Professional Documents
Culture Documents
CONTRACTOR COMPANY
REV DESCRIPTION DATE
PREPARED CHECKED APPROVED REVIEWED APPROVED
A Issued for Internal Review 03-Nov-14 ANR SAN PG
B Issued for Review 28-Nov-14 ANR SAN PG
C Issued for Approval 19-Jan-15 ANR ARY/SAN PG
0 Issued for Design 13-Mar-15 ANR ARY/SAN PG
PERTAMINA EP CEPU
SHEET 2 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
PERTAMINA EP CEPU
SHEET 3 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
Table of Contents
1 INTRODUCTION......................................................................................5
1.1 Scope............................................................................................................................... 5
2 DEFINITIONS AND ABBREVIATIONS..........................................................5
3 REFERENCES..........................................................................................5
4 DESIGN BASIS..........................................................................................7
4.1 Fluid Condition and Properties Data.................................................................................7
4.2 Sizing Basis..................................................................................................................... 7
4.3 Line Sizing Margin............................................................................................................ 7
4.4 Sizing Criteria for Single Phase Liquid Lines....................................................................7
4.5 Pumped Liquid for Salt and Produced Water...................................................................9
4.6 Liquids Flowing by Pressure..........................................................................................10
4.7 Gravity Flow Lines..........................................................................................................10
4.8 Liquids from Drain Boxes...............................................................................................10
4.9 Static Accumulation........................................................................................................11
4.10 Firewater........................................................................................................................ 11
4.11 Other Corrosive Liquids..................................................................................................11
4.12 Drains............................................................................................................................. 11
4.13 Tank Overflows............................................................................................................... 12
4.14 Single Phase Gas Line...................................................................................................12
4.15 Line Sizing Criteria for Two Phase Flow.........................................................................13
4.15.1 Flow Pattern.....................................................................................................13
4.15.2 Erosion.............................................................................................................14
4.15.3 Line Sizing Criteria for Two Phases..................................................................15
4.16 Sizing Criteria for Relief and Depressuring Lines...........................................................15
4.16.1 Relief Valve Inlet Lines.....................................................................................16
4.16.2 Relief Valve Outlet Lines...................................................................................16
4.16.3 Flare Headers and Sub Headers......................................................................17
4.16.4 Flare Stack.......................................................................................................17
PERTAMINA EP CEPU
SHEET 4 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
PERTAMINA EP CEPU
SHEET 5 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
1 INTRODUCTION
Gas Development Project for the Jambaran– Tiung Biru Field is located onshore on the
island of Java, between the cities of Cepu and Bojonegoro. The Processing Facility is
needed to gather gas from various wells, remove or reduce undesirable H2S and CO2
components to acceptable limits, meet sales specifications and safety, transport the gas at
the required pressure, temperature, quantity and quality to the sales point.
1.1 Scope
This document is intended to present the line sizing calculation for Gas Development
Project of Jambaran-Tiung Biru Field in all process and utility unit.
3 REFERENCES
PERTAMINA EP CEPU
SHEET 6 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
4 DESIGN BASIS
PERTAMINA EP CEPU
SHEET 7 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
PERTAMINA EP CEPU
SHEET 8 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
Pump discharge :
up to 20” 5 – 20 1.6 2.0
3 P ≤ 725 psig
5 – 20 3.0 4.0
P > 725 psig
Friction factor should be calculated using pipe roughness as specified in the Table 4.2
below.
Table 4.2 – Roughness value
Roughness
Material / Application
in mm
Carbon Steel non-corroded 0.0018 0.046
PERTAMINA EP CEPU
SHEET 9 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
Roughness
Material / Application
in mm
Stainless Steel for Flare Headers (Hot Rolled,
0.0018 0.046
Longitudinally Welded)
PERTAMINA EP CEPU
SHEET 10 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
while pipes with a diameter of 200 mm (8 inches) and greater shall be designed for 75% full
of liquid.
gu =
[ ρl−ρ g ]
g
ρl = density of liquid (lb/ft3)
ρg = density of gas or vapor (lb/ft3)
g = 32.2 ft/s
D = internal pipe diameter (ft)
Gravity flowlines shall be sized to avoid the formation of siphons and to avoid pulsation and
vibration. One of the following methods can be adopted dependent on the individual
engineering circumstances:
Size the line as self venting as above.
Install a siphon breaker at the system high point.
Size the line for all expected flow rates such that frictional forces offset gravitational
forces thus avoiding sub-atmospheric pressures at the top of the pipe.
Install a back-pressure control near the base of the line.
4.10 Firewater
The design of the firewater piping systems shall be conformed to “Specification for Piping
Material Class”, Doc. No. JTB-SF-L-SPE-900-00005. Pipe flow velocities shall not exceed 6
m/s (20 ft/sec) in any area of the distribution system piping, or any lower velocitiy required
PERTAMINA EP CEPU
SHEET 11 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
due to the properties of the pipe material. Pressure drop in firewater distribution systems
shall be evaluated using PIPENET.
4.12 Drains
To avoid deposits of solid particles, sewage, closed and open drains shall be designed for
the minimum fluid velocities given in Table 7.5 below.
Table 4.5 – Guidelines for Sizing Drain Piping
Max.Velocity
No Service
ft/s (m/s)
1 Sanitary drains 2.6 (0.8)
2 Oily water drains (Open drains) 3.0 (0.9)
3 Other drains 3.6 (1.1)
However, a minimum size of NPS 4” (100) shall be used for the headers and NPS 3” (75
mm) for sub headers.
PERTAMINA EP CEPU
SHEET 12 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
Compressors:
Suction (2) (4)
Discharge -
(3) (4)
Column
Overhead - - 10,000
Stripper
Vapour (5) -
-
Return
Kettle Vapour
Return -
(5) -
Notes:
1) The above indicated line sizing criteria are valid for continuous operation. The pressure
drop in psi/100ft shall be less than 5% of the absolute static pressure for long headers and 10%
for short headers. For intermittent operation, these limits may be exceeded on a case by case
basis.
2) Allowable pressure drop between 0.1 and 0.3 psi/100ft.
3) Allowable pressure drop between 0.2 and 0.5 psi/100ft. In addition to these criteria, the noises
from excessive flowing velocity have also to be considered.
4) Maximum ρ V2 to be comparable with values above.
5) Allowable pressure drop between 0.1 and 0.2 psi/100 ft.
PERTAMINA EP CEPU
SHEET 13 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
4.15.2 Erosion
High velocities in two-phase lines can cause rapid wear by erosion. The velocity at which
erosion may occur is calculated by the formula given in API RP 14E:
PERTAMINA EP CEPU
SHEET 14 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
C
Ve ¿
√ ρm
The density of the gas/liquid mixture, ρm, can be estimated by the following:
ρm= ρg ( 1−l ) +l ρl
Where,
l = liquid volume fraction.
ρg = gas densityliquid (lb/ft3).
ρl = liquid density (lb/ft3).
Alternatively the mixture density can be determined from the HYSYS simulation program.
PERTAMINA EP CEPU
SHEET 15 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
Wellhead flowlines, production manifolds and other lines transporting gas and liquid in two
phase flow where significant pressure drop is available, are generally sized on the basis of
velocity.
Calculation of static head resistance in two phase systems should consider the fluid to be
all liquid since this is likely to occur at some stage of operation. Static gain should be
treated with caution since flashed vapour present may not necessarily recondense in the
downcomer pipe.
Slug flow with resultant pressure pulsation and vibration is to be avoided. Problems are
most likely in lines from exchangers where partial vaporization or condensation has
occurred. In comparison, equilibrium fluids that are continuously flashing with vapour
expansion are usually relatively stable. Where slug flow is expected to be a problem,
consideration should be given to equipment layout, e.g. locate exchanger near terminus so
that the liquid vapour line is as short as possible. In all cases however, it is good
engineering practice to layout piping so that it is self venting to the terminus (i.e. no
pockets).
PERTAMINA EP CEPU
SHEET 16 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
PERTAMINA EP CEPU
SHEET 17 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
5 CALCULATION METHOD
5.1.1 Velocity
The velocity for single gas phase line is calculated based on equation 2.13 API RP 14E:
60 ZQgT
Vg= 2
d P
d=
√ 60 ZQgT
VgP
PERTAMINA EP CEPU
SHEET 18 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
Where,
PERTAMINA EP CEPU
SHEET 19 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
ε = Absolute roughness, ft
D = internal diameter of pipe, ft
fm = Moody friction factor, dimensionless
5.2.1 Velocity
The velocity for single liquid phase line is calculated based on equation 2.1 API RP 14E:
0.012Q1
V 1=
di
2
Note:
d=
√ 0.012Q1
V1
For minimum diameter calculation, used maximal gas velocity for Vg, based on liquid phase line
sizing basis in section 4 above.
Where:
V1 = Average liquid flow velocity, ft/s
Q1 = Liquid flow rate, barrel/day
di = Pipe inside diameter, in
PERTAMINA EP CEPU
SHEET 20 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
0 . 00115 f Ql S l
2
∆ P=
di5
Where:
∆P = Pressure drop, psi/100ft
f = Moody friction factor, dimensionless
di = Pipe inside diameter, in
Q1 = Liquid flow rate, barrel/day
S1 = Liquid specific gravity (water = 1)
PERTAMINA EP CEPU
SHEET 21 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
ρl d i V l
ℜ=
µl
Where:
Re = Reynolds number, dimensionless
ρl = Liquid density, lb/ft3
di = internal diameter of pipe, ft
µl = Liquid viscosity, lb/ft-sec, or centipoises divided by 1488
Vl = Liquid flow velocity, ft/sec
(√ QcVc ) x ( phi4 )
Where:
Qc = Volumetric flow rate, ft/s
Vc = Erosional velocity, ft/s
6 METHODOLOGY
The Line Sizing Calculation using spreadsheet with input data are taken from Heat and
Material Balance Case-2 for process & utility lines, and Case-4 for liquid & mixed phase in
Inlet Separation Unit (221).
7 RESULT
The Sales Gas pipeline from GPF to Pertagas tie-in shall be 20” diameter as recommended
by Flow Assurance Study.
Result of line sizing in process and utility can be shown detail in Appendix A and Appendix
B.
PERTAMINA EP CEPU
SHEET 22 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
APPENDICES
PERTAMINA EP CEPU
SHEET 23 OF 23
REV
DOC. NO. : JTB-SF-P-CAL-900-00003
0
CALCULATION – LINE SIZING
DATE BY CHKD APVD
13-03-2015 ANR SAN/ARY PG
PERTAMINA EP CEPU