Professional Documents
Culture Documents
D. BMS CONTROLLER
INSTRUCTION MANUAL
CHECKIO
OF AUTOMATIC B O I L E R
DRAWN
C O N T R O L SYSTEM
CONFERRED SCALE
K1459 N52-99K-N500
1 MITSUBISHI HEAVY INDUSTRIES, LTD.
NAGASAKI SHIPYARD & MACHINERY WORKS
7252 E
DRAWN ISSUED
/ \M
OINER
7, 8, /*, AS} 2f, 27, 28, 33,
SHIP YARD MITSUBISHI HEAVY INPUSTRIES.
at ft J5r CO., LTD NAGASAKI SHIP YARD
-20-93'
SHIP NO. SAMSUNG
/ICC
H. NO. 1139/40/44
SHIP NAME
AB S
* m
[ I ] GENERAL DESCRIPTION
[H] OPERATING INSTRUCTION
[ 1 ] COMPONENTS
[IV] ALARM DISPLAY
D, BNS CONTROLLER
SAM
PAGE 1
A. INSTRUCTION MANUAL OF BOILER CONTROL SYSTEM
a. U, r
/. x
v.
\ •. v o-
SA
PAGE 2
A. INSTRUCTION MANUAL OF BOILER CONTROL SYSTEM
The Boiler Control Panel is provided with built-in operation, control and
interlock devices required for the running of the boiler.
This control panel perforns the automatic and manual runnings of the
boiler,gives an alarm to tarn the operator if an abnormality occurs
during running, and stops the boiler in an emergency mode by immediately
shutting down the fuel oil supply to the boiler if such an abnormality
should be too serious to continue running any longer.
CAPTION
This manual has been prepared primarily for the instructions of remote-
control running of the boilers.
In running, the boiler, boiler auxiliary machines, oil burners, boiler
automatic control system, equipment attached to the boiler, and air flue,
oust have always been adjusted in good order.
SAM
PAGE 3 ,
( f i
[D ] CHECKS AND OPERATION BEFORE RUNNING
1) AC SOURCE FAIL
2) SEQUENCES ABNOR
3) MANUAL TRIP
4) P. D. FAN TRIP
5) DRBM LEVEL LOI-LOI
6) ATOMIZ PRESS LOI-LOI
7) IGNITION FAIL > Alarm laips shall be "OFF"
8) FLAME FAIL
9) FLAME EYE ABNOK
10) IGNITION VALIDITY TIME OVER
11) BNR PI STOP V/V ABNOR
12) P. 0. PRESS LOI-LOI
13) CONTROL AIR PRESS LOI-LOI
14) F. 0. TEMP. LOI-LOI
CAUTION
(1) Ihile in operation, the indication lanps on the control panel
shall be observed and the boiler checked periodically.
SAM
PAGE 4
B. INSTRUCTION MANUAL OFJUIRNER CONTROL SYSTEM
[ n] OPERATION OF BURNER
A. MANUAL OPERATION OF BURNER START
B. MANUAL OPERATION OF BURNER STOP
C. AUTOMATIC RUNNING OF BOILER
D. OPERATION PANEL GRAPHIC FLOI CHART
E. INTERLOCK BY-PASS OPERATION
[ V] ALARMS
A. PATTERN OF ALARMS
B. BOILER SET POINT LIST
SAM
PAGE 5
B. INSTRUCTION MANUAL OF BURNER CONTROL SYSTEM
In this control, the remote manual and automatic operations are available
on one single-throat burner provided at the ceiling of the boiler.
Its control unit contains a programmable sequencer which can perform the
sequential running of FURNACE PURGE and Pilot Burner and the automatic
operation of the burner piston valve by linking with the boiler Protective
System and the A.C. C.
Also, it transmits the automatic adjustment commands of combustion air
quantity and fuel oil quantity to the A. C. C.at the siart/stop of the
burner.
In an emergency, this control system shuts off the fuel supply to the
burner for the boiler protection.
SAM
PAGE 6
C I] SELECTION OF OPERATING MODES
During the initial start-up and under "INTERLOCK BY-PASS" mode, the boiler
is operated from this B/S BOILER CONTROL PANEL, froi which you can select
*iie following modes.
1. SELECTION OF AUTO/MAN.
The operator can select his desired mode unless otherwise specified.
( a) A. B. C. MAN.
If controller is under ABNOR, this controller is forced
to set A. B. C. to its manual mode.
Also, the F. 0. & AIR controller is set to its manual mode .
in [ I ] A-2 (a), (c).
( b) A. B. C. AUTO
( c) BURNER MAN.
INTERLOCK BY-PASS MODE, the Man Mode is forced to be selected.
( d) BURNER AUTO
( c) EMERGENCY MODE
This mode must be selected when the burner sequencer is unavailable.
See [ H ] E-3 Emergency Operating Mode.
SAM
PAGE 7
PD
3. SELECTION OF BOILER MODE
4. IGS OPERATION
fhen in the IGS mode, the burner is normally kept »in operation.
The IGS lode cannot be selected while sootblower is operated.
The sootblower cannot be operated while in the IGS mode, either.
SAM
PAGE 8
B. SELECTION OF BOILER START MODE
This mode is selected to start from the cold boiler with the burner
atomizing steam and the F. 0. heating steam not provided.
( 1 ) Fuel oil used : A HEAVY OIL
( 3 ) Mode switch
• "F.O. TEMP. BY-PASS" • F. 0. temp, low sequence
SIITCH ON interlock is by-passed.
• BURNER OPERATION \ Automatically set to "MAN"
MODE "MAN" •then selected by
• A.C.C. OPERATION F. 0. temp, byrpass switches.
MODE "MAN"
CAUTION
SAM
PAGE 9
2 . CHANGE-OVER OPERATION FROM BOILER COLD MODE TO ITS HOT MODE
This mode is selected to start from the hot boiler with the
burner atomiz. steal provided and A-oil used.
( 1 ) Fuel oil used A HEAVY OIL
( 3 ) Mode switch
• "P.O. TEMP. BY-PASS" F. 0. Temp, low sequence
SIITCH ON interlock is by-passed.
• BURNER OPERATION
MODE "MAN" Automatically set to "MAN'
• A.C.C. OPERATION when selected by F. 0. temp,
MODE "MAN" by-pass switches.
CAUTION
(1) This mode is to be used at the change-over of A-Oil to C-oil only,
and watching at the boiler side must not be neglected at this
change-over.
After completion of this cohge-over, the Normal Mode or the
Cold Mode must be selected without delay.
(2) To burn A-Oil by Steal Jet Atomizer, the air/fuel ration must
be sufficiently adjusted.
SAM
PAGE 10
3. BOILER HOT START MODE
This mode is selected to start froi the hot boiler with the burner
atoiiz. steam provided and C-oil used.
( 1 ) Fuel oil used C-HEAVY OIL
( 3 ) Mode switch
• BURNER OPERATION The first start is set to "MAN'
MODE "MAN" After the start. "AUTO" can be
selected.
CAUTION
(1) fhen the boiler is operated with C-OIL and F. 0. PUMP is put under
"AUTO" node, F. 0. temperature is set automatically and the following
operations can be done.
^.a) The F. 0. pump automatically starts or stops according to
the temp, of fuel oil before the burner.
F. 0. temp, low (Rf. NO. 1 120SEC. or more)-••-START
F. 0. temp. high(RI. NO. 1 80SEC. or less)-•••STOP
SAM
PAGE 11
C. MASTER/SLAVE BOILERS OPERATION
Automatic start
The master boiler automatically starts up as the S. D. pressure
reaches 12 Kg/cm2.
Automatic stop
The master boiler automatically stops operating as the S. D.
pressure reaches 16. 3 Kg/cm2.
SAM
PAGE 12
/if
(4) Slave boiler autoiatic start/stop
Automaticstart
As the master boiler load increases and F. 0. pressure
reaches 10 Kg/ci2 (60X load), the slave boiler automatically
start its operation
Autoiatic stop
As the master boiler load decreases and the P.O. pressure gose
down to 4.0 Kg/cm2 (20& load), the slave boiler automatically
stop its operation
NOTE :
Even when the slave-boiler burner was manually ignited and the
steam pressure reached the setfpoint,thereafter thereby placing
the slave boiler in the "AUTO RUN" mode and then only when the
slave-boiler burner "AUTO" is selected, the slave boiler does
not stop automatically unless the slave boiler steam pressure
reaches 16.3 Kg/cm2 even if the master boiler's load goes down
under 20&
SAM
PAGE 13
(c ) SLAVE BOILER FUNCTIONS
Automatic start
then the slave boiler S. D, pressure has reached 13 Kg/cm2 or
when the master boiler F.0.pressure has reached 10 Kg/cm2.
Automatic stop
then the slave boiler S. D. pressure has reached to.master set
pressure or when the master boiler F. 0. pressure has gone down
to 4. 0 Kg/cm2 and below.
SAM
PAGE 14
( d) MASTER/SLAVE BOILER OPERATION
SAM
PAGE 15
[H] OPERATION OF BURNER
A. MANUAL OPERATION OF BURNER START
Burner Ignition.
By turning on the "BNR ON" Button, the following burner ignition
sequence starts to ignite the burner.
Also, the interlock conditions (nark O) of the ignition sequence
are established by automatic operation in A. C. C. Auto Mode.
but in Man. mode, the manual operation (| |) according to
the sequence step is needed.
1. Burner Ignition
O P. D.FAN RUN
SAM
PAGE 16
(6) Furnace purge condition "PRE-PURGE START'
established LAMP ON IL
SAM
PAGE 17
(9) Pilot ignition
PILOT BNR PUMP START 'PILOT PUMP START' GL
LAMP ON
'BNR OFF" WL
LAMP FLICKER
SAM
PAGE 18
(11) Burner ignition
(The following motion is made 3 sec. after check of the pilot burner
ignition. )
F. 0. valve full open : "BNR.F.O. V.OPEN" LAMP ON WL
: "BNR.BURN ING" LAMP ON WL
: "IGNITION F. 0. RATE"
LAMP OFF
: "IGNITION AIR RATE"
LAMP OFF
(12) PILOT BNR IGNITOR SPARK STOP
(F. 0. valve opening must have been confirmed or 8 sec.
lust have passed after pilot BNR ign. start.)
(13) Pilot stop
(The following motion is lade 15 sec. after pilot BNR
ignition start)
SAM
PAGE 19, r>
B. MANUAL OPERATION OF BURNER STOP
By selecting the Burner Run Mode to "MAN" and turning on the "BNR OFF"
Button, the burner shut-down sequence starts to stop the burner.
The interlock conditions (O) of the shut-down sequence are established
by ATOMIZER autoiatic operation, under A. C. C. Auto Mode, but under A. C. C.
Man. Mode, the manual operation ([ H) according to the sequence step is
necessary.
(1) Burner run lode
'BNR MANU." LAMP ON WL
v
(11) Furnace after-purge start 'PRE-PURGE START' •" WL
LAMP FLICKER
SAM
PAGE 21
(13) Completion of furnace after-purge : "PRE-PURGE START" LAMP OFF
F. D. FAN AUTO STOP
SAM
PAGE 22
/J-
2, AUTOMATIC RUNNING IN MASTER/SLAVE MODE
SAM
PAGE 25
/jf
c. AUTOMATIC RUNNING OF BOILER
BOILER INDEPENDENT AUTOMATIC OPERATION
By selecting the A. C. C.and the Burner Run Mode to "AUTO". Boiler
Automatic Running can be carried out.
The running conditions and operation are detailed below.
O See [ I ] - B
(then Stm. Drum Press.is below 5kg/cm2 F.0. FLOW Control is selected to
MANU. and then to AUTO after BNR Ignition start. )
v
(5) Burner auto node
: BNR "AUTO" LAMP ON- WL
SAM
PAGE 23
(6) Stealing up mode "STEAMING UP" LAMP ON WL
Pressure is raTsed automatically by limiting combusion load
, in proportion to steam drum Dressure. _ . ' -
STEAM 0RUM PRESS LOAD LIMITER
(Kg/cm2) •
5-10 6096LOAD
1 0~ 1 0 0 %L 0AD
O Under TANKER SERVICE MODE. STM. Drui Press, has reached 12 kg/cn2/
v
(11) BURNER ignition completed
v
BOILER AUTOMATIC OPERATION
SAM
PAGE 24
(4) BOILER AUTO STAND-BY 'STAND-BY" LAMP ON- WL
CAUTION
1 SELECTION OF I.G. S. MODE
This selection is used to run the Inert Gas System.
J,G.S. MODE ON
(1) Burner auto Stop is by-passed.
(2) The boiler minimum load is limited to the larger value of 301
(3) The soot blower steam valve is fully closed.
3 LOADED OPERATION
After the pressure rise is completed and steam drum pressure
reaches the set pressure (AUTO RUN/LAMP ON), perform loaded
operation of boiler.
SAM
PAGE 26
D, OPERATION PANEL GRAPHIC FLOW CHART
SAMSUNG (STBD BLR SIDE)
The operations (A-l ~~ B-6) described below show how to start and stop the
boiler by way of "BNR ON" / "BNR OFF" switch, when the boiler is in the
conditions 1 ~ 7 specified as follows.
1. It is Master Boiler.
2. Boiler is in "TANKER SERVICE" mode.
3. Burner is in "MAN" mode.
4. Each station of ACC is in "AUTO" mode.
5. F. D. fan is in "AUTO" mode.
6. F. 0. pump is in "AUTO" mode.
7. Boiler is in normal condition (not in alarm condition).
* If the burner is in "AUTO" mode, tlie boiler is started and stopped
automatically based on the boiler load. Thus, it is unnecessary to
operate "BNR ON" and "BNR OFF" switch. SAM
PAGE 27
1, LAMP INDICATION FOR BURNER IGNITION
(A- 1)
(1) .Boiler stop condition
Fig. (A-l) is the operation panel
for the boiler prior to operation.
If "BNR ON" is pressed here, the
operation panel will be changed
STU'
as follows.
urn
(A-4)
(41 FURNACE PURGE CONDITION . -
"PRE-PURGE START" lamp is on.
fhen F. D. fan vane is opened to the
specified degree and air draft rea-
ches at the purge rate, "PRE-PURGE
START" lamp is switched "ON" (and
') starts to count furnace purge
time. )
60sec. purge will start.
If the purge rate is not establis-
hed, the operation will result
in ( * b )
after 45 sec.
(A-5)
(50 P.O. REC IRC. STOP CONDI DION
"F. 0. REC IRC. V. OPEN" lamp is off
"F. 0. REC IRC. V. SHUT" lamp is on
P.O. REC IRC. PISTON VALVE CLOSE order!
If "F. O.TEMP. INTERLOCK NORMAL"
lamp is not on, P.O. REC IRC VALVE
CLOSE order will be cancelled with
the operation resulting in (* b ).
Confirm that the lamp is on before
starting the boiler,
(refer to * a )
froi(A-4)after 60sec.
(A- 6)
(6') SWITCHING TO IGNITION MODE
Ignition order is sent from the
burner sequencer to ACC.
"PRE-PURGE START" lamp is off
"PRE-PURGE FINISH" lamp is on
"IGNITION P.O. RATE" lamp is flicker
"IGNITION AIR RATE" lamp is flicker
"IGNITION READY" lamp is flicker
If the each rate (P.O. & AIR) is
n not established, the operation wil
result in (* b ).
(A- 7)
(7) ESTABLISED F. 0. RATE. CONDITION
"PRE-PURGE FINISH" lamp is off.
"FINISH" lamp is switched off
when F. 0. or AIR rate is reached.
"IGNITION P.O. RATE" lamp is on.
when F. 0. pressure and F. 0. control
valve reach the specified rates.
If not, the operation will result
in (* b ).
(A- 8)
(8> IGNITION AIR RATE REACHED TOGETHER
IITH F. 0. AND AIR RATES.
"IGNITION AIR RATE" lamp is on
when air draft reaches the speci-
fied rate for ignition.
If not, the operation will result
in (* b ).
"IGNITION READY" lanp is on when
F. 0. and AIR rates are reached.
If either F. 0. or AIR rate is not
reached, lamp starts to flicker and
the operation will result in (* b ).
(A- 9)
OR) PILOT PUMP START CONDITION
"PILOT PUMP START" lamp is on
when ignition rate is reached and
the pilot puip is started.
smi
UK
n
f
LAMP ONN - • • LAMP FLICKED I |- • • LAMP OFF,
SAM
PAGE 30
(FROM A- 9)
(A- 1 0)
(10) IGNITOR SPARK CONDITION
"PILOT BNR,ON" lamp is on
PILOT SOL. V. OPEN order.
The lamp is switched on when
ignitor sparks and pilot flame
is given out.
(A- 1 1)
Cll) F.O. PISTON VALVE OPEN IN IGNITION
MODE.
"BNR. ON" lamp is on.
"BNR. F.O. V. OPEN" lamp is on.
"BNR. BURNING" lamp is on.
ATI.
The F. 0. V. open is made 3 sec.
sru.
Lilt
after check of the pilot burner
ignition.
"IGNITION F.O. RATE" lamp is off
"IGNITION AIR RATE" lamp is off.
(A- 1 2)
(12) COMPLETION OF BNR.IGNITION
SEQUENCE
"IGNITION READY" lamp is off.
"PILOT PUMP START" lamp is off.
PILOT PUMP STOP order.
"PILOT BNR. ON" lamp is off.
PILOT SOL. V. CLOSE order.
(B-5)
\7
(S) FURNACE PURGE CONDITION
"PRE-PURGE START" lamp is on.
Air draft has reached at the purge
rate (Purge time counting starts.)
Purge for 30 seconds.
(B- 6)
(6)-PURGE COMPLETED AND BOILER NOT IN
OPERATION.
"BNR OFF" lamp is on.
Burner is extinguished.
"PRE-PURGE START" lamp is off.
Furnace purge node ended.
"F. D.FAN RUNNING" lamp is off.
F. D. FAN STOP order.
* F. D. fan is automatically stopped
if 15 minutes have passed since
the start of boiler (A-l).
Otherwise, it keeps operating
until after the 15 minutes.
BOILER START-UP (A- 1 )
CAUTION
* a If a feed-back signal contrary to the burner sequence order signal
is returned, the corresponding lamp flickers and an alarm is given.
If something is wrong with "BOILER INTERLOCK", the boiler is stopped
immediately.
* b If the specified rate is not reached and the lamp keeps flickering,
the boiler is tripped by "IGNITION VALIDITY TIME OVER" after 5 minutes.
By-pass operation
(1) "F. 0. T. BY-PASS" SI. ->: "F.O.T. BY-PASS"-- ->" Y L
LAMP FLICKER
(See [ I ] -B>
F. E. BY-PASS MODE
This mode is selected when the boiler can not be stopped though
the cleaning and check of the flame eyes are headed during running of the
boiler, or when it is desired to avoid the boiler trip due to the keen
sensitivity of the flame eyes under sharp changes of the boiler load
In this case, the flame must always be watched at the boiler side.
By-pass operation
(1) One of the flame eyes > FLAME FAIL ALARMCBOILER NOT TRIP)
detectors flame fail
(2) Both of F.L's detect AFLAME FAIL BOILER TRIP
flame fail
CAUTION
During F. E. By-pass Run. watching must always take place at the boiler side.
SAM
PAGE 35
/
3 s EMERGENCY RUN MODE
This mode is selected when the Burner Sequencer cannot be used.
The burner start in this lode follows the operating procedure below.
SAM
PAGE 36 r\
(/
CAUTION
1, Tine to try ignition of the pilot burner is to be 15 sec. at
maximum.
If the pilot burner fails to be ignited within 15 sec.
the pilot BNR IGN. Sf is to be turned
Check of Ignition Fail.
2, If the ignition fails, ignition is to be re-attempted from (4)
Furnace Purge.
Burner ignition
(Ignition of the pilot BNR is checked. F. 0.Piston Valve is opened,
and ignition is tried. )
CAUTION
1, Time to try ignition of the main burner is to be 10 sec.
at maximum.
Pilot Burner Ign. Sw and P.O. Valve Open Sf are to be set to
"Intermediate Position" (spring-return with hand off) within
10 sec.
CAUTION
1, During the emergency running, the machine-side manual operation and
watching at the machine side must always take place. The boiler trip
interlock conditions are to be checked and confirmed by direct
watching.
SAM
PAGE 37
2, Interlock nor. condition of eiergency run lode
(1) F.D. FAN RUNNING
(2) NOT DRUM IATER LEVEL LOf-LOf
(3) FLAME ON (F.O. VALVE OPEN CONDITION)
(4) EMERG. STOP (MAN.TRIP)
PAGE 38
CAUTION
1, Time to try ignition of the pilot burner is to be 15 sec. at
maximum.
If the pilot burner fails to be ignited within 15 sec.
the pilot BNR IGN. SI is to be turned
Check of Ignition Fail.
2, If the ignition fails, ignition is to be re-atteipted from (4)
Furnace Purge.
CAUTION
1, Time to try ignition of the main burner is to be 10 sec.
at maximum.
Pilot Burner Ign. Sw and F. 0. Valve Open Sf are to be set to
"Intermediate Position" (spring-return with hand off) within
10 sec.
CAUTION
1, During the emergency running, the machine-side manual operation and
watching at the machine side must always take place. The boiler trip
interlock conditions are to be checked and confirmed by direct
watching.
SAM
PAGE 37
2, Interlock nor. condition of emergency run lode
(1) F.D. FAN RUNNING
(2) NOT DRUM IATER LEVEL LOf-LOf
(3) FLAME ON (F.O. VALVE OPEN CONDITION)
(4) EMERG. STOP (MAN.TRIP)
SAM
PAGE 38
c-v
[ffl ] A U T O M A T I C R U N N I N G OF F. D. F A N , F . 0 . P U M P
1. F. D. FAN
(2) F. 0. pump with its mode switch in "AUTO", automatically starts and stops
running with burner start/stop commands.
F.0. RECIC is carried out by automatically starting F. 0.pump so that
F.0.temperature of burner header does not fall too much while the burner
i-s in operation.
SAM
PAGE 39
[IV] SOOT BLOWER O P E R A T I O N
v
(1) DRAIN VALV FULL OPEN
V
(5) No. 1 SOOT BLOfER START/STOP
v
(8)
CAUTION
1, RELATION SOOT BLOEING AND BOILER LOAD
The soot blower shall be operated, as a rule, during a boiler load
exceeding 50X
2, INTERLOCK BETfEEN SOOT BLOfER AND IGS
The soot blower and the IGS are interlocked each other.
During running of any soot blower, IGS can not be operated.
And during the IGS is operated, any soot blower can not be run.
SAM
PAGE 40
[V] ALARMS
A, PATTERNS OF ALARM
AM \f * 1
ALARM LAMP Refer to bottom of
OFF 1\ / this page
^
"BZ. STOP" ON -i
BUTTON
OFF
"LAMP RESET" ON
BUTTON npp
NOTE
The alarm lamp does not disilluminate, even after normal state has been
restored, unless "LAMP RESET" Button is turned on after the turn-on of
"BZ STOP" Button. Also, the alarm lamp can not be turned off before
noioal state has been restored.
SAM
PAGE 41
B. BOILER SET POINT LIST
SAM
PAGE 42
•re
BOILEB SET POINT LIST ECC.; ENGINE CONT.CONSOL
MS. ; MONITOR SW.
PS. ; PRESS. SW.
TS. ; TEMP. SENSOR
F.E.; FLAME EYE
PT. ; PRESS. TRANS.
LS. ; LIMIT SW.
SEQ.; SEQUENCER
TAG. No. DESCRIPTION DETECTING SET___
POINT | _ TIMER
UNIT ALARM ""
LM-1 DRUM LEVEL HIGH MS +200 no 10 sec
(157B)
1
LM-- DRUM LEVEL LOW MS -200 no 10 sec
157B — —
2
LM- DRUM LEVEL LOW-LOW . MS. -240 «n — 0 sec
(156B.159B) —
PT
(123B)
LOW-LOW
*
TAG. No. DESCRIPTION DETECTING SET POINT TIMER
UNIT ALARM TRIP NOR.
,.
C, INSTRUCTION MANUAL OF AUTOMATIC BOILER CONTROL SYSTEM
SAM
ACC 1 f
I
[ I] GENERAL DESCRIPTION OF AUTOMATIC BOILER CONTROL SYSTEM
r
This system (A. B. C. ) is coiposed of the. automatic coibustion control
system (A. C. C. ) and the automatic feed water control systei (F. I. R. ).
I—F. W. C. F. I. CONTROL
SAM
ACC
(e) STEAM DUMP CONTROL SUB-LOOP
The signal during activation of I.G. S. adds a limiter to the fuel oil
flow rate (Master Cont. Signal).
SAM
ACC 4
n] OPERATINGJNSTRUCTIONS OF AUTOMATIC BOILER CONTROL SYSTEM
FEED CONT.V
OUTPUT i 0.
SAM
ACC
1. -MASTER STATION'
CAUTION
In EMERGENCY MODE or F. 0. TEMP. BY-PASS MODE, the Man Mode is
forced to be selected.
SAM
ACC 6
2. "AIR FLO!" STATION"
The change-over and display of Auto/Han, of
the F.D.FAN INLET VANE CONTROL DRIVE OPEN
ORDER, as well as the manual operation and
output display, are perfomed.
The manual set and indication of the Fuel/Air
RATIO AIRSP AIRPV
r K5Q «= r 400.D r 400.0 Ratio (Excess Air Ratio) are perfomed.
CD FUEL/AIR
8SI1 (1) FUEL/AIR RATIO RAISE & LOWER Sf.
CD This switch is used for the manual set of
RATIO RAISE
BS22
& LOIER SI.
CD the Fuel/Air Ratio.
The initial set at power-on is made to 0.
- 1.00 - 200.0 • IM.O
CAUTION
DSK3
CAUTION
In EMERGENCY MODE or F. O.TEMP. BY-PASS MODE, the Man. Mode is forced
to be selected.
© F.f.CONTROL
(4) BAR .GRAPH OF STEAM FLOf
VALVE
AUTO/MAN. INDICATE The right-hand bar graph shows
Steam Flow.
SAM
ACC
[ffl] CONFIGURATION OF AUTOMATIC BOILER CONTROL SYSTEM
o
AMCO •0) PAC ID
O ROTATIONAL
SIITCH
Q a (D LED LAMP
TO GP
COMMUNICATION
r-RS-485-A-,
CONNECTOR ca
as
o o O
CQ ea as
TO ACS10 O o O
•«c
eu Cu a.
COMMUNICATION
CONNECTOR
o o
O
NO NAME FUNCTION
SAM
ACC 9
• _ _ „,... !
NO NAME
SAM
ACC 10
NO NAME
SAM
ACC 11
2, FUNCTION OF KEYS (Fig 1)
(Fig 2)
t
CLR
END
Cursor Up
Cursor Down
Cursor Left
Cursor Right
To next page
[CLR] Data Cancellation
The set data can be cheanged by using the above keys(fig 2)and
ten keys(fig 1 -©).
The set data can only be changed for "PID", "% P", "T P", and "TBL",
(If a manu is selected for those other that stated above, cursor key
and data cancellation key will not work. )
SAM
ACC 13
(Fig 3-1) (Fig 3-2)
PID mm n X P am D
PID Parameter % Parameter
When pressed, then pressed^
PID 1 No No
PC % ) 999.9 1 + 999. 9 11 +999. 9
I (min) 99.99 2 + 999. 9 12 +999. 9
D(oin) 99. 99 3 + 999. 9 13 +999. 9
IloC X ) +999. 9 4 + 999. 9 14 +999. 9
IhiC % ) +999. 9 5 + 999. 9 15 +999. 9
6 + 999. 9 16 +999. 9
7 + 999. 9 17 +999. 9
8 + 999. 9 18 +999. 9
9 + 999. 9 19 +999. 9
10 + 999. 9 20 +999. 9
^ -<• *
71 * *
^ ->•
|END|
CLR
a ^
END
CL8
^ I •<• * TI #
^ I •> CLR
END
a ^
END
^
CLR
SAM
ACC 14
(Fig 3-5) (Fig 3-6)
[y jj| 1 1 D
AID
Analog In/Out Digital In/Out
then pressed^ When pressed.
; All +999. 9 A01 +999. 9 -DI1 0 D01 0
AI2 +999. 9 A02 +999. 9 DI2 0 D02 0
AI3 +999. 9 A03 +999. 9 DI3 0 D03 0
AI4 +999. 9 A04 +999. 9 DI4 0 D04 0
AI5 +999. 9 A05 +999. 9 DJ5 0 DOS 0
AI6 +999. 9 A06 +999.9 DI6 0 D06 0
AIT +999. 9 A07 +999. 9 DI7 0 DOT 0
AI8 +999. 9 A08 +999. 9 DI8 0 DOS 0
1 <• *
t -^
END 1
CLR
±j CLR
CLR
SAM
ACC 15
(Fig 4) 3, CHANGE METHOD OF DATA
X P mm n
X Parameter This explains how to change % parameter
Press Key No Nn set point.
1 + 000. 0 11 +050. 0 (Example) to change No.3 parameter from
2 + 005. 0 12 + 001.0
3 + 010. 0 13 +030. 0 10* to 25X
4 + 003. 0 14 -010. 0 (1) Press key on the station screen
5 -020. 0 15 + 100. 0 of the controller you wish to change,
6 +000. 0 16 +500. 0
and the menu screen [2-(Fig-l)]
7 + 010.0 17 -500. 0
8 +075. 0 18 +000. 0 will be displayed..
9 + 100. 0 19 +000. 0 (2) Press the %P key,
10 -050. 0 20 + 100.0 and (Fig 4) will be displayed.
(3) Press the IT] key of (Fig 4)
a <**
END
CLRI
CAUTION
Please contact the boiler maker(Mitsubishi Heavy Ind.)
before changing invariable numbers such as parameters.
SAM
ACC 16
[IV] ALARM DISPLAY
GP displays reversible and communication errors.
The abnormality are displayed with GP. as follows.
(Fig 6)
F1 F2 F3 F 4 F5 F6 F7 F8
mm D mm D mm D
i
• 11!
•»
091 mi
ISK KB mi
D p D
. 5g9 . COM i
0. Q - S5.8 • 50.0 - 5$ - 56 0 -50.11
V D
V a
V D
•' cLJL
L-7SI
cz '' CZ— i 9 « '
CZ ••Aq c JJ
? =? loAq * ~T3° C
| RUN | | RUN | RUN
1 1
OUTPUT zm % | MANU | OUTPUT |_ ZJ« | MANU | OUTPUT : • N | MANU |
3 AUTO MANU
3 AUTO MANU T|
D]
AUTO MANU
D V A D V A V A
Warn DDDDDDDD IBOST!
1 2 3 4 5 6 7 5 9 0 4- BS ENTR
There are 8 LEDs after "farm", and the location of lighted LEDs
indicates the kind of error.
SAM
ACC 18
D. BMS CONTROLLER
TABLE OF CONTENTS
SECTION
D-[l] SYSTEM C O N F I G U R A T I O N
[ 3] I/O RACK
[ 4] P OWE R SUPPLY
[5] SPECIFICATIONS
/77
SECTION 2
System Configuration and Unit Description
This section provides information about the Racks and individual Units that make up a C200HS PC S ystem. The names of all
the parts of a Unit are given, followed by any details thai apply 10 that Unit alone. For a description of how the Units fit together
to become a PC, refer to Section 3 Assembly Instructions. For information about the model numbers of any of the parts de-
scribed in this section, refer to Appendix A Standard Models. For specifications, refer to Appendix B Specifications.
1. Backplane
There are backplanes available with 3, 5, 8, or 10 slots. The same back-
planes can be used for CPU Racks, Expansion I/O Racks, or Slave Racks.
2. CPU
There are six CPU models available: CPU01-E, CPU03-E, CPU21-E,
CPU23-E, CPU31-E, and CPU33-E.
3. Memory Cassette
EPROM and EEPROM are both available.
4. Standard I/O Unit
The Units can have 5,8,12, or 16 points. In this illustration the I/O Un'rt cover
is mounted. This is the terminal block cover for Units with 10P terminal
blocks.
5. Interrupt Input Unit
One Interrupt Input Unit can be used at the CPU Rack.
6. SYSMAC NET Llnk/SYSMAC LINK Unit, Host Link Unit, or PC Link Unit
7. Remote I/O Master Unit
A maximum of two Units can be used, either on the CPU Rack or on an Ex-
pansion I/O Rack.
8. Terminal Block
Terminal blocks have either 10 or 19 terminals. This is a 19P Terminal Block.
9. High-density I/O Unit (Group 2)
A maximum of ten Units can be used if they are all 32-point Units, and five if
they are all 64-point Units. They cannot be used on Slave Racks.
10. Special I/O Unit
Up to ten Special I/O Units can be used (including PC Link), They can be
used on any Rack.
11. I/O Connection Cable
There are five types of cable, from 30 cm to 10 m. A maximum total of 12 m
can be used.
16
System Configuration Section 2-1
(2)
1. Slave Unit
Either Optical or Wired Slaves can be used.
2. Fiber-optic Cable
2/?-\ IL
^
/&>
CPUs Section 2-2
2-2 CPUs
There are two groups of CPUs available, one that uses an AC power supply, and
one that uses a DC power supply. Select one of the models shown betow accord-
ing to requirements of your control system.
CPU model Power supply voltage
C200HS-CPU01-E/CPU21-E/CPU31-E 100 to 1 20 VAC or 200 to 240 VAC
(voltage selector)
C200HS-CPU03-E/CPU23-E/CPU33-E 24 VDC
Caution Be sure to check the power supply used by the CPU. Absolutely do not apply an
AC power supply to a DC-type CPU.
Battery/Switch compartment:
The backup lithium battery (C200H-BAT09) L
and the DIP switch for setting C200HS opera- - Cable connector for peripheral devices
tions are contained. An optional Memory Cas- (Peripheral device connector)
sette can also be mounted.
18
CPUs Section 2-2
C200HS-CPU21-E/CPU23-E/CPU31-E/CPU33-E
Bus connector:
Available only with the CPU31-E Removable terminal block
and CPU33-E. Use this connector
when SYSMAC NET Link Unit or
SYSMAC LINK Unit is used.
I— COMM1 (orange):
Lights when a peripheral device is in operatbn.
COMM2 (orange):
Available only with the CPU21-E. CPU23-E. CPU31-E,
•RUN (green): and CPU33-E. Lights whe.n the CPU is communicating
Lights when the PC is via the RS-232C connector. POWER (green):
operating normally.
Lights when power is
supplied to the CPU.
19
CPUs Section 2-2
20
Expansion I/O Racks Section 2-3
Note Memory Cassettes for the C200HS cannot be used with the C200H, and
Memory Units for the C200H cannot be used with the C200HS.
C200HS-ME16K (EEPROM) When a Memory Cassette is installed in the CPU. reading and writing of the
user memory (UM) and I/O data is made possible. There is.no need for a
backup power supply. The Memory Cassette can be removed from the CPU
and used for storing data.
C200HS-MP16K (EPROM) The program is written using a PROM Writer. The ROM is mounted to the
Memory Casette and then installed in the CPU. I/O data cannot be stored.
21
Power Supply Section 2-4
The parts of an Expansion I/O Rack are shown in the following diagram.
AC Power Supply
(x)
M^MMM
^© AC Input
(x)
(x) NC
(x) NC
22
IIO Units Section 2-5
DC Power Supply
DWER indicator (green): — Power fuse:
ghts when power is 5 A, 125V
applied to Power Supply (5.2-dia.x20)MF51NR
PS211
POWER jf
—i
fe 2r* - ,»
"*Tr 24 VDC
5d£ (x)
^
""L a
(x) NC
Terminals
C2QOH oowon
* for exter-
PROGRAMMABLE CONTROLLER
© NC
nal con-
nections ©
m LG
Si ©
sSB © NC
© NC
•*. © NC
•
© NC
ill
—i— i—
23
HO Units Section 2-5
Nameplate
I/O indicators:
Indicate ON/OFF sta-
tus of points
Nameplate
24
HO Units Section 2-5
Nameplate
~ I/O indicators:
Indicate ON/OFF status of points
I/O number setting switch
40-pin connector
25
IIO Units Section 2-5
D-shape Units (64-point Units)
Nameplate
I/O indicators:
Indicate ON/OFF status of I/O points
I/O number setting switch
Indicator switch:
Determines whether the status of
connector 1 or connector 2 I/O points
are indicated by the I/O indicators.
40-pin connectors
Note Refer to Optional Products, Appendix A Standard Models for a list of external
connectors.
Setting the Unit Number High-density I/O Units are each allocated 10 I/O words in the IR Area (IR 100 to
IR 199) by setting the unit number switch on the front of each Unit. The 10 words
begin with n, where n = IRlOO + 10x unit number. For example, a Special I/O
Unit with a unit number of 3 would be allocated IR 130 to IR 139.
Always turn the PC power off before changing a Unit's unit number. The new unit
number (0 to 9) will not be recognized unless the PC has been turned off.
26
HO Units Section 2-5
Setting the DIP Switch The operation of High-density I/O Units is controlled by setting the pins of the
DIP switch on the back panel. The following table shows the function of each pin
and applicable Units.
Pin Function Applicable Units Setting
ON OFF
1 Operating mode C200H-OD501/OD215 128 dynamic outputs 32 outputs
C200H-M0501/MD1 1 5/MD21 S 1 28 dynamic inputs 16 inputs, 16 outputs
2 High-speed input1 C200H-I0501/ID215 Inputs 08 to 15 of CN2 Normal inputs
are high-speed inputs.
C200H-MD501/MD115/MD215 Inputs 08 to 15 of CN2 Normal inputs
are high-speed inputs.
3 High-speed input C200H-1D501/ID215 4ms 1 ms
minimum pulse width2 C200H-MD501/MD1 1 S/MD215
4 Input response time3 C200H-ID501/ID215 15ms max. 2.5 ms max.
C200H-M0501/MD1 1 5/MD21 5
5 Data output mode4 C200H-OD501/OD215 Positive logic Negative logic
6 Not used. ._ ... ...
Nameplate
I/O indicators:
Indicate ON/OFF status of points
24-pin connectors
Appendix B
Specifications
The following figures and tables provide specifications for each Unit of the C200HS. I/O Units may take on one of
two different shapes and are sometimes referred to as A-shape Units or B-shape Units. Group-2 High-density I/O
Units take on one of two different shapes and are sometimes referred to as C-shape Units or D-shape Units. Refer
to the figures at the end of the I/O Unit specifications for the exact dimensions of these two shapes of I/O Unit.
93
Specifications Appendix B
3.
Acceleration (G)
Amplitude
0.075 mm
10 57 150
Frequency (Hz)
C200HS Dimensions
M4
Q 2
a a a a a a a
30 1
0a
I *
nu
I fc — >
~~ '
B*
6.5 — A "_ ... J, 7.5
Backplane A W D
CPU01-E/CPU03-E CPU21-E/CPU23-E/
CPU31-E/CPU33-E
C200H-BC031-V2 246 260 118 143
C200H-BC051-V2 316 330
C200H-BC081-V2 421 435
C200H-BC101-V2 491 505
94
Specifications Appendix B
CPU Specifications
Control Method Stored program
I/O Control Cyclic scan and immediate processing are both possible.
Method
Programming Ladder diagram
Method
Instruction Length 1 address/instruction, 1 to 4 words/instruction
Number of 239 (14 basic instructions + 225 special instructions)
Instructions
Execution Time Basic instructions: 0.375 to 1 .313 u,s Special instructions: Approx. 10 us
Program Capacity 1 5.2K words max.
IX) bits 480 IX) relay of I/O Units mounted to Special I/O Optical I/O
(00000 through 02915) High-density Remote IX) Slave Units 1,500 Units 512
I/O Unit 320 Racks 800 (05000 (1 0000 through (20000 through
IRbits 6i688 (group 2) through 09915) 19915) 23115)
(03000 through 2351 5, C03000
30000 through 51115) through
95
Specifications Appendix B
20"
,
15"
10-
5"
0
10 20 30 40 505560
Ambient Temperature (°C)
124
Specifications Appendix B
Terminal Connections
I/O word *m* I/O word *m+r
24 VDC 24 VDC
24 VDC 24 VDC
Note 1. I/O word *m" is determined by the I/O number setting {m = IR 030 + 2 x I/O number).
2. The power can be supplied in either polarity, but the same polarity must be used for all COM terminals.
Connect power supply wiring to every COM terminal, even though the COM terminals are connected
internally.
125
Specifications Appendix B
<5^
fNOO
Input Voftapt:
IN07 6
COMO-o 54 - /
IN08 O K input^
I 60
\ 26.4 V
CN1 IN15O
tn 50~
\ \/
//
c
'0
Q.
^40-
\
1
«30-
|
~ 20
3
A -
E
CO
10~
0
10 20 30 40 50 55 60
B < Ambient Temperature (°C)
N15
<L_. ..J
Terminal Connections
CN1 CN2
I/O word *m+r I/O word *m" I/O word "m+2" IAD word *m*3"
24 V6C , >-K~B
24 VDC
24 V6C
24 VDC
Note 1. I/O word "m" is determined by the I/O number setting (m = IR 030 4-2x1/0 number).
126
Specifications Appendix B
2. The power can be supplied in either polarity, but the same polarity must be used for all COM terminals in
each connector. Connect power supply wiring to every COM terminal, even though the COM terminals in
each connector are connected internally.
100-
M-u
"50 H
CO
COM
4.5 to xfa 16
26.4 VDC
OUTGO
I I
O OUT07 4.5 10 20.4 26.4
COM Power Supply Voltage (V)
4,5 to
26.4 VDC
OUT08
I
OUT 15
COM
127
Specifications Appendix B
Terminal Connections
4,5 to
26.4 VDC
Note 1. I/O word "m" is determined by the I/O number setting (m = IR 030 + 2 x I/O number).
2. When the fuse blows, the F indicator lights and the error flag in AR 02 corresponding to the I/O number is
turned ON. I/O numbers 0 to 9 correspond to AR 0205 to AR 0214.
3. The interruption of power from the external power supply is treated the same as a fuse blowout.
4. Connect power supply wiring to every COM terminal, even though the COM terminals are connected
internally.
128
Specifications Appendix B
Circuit Configuration
rr-~
Internal
Circuit
Indicator
switch/ y *f Output indicator
o
fuse CN2
blowout F indicator
I
O 4.5 to
26.4 VDC
OUTOO
I
OUT07
CN2
L-.
Maximum Switching Capacity
--- 6.0- V.
"2 ^""
I 5.0-
4.0-
CO
O 3.0-
OJ
c 2.0-
£
a
W 1.0-
3 0
4.5 10 20.4 26.4 0 10 20 30 40 505560
Power Supply Voltage (V) Ambient Temperature (°C)
129
,99
Specifications Appendix B
Terminal Connections
CN1 CN2
I/O word *m+1" I/O word •m" I/O word "m+2" I/O word "m+3"
4.5to
26.4 VDC
Note 1. I/O word "m" is determined by the I/O number setting (m = IR 030 + 2 x I/O number).
2. When either fuse blows, the F indicator lights and the error flag in AR 02 corresponding to the I/O number
is turned ON. I/O numbers 0 to 9 correspond to AR 0205 to AR 0214.
3. The interruption of power from the external power supply is treated the same as a fuse blowout.
4. Connect power supply wiring to every COM terminal, even though the COM terminals in each connector
are connected internally.
130
Specifications Appendix B
132 A/
Specifications Appendix B
Circuit Configuration
CN1
CN2
Terminal Connections
CN2
UQ word *n
A B
1
24 24 VDC
+•
COW2 COM3
NC 10 10 NC
NC 11 11 NC
NC 12 12 NC
Note 1. I/O word "n" is determined by the unit number setting (n » IR 100 -t-10 x unit number).
2. When pin 2 of the Unit's DIP switch is ON, input points 08 to 15 in connector 2 are high-speed inputs.
3. At high temperatures, the number of inputs that can be turned ON simultaneously is limited. Refer to the
graphs on page 149 for details.
133
Specifications Appendix B
Circuit Configuration
r 4 5
- *°
I 26.4 VDC
1 — vw—
/~I OUTGO
vj
OUT07
1 CN1
COMO
4.5 to
26.4 VDC
1 OUT08
I
OUT15
Internal COM1
Circuit 4.5 to
26.4 VDC
1 — vw—
1
1 / ,
1
1
vj OUTGO
OUT07
CN2
I COM2
4.5 to
26.4 VDC
OUT08
1
OUT15
COM3
!___
137
Specifications Appendix B
Terminal Connections
CN2
I/O word "n+1"
A B
5 to 24
5 to 24
5 to 24 VDC
VDC
Note 1. I/O word "n" is determined by the unit number setting (n = IR 100 + 10 x unit number).
2. The Unit will have 32 static output points when pin 1 of it's DIP switch is OFF.
69
Reading and Clearing Errors and Messages Section 6-3
Caution The PC will turn ON the ALM/ERR indicator, stop program execution, and turn
OFF all outputs from the PC for most hardware errors, for certain fata! software
errors, or when FALS(07) is executed in the program (see tables on following
pages). PC operation will continue for all other errors. It is the user's responsibil-
ity to take adequate measures to ensure that a hazardous situation will not result
from automatic system shutdown for fatal errors and to ensure that proper ac-
tions are taken for errors for which the system is not automatically shut down.
System flags and other system and/or user-programmed error indications can
be used to program proper actions.
70
Error Messages Section 6-4
initialization Errors The following error messages appear before program execution has been
started. The POWER indicator will be lit and the RUN indicator will not be lit for
either of these. The RUN output will be OFF for each of these errors.
Non-fatal Operating Errors The following error messages appear for errors that occur after program execu-
tion has been started. PC operation and program execution will continue after
one or more of these errors have occurred. For each of these errors, the
POWER and RUN indicators will be lit and the ALM/ERR indicator will be flash-
ing. The RUN output will be ON.
Error and message FAL no. Probable cause Possible correction
01 to 99 FAL(06) has been executed Correct according to cause
FAL error in program. Check the FAL indicated by FAL number
SVS FRIL FfiL** number to determine (set by user).
conditions that would cause
execution (set by user).
71
Error Messages Section 6-4
I/O table verification error E7 Unit has been removed or Use I/O Table Verify
replaced by a different kind Operation to check I/O table
I/O UER ERR of Unit, making I/O table and either connect dummy
incorrect. Units or register the I/O
table again.
Remote I/O error BO or B1 Error occurred in Check transmission line
transmissions between between PC and Master
REMOTE ERR Remote IAD Units. and between Remote I/O
>I/O >
Master Un* nurrtoer Units.
72
Error Messages Section 6-4
Fatal Operating Errors The following error messages appear for errors that occur after program execu-
tion has been started. PC operation and program execution will stop and all out-
puts from the PC will be turned OFF when any of the following errors occur. No
CPU indicators wrH be lit for the power interruption error. For all other fatal oper-
ating errors, the POWER and ALM/ERR indicators will be lit. The RUN output will
be OFF.
Error and message FAL no. Probable cause Possible correction
Power interruption None Power has been Check power supply voltage
No message. interrupted for at least and power lines. Try to
10ms. power-up again.
I/O bus error CO to C2 Error has occurred in The rightmost digit of the FAL
I/O BUS ERR the bus line between the number will indicate the number
Rack no. CPU and I/O Units. of the Rack where the error was
detected. Check cable
connections between the I/O
Units and Racks.
73
CPU Racks and Expansion I/O Racks Section 6-5
Other Error Messages A number of other error messages are detailed within this manual. Errors in pro-
gram input and debugging and errors in cassette tape operation are detailed in
the C200HS Operation Manual (W235). Information on error flags is also con-
tained in the C200HS Operation Manual (W235).
74
Input Units Section 6-6
75
Output Units Section 6-7
76
SECTION 7
Inspection and Maintenance
Certain consumable items in a PC (such as fuses, relays, and batteries) need occasional replacement. This section explains
how to replace these items. Always keep spare items on hand so that they can be used as immediate replacements when heed-
ed
77
Output Unit Fuses Section 7-2
Turn counterclockwise
to remove, clockwise to
attach
Standard _
screwdriver
To replace a fuse, follow the steps below. Use only UUCSA certified replace-
ment fuses.
1, 2, 3... 1. Turn OFF the power to the PC.
2. Remove the fuse holder by turning it approximately 50°counterclockwise
with a standard screwdriver.
3. Remove the fuse from the holder.
4. Insert a new fuse.
5. Reattach the fuse holder by turning H approximately 50°clockwise with a
standard screwdriver.
78
Output Unit Relays Section 7-3
79
Output Unit Relays Section 7-3
5. Pull out the printed circuit board. The Relays are placed on the PC boards of
individual Units as shown in the figures below.
OC221/OC224
OC222
2
LLffl
I
OC223
^
I
i
CEI p
Si
ra
.-C rn
m
T X>
OC225
.15 14
Batteries Section 7-4
6. A Relay puller is provided inside the rear of the case when the Unit is deliv-
ered. Use the Relay puller to pull out the Relay as shown below. Insert a new
Relay.
Relay puller
Using the Relay puller,
pull the relay up and out
of the socket.
7-4 Batteries
When the battery is nearly discharged, the ALARM indicator blinks and the mes-
sage "BATT FAIL" appears on the Programming Console. When this occurs, re-
place the battery within one week to avoid loss of data.
The normal battery service life is five years at 25°C. The service life will be short-
en if used at temperatures higher than that.
The Battery Fail Flag is allocated to 25308 for the C200HS.
The battery comes together with its connector as a set. To replace the Battery
Set (C200H-BATQ9), follow the steps below. The entire replacement must be
completed within five minutes to ensure that the data will not be tost.
%
1, 2, 3... 1. Turn OFF the power to the PC. (If the power was not already ON, turn the
power ON for at least one minute before turning the power OFF.)
2. Remove the cover from the battery compartment of the CPU Unit.
3. Remove the old Battery Set.
4. Install the new Batter/ Set as shown in the following diagram.
Connector
DANGER! Batteries can bum, exptode, or leak. Absolutely do not short-circuit across the
terminals, attempt to recharge batteries, or take them apart, heat them, or ex-
pose them to fire.
82
4-5 The Programming Console
This and the next section describe the Programming Console and the opera-
tions necessary to prepare for program input. 4-7 Inputting, Modifying, and
Checking the Program describes actual procedures for inputting the program
into memory.
Although the Programming Console can be used to write ladder programs, it is
primarily used to support LSS operations and is very useful for on-site editing
and maintenance. The main Programming Console functions are listed below.
1, 2, 3... 1. Displaying operating messages and the results of diagnostic checks.
2. Writing and reading ladder programs, inserting and deleting instructions,
searching for data or instructions, and monitoring I/O bit status.
3. Monitoring I/O status, force-setting/resetting bits.
4. The Programming Console can be connected to or disconnected from the
PC with the power on.
5. The Programming Console can be used with C-series PCs.
6. Supports TERMINAL mode, which allows the display of a 32-character
message, as well as operation of the keyboard mapping function. Refer to
5-25-5 TERMINAL MODE- TERM(-) for details.
Note The Programming Console does not support all of the LSS operations, only
those required for on-srte edHing and maintenance.
74
The Programming Console Section 4-5
gram. The SHIFT key is similar to the shift key of a typewriter, and is used to alter
the function of the next key pressed. (It is not necessary to hold the SHIFT key
down; just press it once and then press the key to be used with it.)
The gray keys other than the SHIFT key have either the mnemonic name of the
instruction or the abbreviatkDn of the data area written on them. The functions of
these keys are described below.
TH
Pressed before designating an address in the TR area.
75
Preparation for Operation Section 4-6
4-5-2 PC Modes
The Programming Console is equipped with a switch to control the PC mode. To
select one of the three operating modes—RUN, MONITOR, or PROGRAM—
use the mode switch. The mode that you select will determine PC operation as
well as the procedures that are possible from the Programming Console.
RUN mode is the mode used for normal program execution. When the switch is
set to RUN and the START input on the CPU Power Supply Unit is ON, the CPU
will begin executing the program according to the program written in its Program
Memory. Although monitoring PC operation from the Programming Console is
possible in RUN mode, no data in any of the memory areas can be input or
changed.
MONITOR mode allows you to visually monitor in-progress program execution
while controlling I/O status, changing PV (present values) or SV (set values),
etc. In MONITOR mode, I/O processing is handled in the same way as in RUN
mode. MONITOR mode is generally used for trial system operation and final pro-
gram adjustments.
In PROGRAM mode, the PC does not execute the program. PROGRAM mode
is for creating and changing programs, clearing memory areas, and registering
and changing the I/O table. A special Debug operation is also available within
PROGRAM mode that enables checking a program for correct execution before
trial operation of the system.
DANGER! Always confirm that the Programming Console is in PROGRAM mode when
turning on the PC with a Programming Console connected unless another mode
is desired for a specific purpose, if the Programming Console is in RUN mode
when PC power is turned on, any program in Program Memory will be executed,
possibly causing a PC-controlled system to begin operation.
76
/
~>2-f
Preparation for Operation Section 4-6
4. Confirm that the CPU's POWER LED is lit and the following display appears
on the Programming Console screen. (If the ALM/ERR LED is lit or flashing
or an error message is displayed, clear the error that has occurred.)
<PROGRflM>
PflSSUORD!
5. Enter the password. See 4-6-1 Entering the Password tor details.
6. Clear memory. Skip this step if the program does not need to be cleared.
See 4-6-3 Clearing Memory for details.
<PROGRfiM>
PflSSUORD!
< P R O <3 R R M > BZ
4-6-2 Buzzer
Immediately after the password is input or anytime immediately after the mode
has been changed, SHIFT and then the 1 key can be pressed to turn on and off
the buzzer that sounds when Programming Console keys are pressed. If BZ is
displayed in the upper right corner, the buzzer is operative. If BZ is not displayed,
the buzzer is not operative.
This buzzer also will also sound whenever an error occurs during PC operation.
Buzzer operation for errors is not affected by the above setting.
4-6-4 Registering the I/O Table
The I/O Table Registration operation records the types of I/O Units controlled by
the PC and the Rack locations of the I/O Units. It also clears all I/O bits.
l!o r°K»abKSOlUtely neoessary to register the I/O table with the C200HS When the
^O table has not been registered, the PC will operate according to the I/O Units
mounted when power is applied. The I/O verification/setting error will not occur.
80
Preparation for Operation Section 4-6
It is necessary to register the I/O table if I/O Units are changed, otherwise an I/O
verification error message, "I/O VER ERR" or -I/O SET ERROR", will appear
when starting programming operations.
I/O Table Registration can be performed only in PROGRAM mode with the write-
protection switch (pin 1 of the CPU's DIP switch) set to OFF (OFF="WRlTE").
Group-2 High-density I/O Units will not be displayed in the I/O table when it is
displayed using a host computer. Four asterisks (****}, indicating no Unit, will be
displayed instead.
Key Sequence
CH '!
•MFT CHQ 7 °3 WMJTX
*
00000
FUN <??)
00000IOTBL
?-?u=
- Register I/O table
00000IOTBL URIT
9 7 *1 °3
00000IOTBL URIT
9713
00000IOTBL URIT
OK
Note This operation can be executed only when the I/O table has been registered.
Key Sequence
CM
cm f\jn SMVT VBK
*
Example
cm
00000
00000
PUN
FUN <??)
00000IOTBL ?
•MtTT f **
(No errors)
MM
00000IOTBL CHK
OK
vex
00000IOTBL CHK (An error occurred)
0- 1 U=Q*#*
Meaning of Displays The following display indicates a G500, C1000H, or C2000H and C200H or
C200HS have the same unrt number on a Remote I/O Slave Rack.
00000I/OTBL CHK
The following display indicates a duplication in Optical I/O Unit unit numbers.
09000I/OTBL CHK
2**HU=R*-I
Indicates duplication
82
Preparation for Operation Section 4-6
Key Sequence
cm PUM •MPT
CM 1 JL
*
T
Rack Unit
EXT number number
.
Example 00000
00000
FUN < ??)
00000 IOTBL ?
= (PC Unit)
?-? U
(Slave Rack Units)
00000IOTBL
R??-?U=
(Optical I/O Unit)
00000IOTBL ?
2??LU=
00000 IOTBL
(PC Unit)
00000!OTBL ?
0-?U =
00000IOTBL 7
0-5U =
00000IOTBL READ
0~5U=i*** 005
00000IOTBL REftD
@ - 4 |J = Q -4: +• * 004
•
00000 I OTBL REflD
8-51j=i*** 005
83
Preparation for Operation Section 4-6
Meaning of Displays
I/O UnK Designations for Displays
(see I/O Units Mounted in Remote Slave Racks, page 85)
n=
T — WD word number
I/O type: i: (input), o: (output)
Unit number (0 to 9}
Rack number (0 to 2)
Remote I/O
Master no. (0 or
84
Preparation for Operation Section 4-6
I: Input Unit
O: Output Unit
Unit number {0 to 9}
Indicates Group-2 High-density I/O Unit
Note Group-2 High-density I/O Units will not be displayed in the I/O table when it is
displayed using LSS (host computer). Four asterisks (****). indicating no Unit,
will be displayed instead.
336
Monitoring Operation and Modifying Data Section 7-1
Example The following example shows the effects of changing the PV of a timer.
Thit example * h MONITOR mode
80800
T000
0122
Timing
PRES URL?
T000 0100 0200
Timing
Timing
337
7-1-13 Changing Timer/Counter SV
There are two ways to change the SV of a timer or counter. It can be done either
by inputting a new value; or by incrementing or decrementing the current SV.
Either method can be used only in MONITOR or PROGRAM mode. In MONI-
TOR mode, the SV can be changed while the program is being executed. Incre-
menting and decrementing the SV is possible only when the SV has been en-
tered as a constant.
To use either method, first display the address of the timer or counter whose SV
is to be changed, presses the down key, and then press CHG. The new value
can then be input numerically and WRITE pressed to change the SV or EXT can
be pressed followed by the up and down keys to increment and decrement the
current SV. When the SV is incremented and/or decremented, CLR can be
pressed once to change the SV to the incremented or decremented value but
remaining in the display that appeared when EXT was pressed or CLR can be
pressed twice to return to the original display with the new SV.
This operation can be used to change a SV from designation as a constant to a
word address designation and visa verse.
346
Monitoring Operation and Modifying Data Section 7-1
Key Sequence
TTrrw/Countw
curmntty deployed. * oa !
*
4
—- [N«wSV]
Example The following examples show inputting a new constant, changing from a con-
stant to an address, and incrementing to a new constant.
Inputting New SV and 00080
Changing to Word
Designation
00000
TIM 000
002015RCH
TIM 000
00201 TIM DflTfl
#0123
00201 TIM DfiTfi
T000 #0123 #????
00201 T I M DflTfl Inputting
T000 #0123 #0124 rwwSV.
347
2.
Monitoring Operation and Modifying Data Section 7-1
t
m 00000
TIM 000
I
•WON
00201SRCH
TIM 000
}
00201 TIM DflTfl
f
#0123
i
T
CHQ
00201 T I M DflTfl
T000 #0123 #7777
f
00201DflTfl
4 T090 # 0 1 2 3 #0122
|
00201DflTfl
t T000 # 0 1 2 3 # 0 1 2 3
.._
00201DflTfl
T000 #0123 #0124
*
f
00201DRTfl 7
cm
T000 # 0 1 2 4 #7777
t
00201 T I M DflTfl Returns to original display
0* wit) new SV
#0124
348
BOILER COfTROL PANEL
SAMSUNG R-
cn
O
rn
CD >
mm en
X Tj Z
^ QHP Qr
1 ^
££ 5 CD
Ow
HO
TJH
TI
w r
SOUR
GNIT
F.a
CH
AB
BOI
TR
IP
UAL
SOURCE
JQNITOR
6
33 TI
S
o
3
m TJ
m—.
I
lo
SCOT
OPEN
BLOAER
ISTON V.
> S
mmC
-° , -0 I
m rr
wo
|3
TJ
AMM 1 PecT 04
SAMSUNG ^ ' DRAWING ffl
SAMSUNG ltN5PKT1<>)|
160
SSI
MASTER
(1 200P)
SLAVE
11 201 P)
A
(14115) (1409S) (1410S)
1U
ATM
94 a
v-
(1300S)
6
{1401S) (1404S) (1407S)
M4ST1R
(12(WS)
IS
ONLY
200
. .
BOILER CONTROL PANEL
BOILER CONTROL
*> *
b'.HiER CONTROL PANEL
• 0J mm •
-
B
l—
•
jp^^TrO^ -•*=<> -
Iiin^m
-
• s.
. ill tR CONTROL PAN L
l<
•. ;
?
•
MI Ml1
M ,' 1 , I M VW V.
a;^!^^
1,
t^^
k
! »3 * 1 *,, * *jp 1_J *3
jp *1*_J 3 *i '
It?
jri'l * i * **; * t *^ *J_r'
! t •• . 'I f
*ji * V* i * '
1