Professional Documents
Culture Documents
net/publication/237012203
CITATIONS READS
8 16,833
4 authors:
Some of the authors of this publication are also working on these related projects:
Wide Area Fault Location using Phasor Measurement Unit (PMU) View project
Mathematical Derivation of Switching Angles of Multilevel Voltage Source Inverter based on Alternative Phase Opposition Disposition (APOD) View project
All content following this page was uploaded by muhd hafizi Idris on 21 May 2014.
Abstract-- This paper describes an adaptive distance relaying Zone 1 reach is normally set only up to 80% - 90% of the
scheme which can eliminate the effect of fault resistance on protected line. It is not set 100% of the protected line to avoid
distance relay zone reach. Distance relay is commonly used as relay from under reached or over reached due to current and
main protection to protect transmission line from any type of voltage measurement errors, transient effect and inaccuracy in
fault. For a stand-alone distance relay, fault resistance can make transmission line parameters. If a fault occurred within this
Mho type distance relay to be under reached and thus the fault
zone where distance relay acts as main protection, the relay
will be isolated at a longer time. In this scheme, the relay detects
the fault location using a two-terminal algorithm. By knowing will instantaneously send trip signal to open the circuit
fault location, fault voltage at the fault point can be calculated by breaker.
using equivalent sequence network connection as seen from local To ensure full coverage of the protected line by considering
terminal. Then, fault resistance is calculated by using simple errors and other effects, zone 2 is set at minimum 120% of the
equation considering contribution from remote terminal current. protected line. It is a common practice to set zone 2 reach
Finally, the compensation of fault resistance is done onto equal to 100% of the protected line plus 50% of the shortest
calculated apparent resistance as seen at relaying point. The adjacent line. For faults within zone 2 reach, tripping signal
modeling and simulation was carried out using Matlab/Simulink will be sent at a delayed time where the relay acts as backup
software. Several cases were carried out and the results show the
for main protection at adjacent line. The tripping time for zone
validity of the scheme.
2 normally set at several hundred miliseconds.
Index Terms—Distance relay, Fault location, Fault resistance, Backup protection for entire adjacent line is covered by
Matlab/Simulink, Mho type, Single line to ground zone 3 reach. It is normally set at least 1.2 times the
impedance of protected adjacent line. The set tripping time for
I. INTRODUCTION zone 3 reach is typically several seconds.
An accurate apparent impedance measurement during fault
occurrence by distance relay is very important because false
T ransmission line is one of the main components in High
Voltage (HV) and Extra High Voltage (EHV) power
system. The protection of transmission line from any type of
measurement might result in delayed tripping signal sent by
distance relay. There are several factors which can lead to
inaccurate apparent impedance measurement such as high
fault is very important because any mis-operation or mal- fault resistance, mutual inductance of parallel line, line
operation of protection relays can give a great effect on the charging capacitance and transient effects due to switching of
stability of power system entirely. One of the main protection Flexible Alternating Current Transmission System (FACTS)
used to protect transmission line is distance or impedance devices [2]-[6].
relay. It uses the impedance measurement technique to In this paper, focus is given to compensate the effect of
measure the apparent impedance as seen by the relay at the fault resistance on the accuracy of Mho type distance relay.
relaying point. The inputs for distance relay are three phase Fault resistance can be high or low depending on the nature of
current and voltage phasors during fault occurrence. fault. Even a small fault resistance value can make the relay to
Transmission line is segregated into several zones of be under reached when it is used to protect short transmission
protection normally zone 1, zone 2 and zone 3 as shown in line. The relay also might be under reached when the fault is
Fig. 1 for relay at substation A [1]. Distance relay acts as main near to remote substation terminal. Delayed tripping of circuit
protection for faults within zone 1 while for zone 2 and zone breaker due to under reached of distance relay will make the
3, it acts as backup protection for adjacent line. power system in stress for a longer time.
locate the fault point. The most and commonly used technique the fault point can be calculated using (2). The value of fault
to locate fault at transmission line is impedance based resistance, RF then directly calculated using (3). During fault
technique [7]. It measures the impedance by dividing the condition, current from both substations will flow into fault
fundamental frequency of voltage and current phasors at the point and return back to their sources. Hence, the contribution
relaying point. It is widely used because of its simplicity and of current from remote substation must be included into fault
easy to be adapted to electronic devices. However, this resistance calculation.
technique is severely affected by fault resistance value where
the inaccuracy of fault location estimation increases with the
increase in fault resistance.
Available impedance based techniques also can be
classified into one-terminal and two-terminal algorithms.
Because of limitation in gaining measurement parameters,
one-terminal algorithm uses many assumptions in fault
location estimation which may lead to inaccurate result. Two-
terminal algorithm is more accurate than one terminal
algorithm because it uses the voltage and current Fig. 3. Sequence network connection as seen from local substation terminal
measurements from both substation terminals. The data are
sent using low speed communication channel available at the m (2)
substation. This algorithm is expected to replace one-terminal
algorithm in the future because of the increasing use of Where;
intelligent electronic devices (IED).
Two-terminal algorithm as was proposed by the author from IA0 = Zero sequence component of phase current from local
the previous research is used to estimate the fault location [8]. substation.
The algorithm does not need source impedance parameters
and estimated fault location is not influenced by fault RF (3)
resistance value. Equation (1) represents the algorithm for
fault location calculation for Single Line to Ground (SLG)
fault while Fig. 2 shows the SLG fault condition at a phase Where;
line.
RF = Fault resistance
VF = Fault voltage between fault point and ground
m (1) IA = Phase current from local substation
IB = Phase current from remote substation
Where; After the relay calculated the fault resistance, next step is to
compensate the effect of fault resistance on Mho type distance
m = fault location estimation (in per unit) relay. This is done first by measuring the apparent impedance
Z1 = Positive sequence impedance at the relaying point. The measurement of apparent impedance
Z2 = Negative sequence impedance is done by using (4) [9]. The apparent resistance, R and
Z0 = Zero sequence impedance reactance, X are the real and imaginary values of (4)
VA = Phase to ground voltage for local substation respectively.
VB = Phase to ground voltage for remote substation
IA = Phase current from local substation (4)
IB = Phase current from remote substation
Where;
209
2013 IEEE 7th International Power Engineering and Optimization Conference (PEOCO2013), Langkawi, Malaysia. 3-4 June 2013
thetaIa Out3
magnitude Z
Ia Out4
angle Z
Va Out1 R
Apparent resistance
thetaVa Out2 X
Out1 R
Va
fcn Rcompensated
In1
Rf Rcompensated
Out2 thetaVa
(pi /180 )*u
Compensated apparent resistance
Iabc Local In1 Out1 radian 2 Ia
Out7
Rcompensated
In4
Vabc local In2 Out4 thetaIa To Workspace1
Out8
SLG Fault fcn Fl _km
Out19
thetaIb
In10
RF Out20 (pi /180 )*u
Fault initiation Fault Location Calculation
Va
radian 4
Fourier Analysis thetaVa
Ia
thetaIa fcn Rf
Ib
Fault Resistance (ohm )
thetaIb
m
Fault Resistance Calculation
210
2013 IEEE 7th International Power Engineering and Optimization Conference (PEOCO2013), Langkawi, Malaysia. 3-4 June 2013
Case 1 Uncompensated
1. Actual fault location = 35 km
2. Actual fault resistance = 0.01 Ω
Compensated
Case 2
1. Actual Fault location = 35 km
2. Actual fault resistance = 2 Ω
Case 3
1. Actual Fault location = 45 km
2. Actual fault resistance = 0.01 Ω
Fig. 7. Apparent impedance locus for case 2
Case 4
1. Actual Fault location = 45 km Fig. 8 shows the result of apparent impedance locus for case
2. Actual fault resistance = 2 Ω 3 during fault occurrence at 45 km. It can be seen that both
locus for compensated and uncompensated apparent
The selected zone reach settings for Mho type distance impedance stop within the same zone and location. This is
relay at the local substation except Zone 3 are as follow; because the fault resistance is very small compared to line
resistance and the effect is hardly seen. The calculated fault
Zone 1 = 80 % of the transmission line (equal to 37.6 km) location and fault resistance are 44.31 km and 0.1968 Ω
Zone 2 = 100 % + 20 % of the adjacent line (equal to 56.4 km) respectively.
Uncompensated
Compensated
211
2013 IEEE 7th International Power Engineering and Optimization Conference (PEOCO2013), Langkawi, Malaysia. 3-4 June 2013