You are on page 1of 3

UTILITY CONSUMPTION LIST

STUBB CREEK
GENERAL NOTES & HOLDS
Project Stubb Creek Marginal Field FEED Update Project Originated By SD
Client Universal / SIPEC JOT Checked By CA
Location STUBB CREEK Approved By KT
Job No. JU11867B Revision 0
Doc No. SCPF-PETW-LIS-P-01001 Date 19/01/2012

NOTES:

1. UTILITY WATER IS REQUIRED FOR VESSEL WASH OUT AND UTILITY STATIONS . NORMALLY NO FLOW
2. DELETED.
3. THE GIVEN VALUES FOR UTILITY CONSUMPTION ARE BASED ON NORMAL OPERATING DATA AND DOES NOT INCLUDE DESIGN MARGIN.
4. PEAK MAXIMUM CONSUMPTION
5. PROPANE BOTTLE (BACKUP FOR FUEL GAS) FOR FLARE PILOT
6. PRELIMINARY DATA. FUEL GAS DEMAND FOR FLARE PACKAGE AND PRODUCED WATER TREATMENT PACKAGE TO BE CONFIRMED BY PACKAGE VENDOR.
7. DELETED.
8. THE STATED VALUES ARE BASED ON MAXIMUM DOSAGE RATE.

HOLDS:

1. DELETED.
2. DELETED.
3. UTILISATION OF EPF CHEMICAL INJECTION PUMPS ( CORROSION INHIBITOR & DEMULSIFIER).

Page 2 of 3
UTILITY CONSUMPTION LIST
STUBB CREEK

Project Stubb Creek Marginal Field FEED Update Project Originated By SD


Client Universal / SIPEC JOT Checked By CA
Location STUBB CREEK Approved By KT
Job No. JU11867B Revision 0
Doc No. SCPF-PETW-LIS-P-01001 Date 19/01/2012

Single Consumption Total Consumption


Consumers'
S/No. Description Consumption Unit Qty. Note 3 Note 3 Remarks
Equipment Tag No.
(kg/h) See Unit (kg/h) See Unit
1 G-101201 Emergency Diesel Generator Diesel Oil Liter /h 1 300.0 Discontinuous
2 P-10302A/B Fire Water Pumps Diesel Oil Liter /h 2 96.0 Discontinuous, one standby
3 G-101101A/B/c Gas Engine Generators Fuel Gas Sm³/h 3 860.0 Two continuous, one standby
4 H-30401 Stabiliser Reboiler Fired Heater Fuel Gas Sm³/h 1 244.0 Continuous
Blanketing Gas / Flare Purge / Discontinuous ,
Fuel Gas Sm³/h N/A 250.0
5 Produced Water treatment Package Note 6
6 CPF Fire Water Users Fire Water m³/h 2 844.0 Discontinuous, one standby
7 V-30303 Desalter system Makeup Water m³/h 1 7.0 Continuous
8 QAT-30201/2 Water Injection Wells Makeup Water m³/h 1 100.0 Continuous , Note 4
9 CPF Process Users Utility Water m³/h N/A 16.0 Discontinuous , Note 1
10 Control Valves, SDVs, On/Off Valves, etc. Instrument Air Nm³/h N/A 170.0 Continuous
11 A-30301/V-30301 1st Stage Separator Demulsifier Liter /h 1 1.9 Discontinuous , Note 8
12 V-30304 Desalter Demulsifier Liter /h 1 7.1 Discontinuous , Note 8
13 A-30301/V-30301 Inlet & Test Manifold Corrosion Inhibitor Liter /h 1 1.2 Discontinuous , Note 8
14 A-35101 Produced Water Treatment Reverse Demulsifier Liter /h 1 1.2 Discontinuous , Note 8
15 A-35101 Produced Water Treatment Flocculant Liter /h 1 1.6 Discontinuous , Note 8
16 A-10105 /A-10103 Makeup Water Treatment Unit Antifoam Liter /h 1 3.3 Discontinuous , Note 8
17 A-10105 /A-10103 Makeup Water Treatment Unit Oxygen scavenger Liter /h 1 3.3 Discontinuous , Note 8
18 A-10105 /A-10103 Makeup Water Treatment Unit Flucculant Liter /h 1 5.2 Discontinuous , Note 8
19 A-10105 /A-10103 Makeup Water Treatment Unit Scale Inhibitor Liter /h 1 6.6 Discontinuous , Note 8
20 A-10105 /A-10103 Makeup Water Treatment Unit Sodium Hypochlorite Liter /h 1 32.5 Discontinuous , Note 8
21 Propane Bottle Propane Sm³/h 1 1.0 Discontinuous , Note 5
22
23
24
25

Page 3 of 3