You are on page 1of 6

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/237012203

Adaptive Mho Type Distance Relaying Scheme with Fault Resistance


Compensation

Conference Paper · June 2013


DOI: 10.1109/PEOCO.2013.6564545

CITATIONS READS
8 16,833

4 authors:

muhd hafizi Idris saufi ahmad


Universiti Malaysia Perlis Universiti Malaysia Perlis
26 PUBLICATIONS   76 CITATIONS    9 PUBLICATIONS   28 CITATIONS   

SEE PROFILE SEE PROFILE

Ahmad Zaidi BIn Abdullah Surya Hardi


Universiti Malaysia Perlis University of Sumatera Utara
24 PUBLICATIONS   31 CITATIONS    19 PUBLICATIONS   39 CITATIONS   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Wide Area Fault Location using Phasor Measurement Unit (PMU) View project

Mathematical Derivation of Switching Angles of Multilevel Voltage Source Inverter based on Alternative Phase Opposition Disposition (APOD) View project

All content following this page was uploaded by muhd hafizi Idris on 21 May 2014.

The user has requested enhancement of the downloaded file.


2013 IEEE 7th International Power Engineering and Optimization Conference (PEOCO2013), Langkawi, Malaysia. 3-4 June 2013

Adaptive Mho Type Distance Relaying Scheme


with Fault Resistance Compensation
Muhd Hafizi Idris, Member, IEEE, Mohd Saufi Ahmad, Ahmad Zaidi Abdullah, Surya Hardi
School of Electrical System Engineering
Universiti Malaysia Perlis,
Arau, Perlis, Malaysia.

Abstract-- This paper describes an adaptive distance relaying Zone 1 reach is normally set only up to 80% - 90% of the
scheme which can eliminate the effect of fault resistance on protected line. It is not set 100% of the protected line to avoid
distance relay zone reach. Distance relay is commonly used as relay from under reached or over reached due to current and
main protection to protect transmission line from any type of voltage measurement errors, transient effect and inaccuracy in
fault. For a stand-alone distance relay, fault resistance can make transmission line parameters. If a fault occurred within this
Mho type distance relay to be under reached and thus the fault
zone where distance relay acts as main protection, the relay
will be isolated at a longer time. In this scheme, the relay detects
the fault location using a two-terminal algorithm. By knowing will instantaneously send trip signal to open the circuit
fault location, fault voltage at the fault point can be calculated by breaker.
using equivalent sequence network connection as seen from local To ensure full coverage of the protected line by considering
terminal. Then, fault resistance is calculated by using simple errors and other effects, zone 2 is set at minimum 120% of the
equation considering contribution from remote terminal current. protected line. It is a common practice to set zone 2 reach
Finally, the compensation of fault resistance is done onto equal to 100% of the protected line plus 50% of the shortest
calculated apparent resistance as seen at relaying point. The adjacent line. For faults within zone 2 reach, tripping signal
modeling and simulation was carried out using Matlab/Simulink will be sent at a delayed time where the relay acts as backup
software. Several cases were carried out and the results show the
for main protection at adjacent line. The tripping time for zone
validity of the scheme.
2 normally set at several hundred miliseconds.
Index Terms—Distance relay, Fault location, Fault resistance, Backup protection for entire adjacent line is covered by
Matlab/Simulink, Mho type, Single line to ground zone 3 reach. It is normally set at least 1.2 times the
impedance of protected adjacent line. The set tripping time for
I. INTRODUCTION zone 3 reach is typically several seconds.
An accurate apparent impedance measurement during fault
occurrence by distance relay is very important because false
T ransmission line is one of the main components in High
Voltage (HV) and Extra High Voltage (EHV) power
system. The protection of transmission line from any type of
measurement might result in delayed tripping signal sent by
distance relay. There are several factors which can lead to
inaccurate apparent impedance measurement such as high
fault is very important because any mis-operation or mal- fault resistance, mutual inductance of parallel line, line
operation of protection relays can give a great effect on the charging capacitance and transient effects due to switching of
stability of power system entirely. One of the main protection Flexible Alternating Current Transmission System (FACTS)
used to protect transmission line is distance or impedance devices [2]-[6].
relay. It uses the impedance measurement technique to In this paper, focus is given to compensate the effect of
measure the apparent impedance as seen by the relay at the fault resistance on the accuracy of Mho type distance relay.
relaying point. The inputs for distance relay are three phase Fault resistance can be high or low depending on the nature of
current and voltage phasors during fault occurrence. fault. Even a small fault resistance value can make the relay to
Transmission line is segregated into several zones of be under reached when it is used to protect short transmission
protection normally zone 1, zone 2 and zone 3 as shown in line. The relay also might be under reached when the fault is
Fig. 1 for relay at substation A [1]. Distance relay acts as main near to remote substation terminal. Delayed tripping of circuit
protection for faults within zone 1 while for zone 2 and zone breaker due to under reached of distance relay will make the
3, it acts as backup protection for adjacent line. power system in stress for a longer time.

II. THEORIES OF THE PROPOSED SCHEME

This section presents the methodologies used to


compensate the effect of fault resistance on the accuracy of
apparent impedance measurement. The process began with
determining the fault location during the occurrence of fault.
Fig. 1. Zones of protection for distance relay There are many techniques currently and previously used to

978-1-4673-5074-7/13/$31.00 ©2013 IEEE 208


2013 IEEE 7th International Power Engineering and Optimization Conference (PEOCO2013), Langkawi, Malaysia. 3-4 June 2013

locate the fault point. The most and commonly used technique the fault point can be calculated using (2). The value of fault
to locate fault at transmission line is impedance based resistance, RF then directly calculated using (3). During fault
technique [7]. It measures the impedance by dividing the condition, current from both substations will flow into fault
fundamental frequency of voltage and current phasors at the point and return back to their sources. Hence, the contribution
relaying point. It is widely used because of its simplicity and of current from remote substation must be included into fault
easy to be adapted to electronic devices. However, this resistance calculation.
technique is severely affected by fault resistance value where
the inaccuracy of fault location estimation increases with the
increase in fault resistance.
Available impedance based techniques also can be
classified into one-terminal and two-terminal algorithms.
Because of limitation in gaining measurement parameters,
one-terminal algorithm uses many assumptions in fault
location estimation which may lead to inaccurate result. Two-
terminal algorithm is more accurate than one terminal
algorithm because it uses the voltage and current Fig. 3. Sequence network connection as seen from local substation terminal
measurements from both substation terminals. The data are
sent using low speed communication channel available at the m (2)
substation. This algorithm is expected to replace one-terminal
algorithm in the future because of the increasing use of Where;
intelligent electronic devices (IED).
Two-terminal algorithm as was proposed by the author from IA0 = Zero sequence component of phase current from local
the previous research is used to estimate the fault location [8]. substation.
The algorithm does not need source impedance parameters
and estimated fault location is not influenced by fault RF (3)
resistance value. Equation (1) represents the algorithm for
fault location calculation for Single Line to Ground (SLG)
fault while Fig. 2 shows the SLG fault condition at a phase Where;
line.
RF = Fault resistance
VF = Fault voltage between fault point and ground
m (1) IA = Phase current from local substation
IB = Phase current from remote substation

Where; After the relay calculated the fault resistance, next step is to
compensate the effect of fault resistance on Mho type distance
m = fault location estimation (in per unit) relay. This is done first by measuring the apparent impedance
Z1 = Positive sequence impedance at the relaying point. The measurement of apparent impedance
Z2 = Negative sequence impedance is done by using (4) [9]. The apparent resistance, R and
Z0 = Zero sequence impedance reactance, X are the real and imaginary values of (4)
VA = Phase to ground voltage for local substation respectively.
VB = Phase to ground voltage for remote substation
IA = Phase current from local substation (4)
IB = Phase current from remote substation
Where;

k0 = residual compensation factor and k0 = (Z0-Z1)/kZ1.


I0 = Zero sequence component of neutral current.

After that, the apparent resistance will be subtracted with


fault resistance as shown in (5).

Fig. 2. Single line to ground fault Rcompensated = R – RF (5)

Fig. 3 shows the equivalent sequence network connection Where;


for SLG fault as seen from local substation terminal. From the
result of fault location calculated using (1), fault voltage, VF at Rcompensated = Compensated apparent resistance
R = Measured apparent resistance.

209
2013 IEEE 7th International Power Engineering and Optimization Conference (PEOCO2013), Langkawi, Malaysia. 3-4 June 2013

The proposed scheme was modeled using Matlab/Simulink


Start software. Table I lists the parameters used for transmission
line model. Fig. 5 shows the overall model for distance relay
V & I phasors from both substation terminals with fault resistance compensation. The function of Analog
Low Pass Filter block is to filter any harmonic components
which may add to the fundamental frequency component of
Calculate fault location, m
voltage and current phasors. Next, the filtered voltage and
current phasors are transferred to Fourier Analysis block. The
Calculate fault voltage, VF function of this block is to extract the magnitude and phase
angle of every voltage and current phasors. Then, the
Calculate fault resistance, RF magnitudes and phase angles are used inside Fault Location
Calculation block. The output of this block is fault location in
kilometer. After that, from the value of fault location, it is
Calculate apparent resistance, R and reactance, X
used inside Fault Resistance Calculation block to calculate
fault voltage and fault resistance.
Subtract fault resistance, RF from apparent Apparent impedance seen by the relay is calculated inside
resistance, R Apparent Impedance Measurement block. The outputs of this
block are apparent resistance and apparent reactance at the
Plot apparent reactance, X versus compensated relaying point. Finally, the compensation is done by
apparent resistance, Rcompensated subtracting the fault resistance from apparent resistance inside
Compensated Apparent Resistance block.
End
TABLE I
Fig. 4. Proposed fault resistance compensation scheme TRANSMISSION LINE PARAMETERS
Line Parameters Value Unit
Fig. 4 shows the overall steps for the proposed fault Line length 47 km
resistance compensation scheme. The final step is to plot the Nominal frequency 50 Hz
apparent reactance versus the compensated apparent resistance Phase to phase voltage 132,000 Volt
on R-X diagram. Positive sequence resistance 0.045531917 Ω / km
Zero sequence resistance 0.151489359 Ω / km
III. MODELING THE PROPOSED SCHEME Positive sequence resistance 0.000617657 H / km
Zero sequence resistance 0.001533983 H / km

thetaIa Out3

magnitude Z

Ia Out4

angle Z

Va Out1 R

Apparent resistance

thetaVa Out2 X

(pi /180 )*u Apparent reactance


Continuous Apparent Impedance
radian 1 Measurement
powergui

Out1 R
Va
fcn Rcompensated
In1
Rf Rcompensated
Out2 thetaVa
(pi /180 )*u
Compensated apparent resistance
Iabc Local In1 Out1 radian 2 Ia
Out7
Rcompensated
In4
Vabc local In2 Out4 thetaIa To Workspace1
Out8
SLG Fault fcn Fl _km

Iabc remote Out7 Vb


In3 Fault Location (km)
Out13

In7 (pi /180 )*u thetaVb


Vabc remote In4 Out10
Out14 radian 3
Transmission Line Analog Low Pass Filter Ib

Out19
thetaIb
In10
RF Out20 (pi /180 )*u
Fault initiation Fault Location Calculation
Va
radian 4
Fourier Analysis thetaVa
Ia
thetaIa fcn Rf
Ib
Fault Resistance (ohm )
thetaIb
m
Fault Resistance Calculation

Fig. 5. Overall model of distance relay with fault resistance compensation.

210
2013 IEEE 7th International Power Engineering and Optimization Conference (PEOCO2013), Langkawi, Malaysia. 3-4 June 2013

Fig. 7 shows the result of apparent impedance locus for case


2 during fault occurrence with the same fault location as in
case 1 but with different fault resistance. It can be seen that for
IV. SIMULATION RESULTS uncompensated apparent impedance locus, fault resistance of
2 Ω has deviated away the final point of locus from zone 1. By
using the proposed scheme, the locus of apparent impedance
This section presents the simulation results of Mho type
stop within the correct zone thus prevent distance relay from
distance relay when subjected to fault with a resistive value.
The effectiveness and adaptability of the proposed scheme is under reached zone 1. The calculated fault location and fault
discussed. There are four cases simulated with different fault resistance are 34.55 km and 1.971 Ω respectively.
locations and fault resistances. Below is the fault data for each
case.

Case 1 Uncompensated
1. Actual fault location = 35 km
2. Actual fault resistance = 0.01 Ω
Compensated
Case 2
1. Actual Fault location = 35 km
2. Actual fault resistance = 2 Ω

Case 3
1. Actual Fault location = 45 km
2. Actual fault resistance = 0.01 Ω
Fig. 7. Apparent impedance locus for case 2
Case 4
1. Actual Fault location = 45 km Fig. 8 shows the result of apparent impedance locus for case
2. Actual fault resistance = 2 Ω 3 during fault occurrence at 45 km. It can be seen that both
locus for compensated and uncompensated apparent
The selected zone reach settings for Mho type distance impedance stop within the same zone and location. This is
relay at the local substation except Zone 3 are as follow; because the fault resistance is very small compared to line
resistance and the effect is hardly seen. The calculated fault
Zone 1 = 80 % of the transmission line (equal to 37.6 km) location and fault resistance are 44.31 km and 0.1968 Ω
Zone 2 = 100 % + 20 % of the adjacent line (equal to 56.4 km) respectively.

Fig. 6 shows the result of apparent impedance locus for case


1 during fault occurrence at 35 km which is near the reach
setting of zone 1. It can be seen that both locus for
Compensated
compensated and uncompensated apparent impedance stop
within zone 1 at the same location. This is because the fault
resistance is very small compared to line resistance. The
calculated fault location and fault resistance are 34.65 km and
0.06976 Ω respectively.

Uncompensated
Compensated

Fig. 8. Apparent impedance locus for case 3

Fig. 9 shows the result of apparent impedance locus for case


4 during fault occurrence with the same fault location as in
Uncompensated case 3 but with different fault resistance. It can be seen that for
uncompensated apparent impedance locus, fault resistance of
2 Ω has deviated away the final point of locus from zone 2. By
using the proposed scheme, the locus of apparent impedance
stop within the correct zone thus prevent distance relay from
Fig. 6. Apparent impedance locus for case 1 under reached zone 2. The calculated fault location and fault
resistance are 44.17 km and 1.933 Ω respectively.

211
2013 IEEE 7th International Power Engineering and Optimization Conference (PEOCO2013), Langkawi, Malaysia. 3-4 June 2013

Compensated VI. REFERENCES

[1] B. Ram and D. N. Vishwakarma, “Power System Protection and


Switchgear”, Tata McGraw Hill, 1995.
[2] M. E. Erezzaghi and P. A. Crossley, “The Effect Of High Resistance
Faults On A Distance Relay”, Power Engineering Society General
Uncompensated Meeting, IEEE, vol. 4, July 2003.
[3] J. Upendar, C. P. Gupta and G. K. Singh , “Comprehensive Adaptive
Distance Relaying Scheme for Parallel Transmission Lines”, IEEE
Transactions on Power Delivery, vol. 26, no. 2, April 2011.
[4] T. Kase, Y. Kurosawa and H. Amo, ‘‘Charging Current Compensation
for Distance Protection’’, Power Engineering Society General Meeting,
IEEE, vol. 3, pp. 2683 - 2688, June 2005.
[5] K. Satyanarayana, B. K. V. Prasad and K. Saikrishna, “Effect of Series
FACTS Devices on Distance Protection”, International Conference on
Fig. 9. Apparent impedance locus for case 4
Sustainable Energy and Intelligent Systems, pp. 36 – 41, July 2011.
[6] T. S. Sidhu, R. K. Varma, P. K. Gangadharan, F. A. Albasri, and G. R.
Ortiz,“Performance of Distance Relays on Shunt – FACTS
V. CONCLUSION Compensated Transmission Lines”, IEEE Transactions on Power
Delivery, vol. 20, no. 3, July 2005.
[7] M. M. I. Hashim, H. W. Ping and V. K. Ramachandaramurthy,
The results from the previous part show the adaptability of “Impedance-Based Fault Location Techniques for Transmission Lines”,
the proposed scheme in compensating the effect of fault TENCON, pp. 1-6, Jan 2009.
[8] M. H. Idris, M. W. Mustafa and Y. Yatim, “Effective two-terminal
resistance from making the Mho type distance relay under single line to ground fault location algorithm”, IEEE International
reached. The scheme started with calculating the fault location Power Engineering and Optimization Conference, pp. 246 – 251, June
using two-terminal algorithm as in (1). Then, the fault voltage 2012.
and fault resistance is calculated directly using (2) and (3) [9] M. H. Idris, S. Hardi and M. Z. Hassan, “Teaching Distance Relay
Using Matlab/Simulink Graphical User Interface”, Malaysian
which consider the contribution of current from remote Technical Universities Conference on Engineering and Technology,
substation. Then, apparent resistance and apparent reactance November 2012.
are calculated using (4). Finally, calculated fault resistance
will be subtracted from calculated apparent resistance as
shown by (5).

View publication stats


212

You might also like