You are on page 1of 1

HYDRANT FLOW TEST DATA

HYDRANT ID S-19 City CITY OF DATE OF TEST xxxxxxx

LOCATION DESCRIPTION Flow: Hydrant-xxx - 23rd Ave


Residual: Hydrant-xxx - 23rd Ave

STATIC 48 PSI RESIDUAL 38 PSI FLOW 1,921 GPM

CALCULATED AT RESIDUAL 20 PSI FLOW 3,350 GPM

TEST BY xxxxxxxxxxxxxxxxxx

HYDRANT FLOW GRAPH Column N


160

150

140

130

120

110

100
P.S.I.

90

80

70

60

50
1, 48
40
2, 38
30

20 3, 20

10

0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200 3400 3600
FLOW - GPM

CREATED BY: ICC

LAST REV.: 11-20-03