Document Review Sheet

From: KEIL To: PETROJET


Contract: KEIL/SIBA/2015/C-051
Document Title: MCC for Chemical Injection
Document No.: C-051-390-MCC-TR2-04-003 Revision:
Touchstone Document No.:
Please respond by: (Refer to Transmittal for Return Date)
The document as listed above has been reviewed and has been found to be:

Reviewed - no comment. Revise and re-submit. Revise and re-submit.


Work may proceed subject to incorporation of Work will NOT proceed.
comments.

*(Tick as appropriate)

Sl. No. Comments (Identify Section/Page/Paragraph) Response


Mechanical/Piping
No Comments.

Civil
Not Applicable.

Electrical
No Comments.

Instrument
Loop folder for all instruments related with this subsystem shall be ICSS sysytem is already sent to KEIL for review
1 included in the ICSS subsystem MCC Dossier. incase of any comment you can add in ICSS
SYSTEM COMMENTS

Page 1 of 4
Classification: General
Sl. No. Comments (Identify Section/Page/Paragraph) Response
2 Noted and covered in section 11.3
To include field instrument installation report for 02-LT-160109.

3 Installation of isolation valve done in field.


Level Transmitter has no isolation valve for maintenance purpose.

Name: Dilio/Suresh/Alaa/Munther Name: Ehab


Date: 20/05/2018. Date:18/05/2018.
Note: Please add/ insert rows for additional comments/ response(s).Do not add additional column.

Page 2 of 4
Classification: General
0

vise and re-submit. Review not Required - for


ork will NOT proceed. information only.

Conclusion

Closed.

Page 3 of 4
Classification: General
Conclusion

Closed.

Closed.

Name: Dilio
Date: 31/05/2018.

Page 4 of 4