Relay Setting Calculation 60 MVA
Relay Setting Calculation 60 MVA
% Impedance = 10
=60*1000000/ 66000*√3
= 524.8 A
CTR= 600/1 A
= 0.874 A
=60*1000000/ 33000*√3
= 1049.758 A
CTR= 1200/1 A
1
= 0.874 A
Slope 1 = 30 % (full tap change range that is 10+10 =20 +10% extra bias)
= 70 %
= 524.8/0.1= 5248 A
CTR = 600/1 A
CT ratio= 600/1A
288.97/600 = 0.96
TMS = 0.05
2
Relay operating time = 155 ms
CT sec = 1A
Setting = 5.250 X In
CTR : 600/1A
TMS: 0.05
104.6/600 = 0.174
Setting = 0.170 x In
Setting: 1.750 x In
3
UNDERVOLTAGE PROTECTION
80% of 110 V = 88 V
Delay = 0 sec
OVERFLUXING PROTECTION
For 1.10 P.U V/F = 2.2 *1.1*50= 121 Volts Phase to phase
Delay = 10.00 s
Delay= 1.00 s
HV REF PROTECTION
CTR = 600/1 A
Rct= 3 ohm
RL = 0. 3 ohm
4
Vs = 5248/600(3+2*0.3)
Vs= 31.48 V
RS = VS/IS
IS = 0.1 A= 31.48/0.1
Delay = 0 sec
LV REF PROTECTION
CTR = 1200/1 A
Rct= 3 ohm
RL = 0. 3 ohm
Vs = 10497/600(3+2*0.3)
Vs= 62.98V
RS = VS/IS
IS = 0.1 A= 62.98/0.1
Delay = 0 sec
997.12/600 = 1.66
5
Secondary = 1.6 x In