COMPOSITE FLOOR
HB938
ZF75 GALVANNEAL
LIMIT STATES
DESIGN
METRIC
DEPTH FROM MAXIMUM FACTORED PHYSICAL
Note SECTION MODULUS Moment of Inertia
NEUTRAL REACTIONS
1. Load Tables are NOMINAL MASS WITH
MIDSPAN SUPPORT MIDSPAN FULL
AXIS TO PROPERTIES
CORE AREA OF ZF75 BOTTOM OF EXTERIOR INTERIOR STEEL PROPERTIES
based on the design Sm Ss Im If
THICKNESS STEEL GALVANNEAL DECK Y b (kN) (kN)
of ONE-WAY (mm3 x 103) (mm3 x 103) (mm4 x 103) (mm4 x 103)
(mm) (mm2) (kg/m2) (mm)
composite slabs
carrying uniformly 0.76 996.8 8.08 9.59 9.76 213.9 228.3 22.16 10.9 15.7 (PER METRE WIDTH)
distubuted loads on a 0.91 1197.4 9.65 11.70 12.31 266.8 274.0 22.26 15.3 22.3 In accordance
simple span basis. with CSA
1.22 1593.0 12.83 15.87 16.21 364.0 364.0 22.45 25.8 38.4
For complete design Specification
criteria see the 1.52 1992.1 15.96 20.00 20.06 454.4 454.4 22.65 38.9 58.7
S136-07
VICWEST Hi-Bond
Composite Floor SLAB THICKNESS 101 111 126 136 PHYSICAL
Designer's Manual. h(mm)
Slab Weight, W1(kN/m2) 1.89 2.11 2.45 2.68 PROPERTIES
2. A uniform loading in
Concrete Volume, (m3/m2) 0.078 0.088 0.103 0.113 COMPOSITE SLAB
excess of 10 kPa Base Steel Nominal (PER METRE WIDTH)
(200 psf) is often an Thickness IC d IC d IC d IC d
indication of Composite
(mm)
concentrated or Moment of
moving loads. Such 0.76 5455 78.8 7228 88.8 10548 103.8 13244 113.8 Inertia,
conditions may 0.91 5836 78.7 7725 88.7 11252 103.7 14109 113.7 I C (mm4 x 103)
require additional
1.22 6516 78.6 8613 88.6 12519 103.6 15673 113.6 Effective Depth,
reinforcing steel.
Contact VICWEST d (mm)
1.52 7121 78.4 9408 88.4 13662 103.4 17090 113.4
for additional design
Base Steel
information
Nominal 1 2 3 1 2 3 1 2 3 1 2 3
LOAD TABLE
3. Slab Thickness h, is Thickness Span Span Span Span Span Span Span Span Span Span Span Span Span
from underside of (mm) (mm)
steel deck to top of 1200 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 Maximum
concrete. Maximum 1400 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 Specified
0.76
span is not to exceed 1600 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 Uniformly
32h. 1800 20.0 20.0 20.0 20.0 Distributed Load
4. Properties and loads 1200 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
are based on Grade in kN/m 2 (kPa)
1400 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
230 steel (Grade 33 1600 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
steel) with a 0.91
1800 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 Shear Bond
minimum yield stress 2000 19.4 19.4 20.0 20.0 20.0 Coefficents
of 230 MPa (33,000
2200 k 1 = 10.2690
psi) and a maximum
1400 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 k 2 = 221.5570
stress under
1600 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 k 3 = 0.2318
Factored loads of 207
MPa (29,700 psi). 1800 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 k 4 = -0.1439
2000 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
1.22
5. Load values are 2200 18.8 18.8 18.8 20.0 20.0 20.0 20.0 20.0 20.0 20.0
based on Normal 2400 16.2 16.2 18.2 18.2 20.0 20.0
Weight Concrete 2600 14.1 14.1
(density of 2300 2800
kg/m3) (145 pcf) with 1800 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
a minimum 2000 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
compressive strength 20.0 20.0 20.0 20.0
2200 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
of 20.7 MPa (3,000 1.52 2400 18.4 18.4 18.4 20.0 20.0 20.0 20.0 20.0 20.0 20.0 20.0
psi) and a Modular
2600 16.1 16.1 16.1 18.2 18.2 20.0 20.0 20.0 20.0
Ratio n=9
2800 14.0 14.0 16.1 16.1
3000 11.4
Continued on back
In accordance with ongoing efforts to improve our products and their performance, Vicwest
reserves the right to change without notice the specifications contained herein.
The contents herein are for general information and illustrative purposes only and are not intended to
serve as any type of advice. Every effort is made to ensure the accuracy of the information included in
this brochure and it is believed that the information contained herein is accurate and reliable as of the
date of publication. Vicwest, however, does not warrant or represent the accuracy or reliability of any
information included in this brochure. Any reliance on any information without consultation with Vicwest VW00147EN10/10
or a duly authorized representative shall be at the user's own risk. ©2010, Vicwest – All rights reserved
HI-BOND
COMPOSITE FLOOR
HB938
ZF75 GALVANNEAL
LIMIT STATES
DESIGN
IMPERIAL
PHYSICAL DEPTH FROM MAXIMUM FACTORED
SECTION MODULUS Moment of Inertia Note
NEUTRAL REACTIONS
PROPERTIES NOMINAL MASS WITH
MIDSPAN SUPPORT MIDSPAN FULL
AXIS TO
Continued from
STEEL PROFILE CORE AREA OF ZF75 BOTTOM OF EXTERIOR INTERIOR
STEEL GALVANNEAL Sm Ss Im If DECK Y b front
THICKNESS (pounds) (pounds)
(inches) (inches2) (lb/ft2) (inches3) (inches3) (inches4) (inches4) (inches)
(PER FOOT WIDTH) .030 0.471 1.655 0.1784 0.1815 0.1566 0.1672 0.872 747 1076 6. No additional
In accordance with ongoing efforts to improve our products and their performance, Vicwest
reserves the right to change without notice the specifications contained herein.
The contents herein are for general information and illustrative purposes only and are not intended to
serve as any type of advice. Every effort is made to ensure the accuracy of the information included in
this brochure and it is believed that the information contained herein is accurate and reliable as of the
date of publication. Vicwest, however, does not warrant or represent the accuracy or reliability of any
information included in this brochure. Any reliance on any information without consultation with Vicwest VW00147EN10/10
or a duly authorized representative shall be at the user's own risk. ©2010, Vicwest – All rights reserved