You are on page 1of 25

CHAINSA – JHAJJAR – BAMNOLI PIPELINE PROJECT

TENDER FOR SCADA

11/0230/JPK/GAIL/10-R0
CORRIGENDUM – 1
Date – 18.03.2009

Section
Tender
Sr. /
Doc. Clause Description Addition/Deletion/Modification.
No. Clause
Page No.
No.

The cabinets [minimum MODIFIED:-


1100mmheight(1000mm
Cl.No. Page 12
1 height+100mm base The RTU cabinet shall be 2100 height (2000mm
3.5 of 19
plate),1000mm width and height+100mm base channel),1000mm
800mm depth]…….. width,800mm depth

ANNEX. Page 19
2. ANNEX.1 MODIFIED:-
1 of 19
ANNEX.1 Attached.

ANNEX.
3. - - Added :
2
ANNEX.2 Attached.

Page 1 of 1
CHAINSA – JHAJJAR – BAMNOLI PIPELINE PROJECT
TENDER FOR SCADA

REPLIES TO BIDDER’S QUERIES


11/0230/JPK/GAIL/10-R0
Date – 18.03.2009

Section / Tender
Sr. Reply /
Clause Doc. Clause Description Bidder’s Query
No. Clarifications
No. Page No.
The serial port and
Ethernet port
mentioned is for
communication of
RTU with SCADA
Server at Master
Minimum two (2) Ethernet ports In the bill of material not Station and
Page 7 of
Cl. No. encapsulating TCP/IP network mention any IP port in Emergency Master
1 19
3.2 (e) compatibility to IEEE 802.3, the Anex.1.please Station. However for
technical.
10/100 Base –T specifications. mention. the present project,
serial port
communication will
be used with
provision of Ethernet
port for future
communication/use.
GSM/GPRS SIM
charges who will
provide not mentioned
Vendor shall include
in bid.
purchase of SIM
cards with SIM card
2 NIL NIL NIL
re-charge payment
for initial Two
months at their end.

In the Anex 1 SV-2 &


PPCL not mentioned
Page 19 the serial port, please
3 Annex.1 Refer Corr. 1
0f 19 confirm how many
Annex1.
serial ports are
required.
Vendor shall be
provided with 19.2
Kbps channel in
telecomm equipment
In RTU communication
in respective stations
features fiber optic link.
4 NIL NIL NIL and SCADA vendor
Please confirm the
shall supply and
bidder’s scope.
terminate the cable in
the same with
appropriate
connector.
Please confirm the The PDT/LCT shall
PDT/LCT laptop power be suitable for 230V
5 NIL NIL NIL
supply voltage i.e. AC And supplied with
220VAC or 24V DC. adapter/converter

Page 1 of 3
CHAINSA – JHAJJAR – BAMNOLI PIPELINE PROJECT
TENDER FOR SCADA

Redundancy for
communication
module should be
against serial port for
communication with
Please clarify the
Master Station
redundancy point what
/EMS.For other serial
Redundancy should be level of redundancy
ports meant for
Cl. No. Page 8 of achieved at the following levels: required for
6 communication with
3.2 (p) 19 CPU, Power Supply, CPU,POWER
IEDs, redundancy is
Communication modules. SUPPLY,COMMUNICA
not required.
TION Please clarify in
Redundancy for CPU
details.
not required,
However redundancy
for power supply
required.

Local display: Please


confirm size of local
Cl.No.3.2 Page 8 of Local LCD display panel as an display, what kind of Requirement of local
7
(t) 19 integral part of the RTU. software will provide, display is deleted.
what are pages
requirement.
Software will be
supplied with our All softwares supplied
8 NIL NIL NIL standard ,perpetual , by vendor shall be
royalty free license for licensed to GAIL.
right to use.
Whether the IS/Non IS
Barrier for Analog &
IS/Non IS Barriers
Digital inputs to be
9 NIL NIL NIL are not in vendors’
supplied by bidder and
scope of supply.
to be mounted in the
RTU Panel.
Since supply of any
instrument panel is not
considered in bidder’s
scope, We would like to
know whether you need
These are not in
have any
10 NIL NIL NIL vendor’s scope of
indicators/Ann. Lamps
supply.
& Push Buttons to be
mounted on RTU Front
Door or do you like to
go in for miniature LCD
panel on the RTU
Completion schedule
should separate for
supply and completion:

Supply : Six month from


Not Acceptable
IFB 2 FOI
11 Completion Schedule Tender Conditions
1.2.3 Vol I of II Commissioning
Prevail.
/SAT/Handing over:
Three months form
Date of intimation for
site readiness form JP
Kenny / GAIL.

Page 2 of 3
CHAINSA – JHAJJAR – BAMNOLI PIPELINE PROJECT
TENDER FOR SCADA

Attachme
nt – 1
Not Acceptable
Forms 38 & 39 As per Bidder’s
12 EMD Tender Conditions
and Vol I of II Submitted Format
Prevail.
Formats
/ F-4
Attachme
nt – 1
44,45 & Not Acceptable
Forms PBG As per Bidder’s
13 46 Tender Conditions
and Submitted Format
Vol I of II Prevail.
Formats
/ F-9
We are subject to US
Export law restrictions
which debar us from
dealing with some Not Acceptable
GCC 85 & 86
14 Patents & Royalties entities and some Tender Condition
43.1 Vol I of II
countries so we can Prevail.
agree to use of our
products by affiliates
that Gail has at present

Page 3 of 3
ANNEXURE - I

Input/Output list.

“No of consumers
to be polled
Analog Analog Digital Digital Serial
through
Sl. No. Location Input output Input Output Ports
GSM(dialup/GP
(AI) (AO) (DI) (DO) .
RS)”

10
(RS23
1 CHAINSA 42+(5*) NIL 60+(14*) 12+(4*) 2:- 15
4,RS4
85:-6 )
6(RS
232:-
2 SV-2 15 NIL 30 4 10
3,RS4
85:-3)
6(RS232:
-3
3 SV-3 15+(8*) NIL 30+(10*) 4+(4*) RS48 (10*)
5:-3)
10(RS23
BAMNOULI 2:-6,
4 66+(5*) 2 64+(10*) 8+(4*) (20*)
-SV-4 RS48
5:-4)
6(RS
232:-
5 PPCL 23 NIL 35 6 3, 15
RS48
5:-3)
10(RS23
2:-5,
6 JHAJJAR 24+(36*) NIL 35+(35*) 6+(16*) 15
RS48
5:-5

* Vendor shall provide indicated inputs /outputs additionally to be configured/integrated by him as per
owner’s instruction and guidance.

2 Document No. Rev

TECHNICAL SPECIFICATION FOR 11-0230-00-11-2-017 A


RTU
ANNEXURE - II

P & ID

3 Document No. Rev

TECHNICAL SPECIFICATION FOR 11-0230-00-11-2-017 A


RTU

You might also like