UCE observed both TDBFP recirculation valve got opened UCE
and 220vdc voltage became zero along with “220V DC charger-1 &2 fail”. Unit control engineer will inform to other desk engineer to UCE start DG set from UCB. If not started, start from local. Announce from local, DG Main/ Standby has started. Desk Engineer Another Boiler desk engineer will go to Emergency Desk Engineer switchgear. Before making UES dead, Engineer will ensure whether AC Desk Engineer SOP-2, HPCF-2, PW-2 has been changeovered from Emergency bus. Make UES dead and charge UES-A&B from DG Desk Engineer Main/Standby Start AOP-2, ACSOP-2, ACJOP-2, PW-2, HPCF-2 UCE Ensure CW pumps are in unitized mode.(Interconnection UCE valve to be closed) Trip boiler from PB at desk, if not tripped UCE Ensure turbine trips on MFT. UCE Open 400KV breaker & Tie Breaker from Switchyard. UCE Trip all HT drives from local.: Name* Desk engineer Ensure closing of HOTV, LOTV and tripping of gravimetric Desk Engineer feeders. Observe turbine lub oil system and turbine speed. Desk Engineer Isolate Seal Steam when vacuum deteriorates below -0.3, Desk Engineer Close MS-1 & 2 and open MS Strainer drains to UFT. Trip TDBFPs and isolate their steam, and ensure they come Desk Engineer on barring. Charge the emergency cooling of CC Pumps Desk Engineer