenljivi magnetni fluks će u sudu indukovati vrtložne struje, koje opet
indukuju struje u primarnom namotu ( jednakost flukseva) pa će struja primarnog namotaja tek neznatno
pasti, a da pri tome bude indukovana odgovarajuća elektromotorna sila koja se suprostavlja primarnom
naponu. To znači da je onda Xo relativno velika (X0 = 10-15 Xd).
II‐SLUČAJ: MAGNETNO KOLO SA PET STUBOVA
Izračunavanje ekvivalentnih
impedansi
pasivnih mreža
Očekivana struja KS‐ struja koja bi tekla u slučaju da je na mestu kratkog spoja
zanemarljiva impedansa (“metalni kratak spoj”)
Simetrična struja KS‐ efektivna vrednost naizmenične komponente struje KS
Početna simetrična struja KS‐ efektivna vrednost naizmenične simetrične
Komponente očekivane struje KS u trenutku nastanka kvara
Udarna struja KS‐ maksimalna trenutna vrednost struje kvara
Aperiodična (jednosmerna‐DC) komponenta struje KS‐ srednja vrednost između
gornje i donje anvelope krive struje kvara
2π f n ⋅ R
− ⋅t
iDC = 2 ⋅ I ⋅ e " "
X
k
t‐vreme
fn‐ nominalna učestanost
PRORAČUN STRUJE KRATKOG SPOJA‐
DVOFAZNI (DVOPOLNI) KRATAK SPOJ BEZ
ZEMLJOSPOJA
KRATAK SPOJ: FAZA-FAZA
OBZIROM DA NEMA ZEMLJOSPOJA:
uopšteno
za kvar koji je
daleko od generatora
UTICAJ RASTOJANJA MESTA KVARA
(KRATKOG SPOJA) OD GENERATORA
• OVDE ĆE BITI RAZMOTRENA DVA SLUČAJA: KADA JE KVAR
DALEKO OD GENERATORA I KADA JE KVAR BLIZU GENERATORA
• KRATAK SPOJ DALEKO OD GENERATORA: SITUACIJA U
MREŽAMA GDE STRUJE KRATKOG SPOJA NEMAJU
PRIGUŠENU NAIZMENIČNU KOMPONENTU, TAKOĐE JE
OVO SLUČAJ U NN MREŽAMA, OSIM U SLUČAJU
KADA POSEBNA VN TRAFOSTANICA NAPAJA
POTROŠAČ.
• KRATAK SPOJ BLIZU GENERATORA: SITUACIJA KADA
STRUJE KRATKOG SPOJA IMAJU PRIGUŠENU
NAIZMENIČNU KOMPONENTU, TAKOĐE OVO JE
SLUČAJ U VN SISTEMIMA ALI I U NN SISTEMIMA, NA
PRIMER KADA SIGURNOSNI GENERATOR SNABDEVA
PRIORITETNE POTROŠAČE.
ŠTA JE SA SIMETRIČNIM
IMPEDANSAMA?
• KADA JE KRATAK SPOJ DALEKO OD GENERATORA,
POČETNA, USTALJENA I PREKIDNA STRUJA KRATKOG
SPOJA SU JEDNAKE (RESPEKTIVNO):
-TEMPERATURA NA 20°C
-DOZVOLJENA TEMPERATURA
PROVODNIKA, data u (°C), TOKOM
KRATKOG SPOJA
IMPEDANSA ASINHRONIH MOTORA
Z M = RM + jX M
2
I nM U nM I nM U nM
ZM = ⋅ = ⋅
I kr 3I nM I kr SnM
I nM ,U nM , SnM Nominalna struja, nominalni napon i nominalna
prividna snaga motora, respektivno
I kr Struja pri ukočenom rotoru motora
Korekcioni faktori impedansi energetskih
transformatora, sinhronih generatora i
elektrana
• Radi kompenzacije pojednostavljenja i pretpostavki
u predloženoj metodi proračuna KS, prema
standardu IEC60909 se uvode korekcioni faktori
impedansi pojedinih elemenata sistema:
KT Korekcioni faktor impedansi transformatora
KG Korekcioni faktor impedansi generatora
Korekcioni faktor impedansi elektrana, ako transformator u
KE elektrani ima regulator za regulaciju napona pod opterećenjem
Korekcioni faktor impedansi elektrana, ako transformator u
K E 0 Elektrani nema regulator za regulaciju napona pod opterećenjem
transformatori
cmax
KT = 0.95 ⋅ xT − relativna reaktansa transformatora
1 + 0.6 ⋅ xT
sinhroni generatori
elektrane
U ns ,mreže 1 cmax
KE0 = ⋅ ⋅ (1 ± pT max ) ⋅
U ns ,G (1 + pT max ) mT 1 + xd" ⋅ sin ϕ nG
Regulacioni opseg transformatora oko
srednjeg izvoda (u r.j)
JEDNAČINE ZA PRORAČUN STRUJA
KRATKIH SPOJEVA
PREKIDAČA??????
τ = tr + τ p
Računsko vreme zaštitnog prekidača je zbir vremena reagovanja
i vremenskog kašnjenja usled inercije
tr − Računsko vreme reagovanja zaštite (obično se usvaja da je ono 0.01s)
τ p − Vreme inercije zaštitnog prekidača
POČETNA SIMETRIČNA SNAGA KRATKOG SPOJA
S = 3 ⋅ U n ,mreže ⋅ I
"
k
"
k
Koristi se kod izbora zaštitnog prekidača. Zaštitni prekidač mora obezbediti
isključenje KS, a da se pri tome ne ošteti. Za zaštitne prekidače se u katalozima
Proizvođača daju dozvoljene vrednosti početne simetrične snage KS.
Ova snaga se izražava u MVA.
Mora biti zadovoljen uslov:
S = 3 ⋅ U n ,mreže ⋅ I ≤ S
"
k
"
k
"
k , prekidača [ MVA]
Konzervativna pretpostavka za
faktor μ
KAKO IZRAČUNATI i ?
TURBOGENERATORI HIDROGENERATORI
tk
1 A
∫
2
I th = ⋅ i (t ) ⋅ dt =
tk tk
0
A- termički impuls
tk‐ vreme trajanja kvara
TERMIČKA STRUJA JE USTVARI RAČUNSKA KONSTANTNA STRUJA KOJA
JE PREMA SVOJIM TOPOLOTNIM EFEKTIMA U TOKU VREMENA tk
EKVIVALENTNA STVARNOJ SLOŽENO PROMENLJIVOJ STRUJI KVARA:
tk
1
I th = ⋅ ∫ i (t ) ⋅ dt
2
tk 0
PRAKTIČNIJI IZRAZ ZA INŽENJERSKU PRAKSU JE :
početna (subtranzijentna)
I th = m + n ⋅ I "
K struja kvara
KOEFICIJENTI m , n su funkcije vremena trajanja kratkog spoja
m‐ određuje toplotni uticaj jednosmerne komponente struje kvara
n‐ određuje toplotni uticaj naizmenične komponente struje
Toplotni uticaj jednosmerne komponente struje kvara
(trofazni i monofazni sistemi)
t‐vreme trajanja kvara, f‐učestanost u normalnom pogonu
Odnos subtranzijentne i ustaljene struje kvara
Toplotni uticaj naizmenične komponente struje u trofaznim sistemima
(približno važi i za monofazne)
ZADATAK ZA AUDITORNE
VEŽBE:
6% 6%
•Tokom montaže voda G-H dužine
30km, je potrebno prema podacima
sa prstenaste jednopolne šeme
proveriti prekidnu moć prekidača
M, za slučaj naznačenog kvara
(zemljospoja).
•Proveru izvršiti za dva slučaja:
-kada nema voda GH
-kada je postavljen vod GH
8% 8%
•Usvojiti da su na strani 30kV
reaktanse direktnog i inverznog
redosleda jednake i da iznose
0.35Ω/km, kao i da je nulta
KS impedansa trostruko veća.