CHANGES IN NEW OISD-116, 2010

S.No. Clause as per old OISD-116, 2008 Clause as per old OISD-116, 2010
1 Clause:4.2.3 Clause: 4.2.3
Automatic Actuated Rim seal Automatic Actuated Rim seal
Protection System for Floating Protection System for External
Roof tanks: Floating roof tanks:
Automatic Actuated rim seal fire extinguishing Automatic actuated rim seal fire detection
system should be considered for floating roof and extinguishing system shall be provided on
tank diameter of 60 meters and above for all existing as well as new external floating roof
class “A” products. The Automatic Actuated rim tanks storing Class A petroleum. Only those
seal fire extinguishing system may be based Rim seal protection systems, which use the
on Foam Flooding or Clean Agent Flooding linear heat hollow metallic tube type detectors
mechanism. This is in addition to the with foam based extinguishing media, either for
water spray and semi-fixed foam system on all existing/ new or for replacements of existing
the floating roof tanks storing class A & B detection system when due, shall be used.
products. Foam Flooding system: Selection These detection systems shall be certified by
and design of foam based fire protection any of the international certifying agencies like
system should be as defined in latest Standard UL, FM, VdS or LPC to ensure that those
for Foam systems - NFPA-11& 11A. systems are used which meet with highest
Clean Agent Flooding system: Selection of international standards of safety certification.
Clean Agent and system design for fire (Refer Explanatory Note for Implementation in
protection should be in line with the “Standard Annexure-IX). The minimum requirement for
on Clean Agent Fire Extinguishing Systems – design of the system is given in Annexure VII
NFPA 2001(Edition 2004) and the latest”. The This shall be in addition to the water spray and
clean agent should also comply with the semi-fixed foam system on all the floating roof
requirements of the “Ozone Depletion tanks storing class- A products.
Substances Regulation & Control Annexure- IX
Rules,2000,Ministry of Environment & i) The rim seal protection system shall
Forests, Government of India. Listed Clean be implemented in all existing
Agents like Trifluoroiodide and others can be installations progressively within 24
used as fire suppressant for floating roof rim months for class A floating roof tanks
seal Fire Protection System. Listed Clean above 5000 KL capacity & balance
Agents like Fluoroketone and others can be
class A floating roof tanks
used as fire suppressant in Control rooms and
progressively in 36 months from the
Computer rooms.
date of issuance of the standard.
ii) Installation of rim seal system shall
be done for all new/upcoming
external floating roof tanks storing
Class A petroleum storage tanks with
immediate effect.
iii) The automatic actuated rim seal fire
detection & extinguishing system
already provided in existing tanks
shall be replaced with linear heat
hollow metallic tube type detectors
with foam based extinguishing media
whenever the existing system is due
for replacement or shall be replaced
within a period of 4 years from the
day of installation whichever is
earlier.
2 Clause 4.2.5 Clause 4.2.5
Water Spray System in Process Unit Water Spray System in Process Unit
- Water spray rings for columns of - Water spray rings for columns of
height more than 45 M should be height more than 45 M shall be
provided provided
3 Clause 4.2.7 Clause 4.2.7
Clean Agent ( Halon substitute) for Clean Agent ( Halon substitute) for
Control rooms Control rooms
Selection of Clean Agent and design of Fire Selection of Clean Agent and design of Fire
protection system for process control rooms, protection system for process control rooms,
computer rooms and pressurised rooms should computer rooms, SRR and pressurized rooms
follow the Standard on “Clean Agent shall follow the Standard on “Clean Agent
Extinguishing systems NFPA Standard 2001 Extinguishing systems NFPA Standard 2001
(Edition 2004) including its safety guidelines (Edition 2008 and the latest) including its safety
with respect to “Hazards to Personnel”, guidelines with respect to “Hazards to
electrical clearance and environmental factors Personnel”, electrical clearance and
in line with environmental considerations of environmental factors in line with
Kyoto Protocol. Clean Agents like inert gas, environmental considerations of Kyoto &
Fluoroketone can be used as fire suppressant Montreal Protocols and latest MoEF
in Control rooms and Computer rooms. regulations. Clean Agents like inert gas,
Fluoro-ketone can be used as fire suppressant
in Control rooms & SRR and Computer/Server
rooms. (For areas to be covered with clean
agent refer OISD STD 163).
4 Clause:5.2 Clause:5.2
FIREWATER FLOW RATE FIREWATER FLOW RATE
- Fire water flow rate for supplementary - Fire water flow rate for based on using
stream, shall be based on using 4 4 single hydrant outlets and 1 HVLR
single hydrant outlets and 1 monitor (1000GPM) simultaneously. Capacity
simultaneously. Capacity of each of each hydrant outlet as 36 m 3/hr and
hydrant outlet as 36 m3/hr and of each of each monitor as 228 m3/hr shall be
monitor as 144 m3/hr may be considered at a pressure of 7 kg/cm 2g.
considered at a pressure of 7 kg/cm2g.
5 Clause: 5.7.2 Clause: 5.7.2
Monitors Monitors
- Variable flow monitors may be installed - Field adjustable variable flow monitors
at critical locations. shall be installed at critical locations.
These shall be UL/FM listed /
approved.
6 Clause: 5.7.4 Clause: 5.7.4
Mobile/Fixed High Volume Water/Foam Fixed Remote / Manual operated High
Monitors Volume Long Range Water cum Foam
Provision for fighting storage tank fire from Monitors
road side through mobile/fixed/variable flow volume long range water cum foam monitors
high volume long range monitors should be (Capacity 1000 GPM & above) shall be
considered at critical storage locations. variable flow type with flow adjustable manually
in the field, with foam induction to monitor
being possible from minimum 60 m distance
from the monitor and shall be provided in
i) Tank farm area.
ii) Inaccessible areas such as
column, reactor, compressor
house etc in critical units like
CCRU, DHDS, HCU, Hydrogen,
FCCU, DCU, CDU etc
iii) Critical equipments at higher
locations (above 45 mtrs.)
The basic water cum foam monitors shall be
UL/ FM listed / approved. The electrical or
hydraulic remote control mechanism shall be in
line with Hazardous Area Classification.
Following criteria shall be followed for
installation of variable flow foam-cum-water
monitors in tank farm area:
a) Remote/ manual operated variable flow
monitors shall be installed in such
ways that all the tanks in the
installation are within the horizontal
range of foam throw.
b) Number and capacity of monitor shall
be provided in such a way that foam
application rate from the monitors meet
requirement of foam application rate
(8.1 LPM/m2) for full surface tank fire
as per NFPA- 11
For determining the total foam solution
requirement, potential foam loss from wind and
other factors shall be considered.
Annexure-IX
i) Shall be provided progressively
within 24 months from the issuance
of the Standard for existing tank
farms.
ii) Installation of monitors for all
new/upcoming tanks shall be done
along-with commissioning of the
tanks.
7 ------------------------- New Clause Added
Clause:10.0
Modernization plan for firefighting
equipments:
Rapid intervention, Water Mist cum
Compressed air Foam Technology The
technology of water mist cum compressed air
foam system involves creation of water mist or
a mist combination of water and foam using
specialized nozzles. The mist droplets create
an enlarged surface area resulting in rapid
cooling due to absorption of heat. Mist droplets
turn to steam on contact with fire resulting in
blanketing effect, thereby cutting off oxygen &
extinguishing the fire very fast. This is achieved
by propelling mixture of water & foam using
compressed air. Water mist cum Compressed
air foam system is for low as well as high
pressure rating. The suitability of the system
shall be decided for the particular application
based on minimum recoil jerk, safety of the
user and refillability criteria. The system shall
be approved as per highest international
safety standard DIN EN3 or equivalent for
maximum fire rating. The water mist cum
compressed air foam system has advantage
over conventional fire fighting systems (DCP,
CO2) as it provides combined effect of cooling
& blanketing which results in efficient fire
fighting thereby helping control fire in the initial
stages. Mist also helps in blocking radiant heat
making it easier for the fire fighter to approach
the fire. In addition to the conventional fire
extinguishing systems such as foam, carbon-
dioxide and DCP, the Backpack/ Portable/
Trolley mounted (mobile) water mist cum
compressed air foam technology should be
used to fight fires at critical locations such as
hot pumps handling fluids above auto ignition
temperature, like column bottom pumps at
CDU, VDU, Coker, FCCU & HCU units, any
other high temperature column, exchangers
etc. Criteria to determine the quantity is given
in the following table.
CHANGES IN NEW OISD-117, 2010

S.No. Clause as per old OISD-117, 2008 Clause as per old OISD-117, 2010
1 Claus:4.2.2 Clause:4.2.2
One single largest risk shall be considered for The fire water system shall be provided based
providing facilities. on two largest fire contingencies
simultaneously for all locations where total
tankage in the terminal is more than 30,000
KL.
Wherever water replenishment @ 50% is
available, single fire contingency shall be
considered for Fire water storage.
2 Clause: 4.2.12 Clause: 4.2.12
Automatic actuated rim seal fire extinguishing Automatic actuated rim seal fire detection and
system may be provided based on foam or clean extinguishing system shall be provided on all
agent flooding mechanism on floating roof tanks existing as well as new external floating roof
having diameter larger than 60 m. This is in tanks storing Class petroleum. Only those Rim
addition to the fixed water spray system and seal protection systems, which use the linear
Fixed foam system or Semi-fixed foam system on heat hollow metallic tube type detectors with
all floating roof tanks storing Class A & B foam based extinguishing media, either for
petroleum. Foam Flooding System : Selection existing/ new or for replacements of existing
and design of foam based flooding system
detection system when due, shall be used.
should be as defined in latest “Standard for Foam
These detection systems shall be certified by
Systems : NFPA-11 & 11A”. Clean Agent
Flooding System : Selection and design of clean
any of the international certifying agencies like
agent based flooding system should be in line UL, FM, VdS or LPC to ensure that those
with the “Standard on Clean Agent Fire systems are used which meet with highest
Extinguishing Systems - NFPA international standards of safety certification.
2001(Latest Edition). The clean agent should This is in addition to the fixed water spray
also comply with the requirements of “Ozone system and fixed foam system or Semi-fixed
Depletion Substances Regulation & Control foam system on all floating roof tanks storing
Rules - 2000, Ministry of Environment & Forests, Class A & B petroleum.
Government of India. Listed clean agents like Annexure VI:
Trifluroiodide & others can be used as fire i) The rim seal protection system
suppressant for floating roof rim seal fire shall be implemented in all existing
protection System. Listed clean agents like
installations progressively within 24
Fluroketone and others can be used as fire
suppressant in control room & computer rooms. months for class A floating roof
The clean agent based protection system tanks above 5000 KL capacity &
consists of an in-built fire detection, control and balance class A floating roof tanks
actuation mechanism. If a rim seal fire occurs, its progressively in 36 months from
heat causes one or more spray nozzles to the date of issuance of the
open and the extinguishing gas (clean agent) is standard.
applied on the surface of fire and simultaneous
alarm is also sounded. Refer (Annexure-V) for a
ii) Installation of rim seal system shall
typical system of automatic rim seal fire be done for all new/upcoming
protection using clean agent. external floating roof tanks storing
Class A petroleum storage tanks
with immediate effect.
iii) The automatic actuated rim seal
fire detection & extinguishing
system already provided in existing
tanks shall be replaced with linear
heat hollow metallic tube type
detectors with foam based
extinguishing media whenever the
existing system is due for
replacement or shall be replaced
within a period of 4 years from the
day of installation whichever is
earlier.
3 Clean Agent (Halon substitute) based flooding Clause : 4.2.14
system may be considered for control rooms, Clean Agent (Halon substitute) based
computer rooms and pressurized rooms in major flooding system should be provided for control
locations having automated pipeline rooms, computer rooms/ repeater station and
receipt/dispatch and/or TW/TT loading facilities. pressurized rooms in major locations having
automated pipeline receipt/dispatch and/or
TW/TT loading facilities.
4 New Clause Added in : 4.3.7
For marketing terminals & Petroleum Depots, the
remote operated high volume long range water
cum foam monitors (Capacity 1000 GPM ) to fight
tank fires shall be provided which shall be of
variable flow 1000/750/500GPM (with flow
adjustable manually in the field). Foam induction
to the monitor shall be possible from minimum 60
m distance from the monitor. For Pipeline tank
farms & Central Tank Farms, Remote operated
high volume long range water cum foam monitors
(capacity 1000 GPM and above) to fight tank fires
shall be provided which shall be of variable flow
type (with flow adjustable manually in the field).
Foam induction to the monitor shall be possible
from minimum 60 m distance from the monitor.
These high volume long range monitors shall be
located more than 45 m from the hazardous
equipment. The basic water-cum-foam monitors
shall be UL/FM listed/approved. The electrical or
hydraulic remote control mechanism shall be in
line with Hazardous Area Classification. Following
criteria shall be followed for installation of variable
flow foam-cumwater monitors:
a) Remote operated variable flow monitors
shall be installed in such a way that all
the tanks in the installation are within the
horizontal range of foam throw.
b) Minimum two nos. of monitors shall be
installed for each tankfarm having
aggregate storagecapacity up to 10,000
KL in the installation to meet the
requirement as per S.No. (a) above.
c) In tank farm having aggregate storage
capacity more than 10,000 KL, additional
monitor/s should be provided (depending
on tank interdistance & throw of the
monitor).
d) Number & Capacity of monitor shall be
provided in such a way that the foam
application rate from themonitors meets
requirement of foam application rate
(8.1LPM/m2) for full surface tank fire as
per NFPA-11.
e) For determining the total foam solution
requirement, potential foam loss from
wind and other factors shall be
considered.
Annexure VI
i) Shall be provided progressively
within 24 months from the issuance
of the Standard for existing tank
farms.
ii) Installation of monitors for all
new/upcoming tanks shall be done
along-with commissioning of the
tanks.

5 4.4.11 FOAM QUANTITY REQUIREMENT 4.4.11 FOAM QUANTITY REQUIREMENT


Size of Terminal Water/Foam Size of Terminal Water/Foam
(In KL) Monitor (Nos.) (In KL) Monitor (Nos.)
For Installation having Nil. For Installation having Nil.
aggregate capacity of aggregate capacity of
1000 KL 1000 KL
For Installation having Minimum 1 No. up to For Installation having Minimum 2 No. up to
aggregate capacity up 1600LPM aggregate capacity up 1000GPM
to 10,000 KL to 10,000 KL
For Installation having 1 No. of 2400 lpm. For Installation having More than 2 No. of
aggregate capacity up aggregate capacity no. 1000 GPM(as per
to 25,000 KL more than 10,000 KL 4.3.7(vi)c
For Installation having 2 Nos. of 2400 lpm.
aggregate capacity
more than 25,000 KL