SEISMIC LOAD

Values to consider:
By using the application, Tremors, which gives the distance from one location to the nearest
West Valley Fault, it was found out that the closest distance to known seismic source from
Tagaytay Southridge Estates is 8.32 km.
a. Near Source Factor

Solving for 𝑁𝑎 by interpolating:


𝑁𝑎(8.32 𝑘𝑚) − 𝑁𝑎(5 𝑘𝑚) 𝑁𝑎(10 𝑘𝑚) − 𝑁𝑎(8.32 𝑘𝑚)
=
8.32 𝑘𝑚 − 5 𝑘𝑚 10 𝑘𝑚 − 8.32 𝑘𝑚
𝑁𝑎(8.32 𝑘𝑚) − 1.2 1 − 𝑁𝑎(8.32 𝑘𝑚)
=
8.32 − 5 10 − 8.32

𝑁𝑎(8.32 𝑘𝑚) = 1.0672

𝑁𝑣(10 𝑘𝑚) − 𝑁𝑣(8.32 𝑘𝑚) 𝑁𝑣(8.32 𝑘𝑚) − 𝑁𝑣(5 𝑘𝑚)


=
10 𝑘𝑚 − 8.32 𝑘𝑚 8.32 𝑘𝑚 − 5 𝑘𝑚
1.2 − 𝑁𝑣(8.32 𝑘𝑚) 𝑁𝑣(8.32 𝑘𝑚) − 1.6
=
10 − 8.32 8.32 − 5

𝑁𝑣(8.32 𝑘𝑚) = 1.3344

b. Seismic Coefficients
Solving for 𝐶𝑎 :
𝐶𝑎 = 0.4𝑁𝑎 𝐶𝑎 = 0.4(1.0672)𝐶𝑎 = 0.42688
Solving for 𝐶𝑣 :
𝐶𝑣 = 0.56𝑁𝑣 𝐶𝑣 = 0.56(1.3344)𝐶𝑣 = 0.747264

c. Total Load

𝑊𝑻 = 𝑊𝟏 + 𝑊𝟐 + 𝑊𝒓𝒐𝒐𝒇
where:

𝑊1 = ∑ 𝑊𝑐𝑜𝑙𝑢𝑚𝑛 + ∑ 𝑊𝑏𝑒𝑎𝑚 + ∑ 𝑊𝑠𝑙𝑎𝑏 + ∑ 𝑊𝑤𝑎𝑙𝑙

𝑊1 = (12)(29.6)(2.8)(0.3)(0.3) + (23.6)(78.2)(0.4)(0.3) +
(23.6)(0.11)(15.9)(7.5) + 2(23.6)(7.5)(0.2)(3.6) + 2(23.6)(15.9)(0.2)(3.6)=1397.6

𝑊2 = (12)(29.6)(2.8)(0.3)(0.3) + (23.6)(78.2)(0.4)(0.3) +
(23.6)(0.11)(15.6)(7.2) + 2(23.6)(7.2)(0.2)(2.4) + 2(23.6)(15.6)(0.2)(2.4)=1093.6

𝑊𝑟𝑜𝑜𝑓 = (23.6)(0.3)(120.2) = 914.736


d. Elastic Fundamental Vibration of the Structure, T
3
𝑇 = 𝐶𝑡 (ℎ𝑛 )4
3
𝑇 = (0.0731)(8.8)4
𝑇 = 0.3735

e. Design Base Shear


𝐶𝑣 (𝐼)(𝑊) (0.747264)(1.00)(3400.0306)
𝑽= = 3
𝑅𝑇
8.5(𝐶𝑇 )(ℎ𝑛)4
(0.747264)(1.00)(3405.969)
= = 𝟖𝟎𝟏. 𝟔𝟖𝟕𝟔𝟗𝟖𝑲𝑵
8.5(0.0731)(0.3735)

Max V,
2.5𝐶𝐴 (𝐼)(𝑊) 2.5(0.4272)(1.00)(3405.969)
𝑽= = = 𝟒𝟐𝟕. 𝟔𝟐𝟗
𝑅 8.5
Min V,
𝑽 = 0.11𝐶𝐴 𝐼𝑊 = 0.11(0.4272)(1.00)(3405.969) = 𝟏𝟓𝟗. 𝟗𝟗𝟑
0.8𝑍(𝑁𝑣 )(𝐼)(𝑊) 0.8(0.4)(1.3344)(3405.969)
𝑽= = = 𝟏𝟕𝟏. 𝟏𝟎𝟑
𝑅 8.5

(𝑉−𝐹𝑇 )(𝑊𝑋 )(ℎ𝑋 )


𝑭𝒙 = ∑(𝑊𝑖 )(ℎ𝑖 )
; 𝑭𝑻 = 0.07𝑇𝑉

3
(𝑽 − 𝑭𝒕 ) = 427.629 − 0.07 [(0.0731)(8.8)4 ] (427.629) = 𝟒𝟏𝟔. 𝟒𝟒𝟖𝟗

(416.4489)(1397.6274)(4)
𝑭𝟐 = = 𝟔𝟎. 𝟕𝟗𝟔
(3405.969)(8.8)
(416.4489)(914.736)(6.8)
𝑭𝟑 = = 𝟖𝟔. 𝟒𝟐𝟔
(3405.969)(8.8)

For Earthquake load


(416.4489)(1397.6274)(4)
𝑭𝟐 = = 𝟏𝟎𝟑. 𝟎𝟖𝟗
(2008.626)(8.8)
(416.4489)(914.736)(6.8)
𝑭𝟑 = = 𝟏𝟒𝟔. 𝟓𝟒𝟗𝟔
(2008.626)(8.8)

To not stress only one column, transfer concentrated loads to uniform loads along 7.5
m,

Y-FRAME
𝐹2
= 19.5399
7.5
𝐹1
= 13.7452 𝑘𝑁⁄𝑚
7.5
X-FRAME

𝐹2
= 9.217
15.9
𝐹1
= 6.483
15.9

Then multiply to respective tributary spans,


19.5399(1.575) = 30.775 𝑘𝑁 A
19.5399(3.75) = 73.275 𝑘𝑁 B
19.5399(2.175) = 42.499 𝑘𝑁 C
13.7452(1.575) = 21.649 𝑘𝑁 D
13.7452(3.75) = 51.545 𝑘𝑁 E
13.7452(2.175) = 29.896𝑘𝑁 F

X-FRAME

9.217(3.075) = 28.342KN A
9.217(6.075) =55.993KN B
9.217(4.875) = 44.9333KN C
9.217(1.875)=17.282KN D
6.483(3.075) = 19.937KN E
6.483 (6.075) =39.388KN F
6.483 (4.875) = 31.608KN G
6.483 (1.875)=12.157KN H
Maximum Sidesway:
FORMULAS:

∆𝑠 = 26.8𝑚𝑚(𝑦 − 𝑓𝑟𝑎𝑚𝑒)
∆𝑠 = 19.66𝑚𝑚(𝑥 − 𝑓𝑟𝑎𝑚𝑒)
∆𝑀 = 0.7(∆𝑆 )

∆𝑀𝑦 = (0.7)(26.8)(8.5)
∆𝑀𝑦 = 159.46𝑚𝑚(𝑦 − 𝑓𝑟𝑎𝑚𝑒)
∆𝑀𝑥 = (0.7)(19.66)(8.5)
∆𝑀𝑥 = 116.98𝑚𝑚(𝑥 − 𝑓𝑟𝑎𝑚𝑒)

Max Sidesway= H x 0.025

𝑀𝑎𝑥. 𝑆𝑖𝑑𝑒𝑠𝑤𝑎𝑦 = 8𝑚(1000)(0.025)


𝑀𝑎𝑥. 𝑆𝑖𝑑𝑒𝑠𝑤𝑎𝑦 = 200𝑚𝑚