This maintenance checklist contains items to inspect weekly, fortnightly, monthly, and annually for an evaporative condenser. Key items include checking the condition of drive belts weekly, operation of the low water level float fortnightly, ball valve and fan shaft bearings monthly, fan motor operation every two months, and the internal and external condition of the condenser weekly. Vibration monitoring checks should also be taken every two months.
This maintenance checklist contains items to inspect weekly, fortnightly, monthly, and annually for an evaporative condenser. Key items include checking the condition of drive belts weekly, operation of the low water level float fortnightly, ball valve and fan shaft bearings monthly, fan motor operation every two months, and the internal and external condition of the condenser weekly. Vibration monitoring checks should also be taken every two months.
This maintenance checklist contains items to inspect weekly, fortnightly, monthly, and annually for an evaporative condenser. Key items include checking the condition of drive belts weekly, operation of the low water level float fortnightly, ball valve and fan shaft bearings monthly, fan motor operation every two months, and the internal and external condition of the condenser weekly. Vibration monitoring checks should also be taken every two months.
ANNUALLY(A) FORTNIGHTLY(F) 2 MONTHLY(2) 6 MONTHLY(6) ITEM NO EVAPORATIVE CONDENSER 17 W 1 Check condition of drive V-belts. Replace if necessary. 18 F 2 Check operation of low water level float. 19 W 1 Check operation of condenser pan water heater and thermostat.
20 M 4 Check ball valve for correct operation, lubricate arm and set for correct water level.
21 M 4 Check and lubricate fan shaft bearings and locking collars.
22 2 8 Check operation of fan motor. Grease adjusting screw. 23 3 12 Check/adjust condenser drives if necessary.
24 W 1 Check correct operation of condenser drive vibration switch.
25 6 26 Check that clean and chlorination is being carried out.
26 A 52 Check on external condition of condenser, I.e. rust, dirt, etc. 27 W 1 Check internal condition of condenser, I.e. rust, dirt, etc. 28 W 1 Check operation of fan dampers. 29 W 1 Check condenser on start-up and when running. 30 F 2 Take vibration monitoring checks. 31 W 1 Check softender brine bin level. Top up with salt as necessary and report on stock level. 32 W 1 Check level in chemical bin. Top up as necessary. 33 W 1 Check operation of dosing pumps. Engineer's Customer's Signature Signature A