Given:

𝑍𝑠 = 𝑗0.05; 𝑍𝑐𝑎𝑝 = −𝑗0.83; 𝑉 = 1.0 𝑝𝑢; 100 𝑀𝑉𝐴 𝑏𝑎𝑠𝑒

Then:
𝑗0.05 ∗ −𝑗0.83
𝑍𝑆 ||𝑍𝑐𝑎𝑝 = = 𝑗0.053205
𝑗0.05 − 𝑗0.83

1.0 𝑝𝑢𝑉
𝐼𝐹 = = −𝑗18.7952 𝑝𝑢
𝑗0.053205

Current divider, Cap:


𝑍𝑆 𝑗0.05
𝐼𝑐𝑎𝑝 = 𝐼𝐹 ∗ = −𝑗18.7952 𝑝𝑢 ∗ = 𝑗1.20482 𝑝𝑢
𝑍𝑆 + 𝑍𝑐𝑎𝑝 𝑗0.05 − 𝑗0.83

100 𝑀𝑉𝐴
𝐼𝑏𝑎𝑠𝑒 = = 358.603 𝐴
161 𝑘𝑉⁄√3

𝐼𝑐𝑎𝑝 = 𝑗1.20482 𝑝𝑢 ∗ 358.603 𝐴 = 432∠90° 𝐴

Current divider, Source:


𝑍𝑐𝑎𝑝 −𝑗0.83
𝐼𝑐𝑎𝑝 = 𝐼𝐹 ∗ = −𝑗18.7952 𝑝𝑢 ∗ = −𝑗20.0 𝑝𝑢
𝑍𝑆 + 𝑍𝑐𝑎𝑝 𝑗0.05 − 𝑗0.83

𝐼𝑐𝑎𝑝 = −𝑗20.0 𝑝𝑢 ∗ 358.603 𝐴 = 7172∠ − 90° 𝐴

Note: conventions for these are from the equipment terminals towards the fault.